PLM-Aging Inspection | 4/27/2020 | 4/27/2020 | 4/27/2020 | | PASS |
Matt Wrobel
|
|
|
|
DOC - Permit Finaled | 4/27/2020 | 4/27/2020 | 4/27/2020 | P | PASS |
Matt Wrobel
|
|
|
|
Water and/or Sewer | 8/4/2019 | 8/5/2019 | 8/5/2019 | A | PASS |
Matt Wrobel
|
|
|
our inspection is from the water meter to with in 5 foot of the house. tie into house is to be by other.. Phone #: ###-#### Inspection requested via web by shannon boepple do not hook to house without proper permit
|
Final | 7/30/2019 | 7/31/2019 | 7/31/2019 | A | FAIL |
Matt Wrobel
|
|
|
please call or text me at 208 713 2289 with the results .. I was over at another job most of today , I stopped by 9900 McMillan job this afternoon , and seen that the home owners clean up guy backfilled most all of my water line trench . I had it shaded with sand and mostly opened for inspection.. I cleaned it out were it goes into the house so you can see the connection. please let me know if you need me to bring an excavator back out there and do any thing for you and I will .. as well it is 1 solid piece of pipe .. THANKS ,, Phone #: ###-#### Inspection requested via web by shannon boepple 1 water service trench must be left open for inspection 2. cannot verrify connection at meter 3. water service must be 42 inches deep per ispc 4. minimum 16 guage blue tracer wire must run entire length of wayter service 5. need approved transition fitting at pex pole connection by house.
|
Issue PAID IN FULL permit | | | 7/29/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/29/2019 | | DONE |
|
|
|
This permit was created on the web by shannon boepple
|