Final | 4/9/2020 | 4/13/2020 | 4/13/2020 | P | PASS |
Daryl Spivey
|
|
|
Please call Jimmy 30 min prior to arrival for access Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Final | 4/8/2020 | 4/9/2020 | 4/9/2020 | A | PART |
Daryl Spivey
|
|
|
please call Jimmy 30 min prior to arrival for access.
thanks, Phone #: ###-#### Inspection requested via web by Nicholas Paige need to test b/f's and repipe T&P. cannot use flex connector nand run seperate from pan drain...........ds
|
Plumbing Rough-in | 4/8/2020 | 4/8/2020 | 4/8/2020 | P | PASS |
Daryl Spivey
|
|
|
|
Plumbing Rough-in | 2/5/2020 | 2/6/2020 | 2/6/2020 | A | PART |
Matt Wrobel
|
|
|
please call Jake 30 min prior so he can meet you onsite
thank you Phone #: ###-#### Inspection requested via web by Nicholas Paige this completes the water rough
|
Plumbing Rough-in | 1/28/2020 | 1/29/2020 | 1/29/2020 | A | PART |
Daryl Spivey
|
|
|
please contact Jake prior to arrival for access Phone #: ###-#### Inspection requested via web by Nicholas Paige water in restrooms and waste and vent on brk room ok.........still have some water to do..........ds
|
Plumbing Rough-in | 1/10/2020 | 1/13/2020 | 1/13/2020 | A | PART |
Daryl Spivey
|
|
|
please call jake for access and work location prior to arriving. thanks, Phone #: ###-#### Inspection requested via web by Nicholas Paige ok in walls to cover...4th floor....ds
|
Other | 12/17/2019 | 12/18/2019 | 12/18/2019 | A | PART |
Dan Ediger
|
|
|
Please call Jake Prior to arriving so he can be found onsite. ###-####
this is a conference inspection Phone #: ###-#### Inspection requested via web by Nicholas Paige 1. Page P2.1B shows 2" vents running horizontal more than 40 feet. Change to 2-1/2 or 3". 2. The existing drinking fountain was plumbed without a vent. Repipe to include a vent. 3. The men's rr urinals are wet vented on-top of the woman's wc's. Change carriers to 3' or re-pipe off the carriers.
|
Other | 12/17/2019 | 12/17/2019 | 12/17/2019 | P | NR |
Dan Ediger
|
|
|
This is a conference inspection to go over some job specific questions.
Phone #: ###-#### Inspection requested via web by Nicholas Paige Plumbers not on site 2pm
|
Issue PAID IN FULL permit | | | 12/17/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/17/2019 | | DONE |
|
|
|
This permit was created on the web by Nicholas Paige
|