Sprinkler (Final) | 4/16/2020 | 4/17/2020 | 4/17/2020 | P | PASS |
Eric Strole
|
|
|
Had to bring DC backflow to code with a PVB. Moved it from the between street and sidewalk to next to the house. I have tested the new PVB assembly it passed Air inlet 2.6, opened fully the check valve held at 1.7. Phone #: ###-#### Inspection requested via web by Brian White
|
Issue PAID IN FULL permit | | | 4/13/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/13/2020 | | DONE |
|
|
|
This permit was created on the web by Brian White
|