INSP - Final | 11/17/1998 | 11/18/1998 | 11/18/1998 | P | PASS |
Jim Soden
|
|
|
11/18/98 347 -
|
Issue PAID IN FULL permit | | | 8/16/1996 | | |
|
|
|
|
(F) Reprint permit | | | 7/25/1996 | | |
|
|
|
|
INSP - Final | 7/23/1996 | 7/23/1996 | 7/23/1996 | P | FAIL |
Jim Soden
|
|
|
MITCHELL PLUMBING RELEASED FROM JOB BY OWNER. FAILED PER JIM SODEN
|
INSP - Water lines | 7/19/1996 | 7/22/1996 | 7/22/1996 | A | FAIL |
Jim Soden
|
|
|
07/19/96 347 - FAIL R/I 7/23/6 347 support both shr valves extend outside vent above roof 6"--t&p discharge line required(o/k to discharge into w/b---150# pressure test required on hot and cold polybutylene water piping---water leaks at (test) valve on north side of basement and w/b----resize water piping per code (low pressure range)
|
INSP - Ground work | 7/9/1996 | 7/9/1996 | 7/9/1996 | P | PASS |
Jim Soden
|
|
|
07/09/96 347 - g/w o/k 7/9/6 347
|
Issue FEE-DUE permit | | | 7/9/1996 | | |
|
|
|
|
Application received | | | 7/9/1996 | | |
|
|
|
|