Permit Information
Permit NumberBLD00-00498
StatusFinaled
Name JAY BLACKER (OWN REP)
Site Address 1501 S FEDERAL WAY (1ST FLR)
Project NameVIEW POINT-1ST FLR
Customer Number 
ePlanReviewNo
Description
(TOUCH AMERICA - BOISE POINT OF PRESENCE) This building is not fire sprinklered. To remodel a 1,174 square foot room on the first floor of an existing office building. The room will be used as a fiber-optics equipment facility (control room and telephone equipment room). Outside, the work is to include a backup generator, two condensing units, and an exterior concrete equipment pad. Inside, the work is to include two air handling units, an interior unistrut grid, a UPS lead-acid battery system, a 2-hr shaft to the roof, and miscellaneous equipment all per approved drawings and plan review conditions on file. PC-151-00 **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/31/20018/31/20018/31/2001PPASS
DetailsJim Storey
Tammy, ###-#### - Touch America - Cathy has the card final ok 8/31/2001 2:22:52 PM
Permanent Occupancy 8/31/20018/31/2001 DONE
Details
FIRE-Final Inspection8/30/20018/30/20018/30/2001APASS
DetailsRick Jackson
Added by Inspector: 409 On 8/30/2001 8:46:27 AM
BLD-Conference6/19/20016/21/20016/21/2001APASS
DetailsSteven Webb
Tammy @ ###-#### wants to meet with you, Rick Jackson & Dave Lightfoot @ 10:00.
FIRE-Conference6/19/20016/19/20016/19/2001AFAIL
DetailsRick Jackson
Tammy @ ###-#### wants to meet w/you, Jim Storey & Dave Lightfoot @ 10:00. need alarm plans submitted and to test them 6/21/2001 12:50:14 PM
BLD-Final4/4/20014/4/20014/4/2001PFAIL
DetailsJim Storey
tammy ###-#### fire is also going out need all other insp. 4/4/2001 2:48:45 PM
FIRE-Final Inspection4/4/20014/4/20014/4/2001PFAIL
DetailsRick Jackson
tammy ###-#### lead acid battery sign on hallway door; rear door hardware; dampers at shaft; alarm test required with alarm plans; extinguishers require current inspection tags 4/4/2001 3:35:46 PM
BLD-Framing/Rough-in6/9/20006/9/20006/9/2000PFAIL
DetailsJim Storey
###-#### shaft wall studs and butt lap. 6/9/00 2:34:07 PM