BLD-Final | 2/4/2002 | 2/4/2002 | 2/4/2002 | P | PASS |
Tom Arcoraci
|
|
|
cecil ###-#### ok for perm occ 2/4/2002 3:08:30 PM
|
Permanent Occupancy | | 2/4/2002 | 2/4/2002 | | DONE |
|
|
|
|
FIRE-Final Inspection | 1/31/2002 | 2/1/2002 | 2/1/2002 | P | PASS |
Troy Cobbley
|
|
|
Fire life/safety OK. Fire alarm system tested OK. Fire sprinkler system OK. Ok for perm occ. 2/1/2002 3:36:15 PM
|
FIRE-Final Inspection | 1/22/2002 | 1/24/2002 | 1/24/2002 | A | FAIL |
Troy Cobbley
|
|
|
provide fire extinguisher in penthouse and basement electrical room, elevator recall does not work, a bush is obstructing the FDC, paint curbing per sheet A1.0, place no parking signs per note 13, provide secondary containment verification for emergency generator, provide offsite sprinkler monitoring, provide floor signage and use stairs signs per note 28 and 29, install door at the ground level south shell exit, provide door on 2nd floor electrical room, verify life/safety and fire alarm and fire sprinklers at end of link and in Meditation room, provide "door to remain unlocked" sticker on both main exit doors 1/25/2002 3:06:12 PM
|