Permit Information
Permit NumberBLD00-01933
StatusFinaled
Name WASHINGTON TRUST BANK
Site Address 901 W BANNOCK ST
Project Name9TH & BANNOCK GARAGE
Customer Number 
ePlanReviewNo
Description
To remodel for a new 5,500 sq.ft. tenant in existing building for bank/office use and remodel the existing drive through teller areas outside the tenant space within the drive through parking area per approved plans on file. The tenant space has a mezzanine for mechanical use. Main floor is 4,800 sq.ft. Mezzanine is 700 sq.ft. Work to include demolishing some interior walls and a portion of the mezzanine, upgrading restrooms to meet current accessibility standards, new storefront windows and entry, construct new small portion of mezzanine floor and new small portion of the supporting bearing wall, upgrading existing mezzanine floor and existing supporting bearing wall to meet two-hour fire rating, new portions of existing one-hour fire rated corridor, footings for new vault, masonry wall infill work, new interior walls with doors and windows, relocating existing interior stairway, interior finish, new suspended ceiling, new alarm system, new plumbing work, new mechanical work, and new electrical work. NOTE: This tenant space will have a new fire alarm system installed under this permit. Plans and materials data must be submitted and reviewed meeting the requirements of UFC 1001.3. A fire permit must be issued by the Fire Department prior to any installation work of the same. (P.C.#531-00) JCB
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 10/27/200010/27/2000 DONE
Details
BLD-Final10/25/200010/26/200010/26/2000PPART
DetailsJim Storey
Don, ###-#### ok pending ele sign off for perm. 10/26/2000 2:04:28 PM
FIRE-Final Inspection10/25/200010/26/200010/26/2000APASS
DetailsRick Jackson
Don, ###-#### - reinspect
FIRE-Final Inspection10/24/200010/25/200010/25/2000AFAIL
DetailsRick Jackson
Don Bryan, ###-#### alarms not complete; need damper at ceiling in janitors closet; exit signs; painted fusible links on dampers in bathrooms; c/n issued 10/25/2000 1:44:43 PM
BLD-Wall cover10/10/200010/11/200010/11/2000AFAIL
DetailsJim Storey
Don Bryan, ###-#### supplys not supported / lights not wired / two dead bolts not allowed at main entry. 10/11/2000 4:18:16 PM
BLD-Framing/Rough-in9/28/20009/29/20009/29/2000APASS
DetailsJim Storey
Don Bryan, ###-#### ceilling fire stopped and ok for framing at attic. 9/29/2000 2:50:23 PM
BLD-Framing/Rough-in9/18/20009/18/20009/18/2000PPART
Details
Don Bryan, ###-#### needto see firecaulking of the 2-hr ceiling prior to any fixture install 9/18/2000 2:35:50 PM
BLD-Framing/Rough-in9/12/20009/13/20009/13/2000PNR
Details
Don Bryan, ###-#### work not complete enough for insp to be made 9/14/2000 9:23:21 AM
BLD-Framing/Rough-in9/8/20009/8/20009/8/2000PPART
Details
Don Bryan, ###-#### ok to cover new ceiling only 9/8/2000 2:08:30 PM
BLD-Conference9/5/20009/5/20009/5/2000PPART
Details
###-#### ok for thefront partition walls, need assy fr the 2-hr walls and deck as work has proceeded farther than planned 9/6/2000 9:37:51 AM
BLD-Framing/Rough-in8/29/20008/30/20008/30/2000PFAIL
DetailsJim Storey
Don ###-#### arch. to address 2 hr. ceilling continuity of all walls top plates and ele,plm intagraty. 8/31/2000 12:22:40 PM
BLD-Foundation8/10/20008/11/20008/11/2000APART
Details
CONCRETE SLAB-- DON ###-#### sp insp not req per keith jones designd for 2500 psi 8/14/2000 8:12:50 AM
BLD-Framing/Rough-in8/8/20008/8/20008/8/2000PPART
Details
Don ###-#### ok to hang rock on the demising wall with elec ok,s 8/8/2000 4:13:15 PM