Permanent Occupancy | | 10/27/2000 | 10/27/2000 | | DONE |
|
|
|
|
BLD-Final | 10/25/2000 | 10/26/2000 | 10/26/2000 | P | PART |
Jim Storey
|
|
|
Don, ###-#### ok pending ele sign off for perm. 10/26/2000 2:04:28 PM
|
FIRE-Final Inspection | 10/25/2000 | 10/26/2000 | 10/26/2000 | A | PASS |
Rick Jackson
|
|
|
Don, ###-#### - reinspect
|
FIRE-Final Inspection | 10/24/2000 | 10/25/2000 | 10/25/2000 | A | FAIL |
Rick Jackson
|
|
|
Don Bryan, ###-#### alarms not complete; need damper at ceiling in janitors closet; exit signs; painted fusible links on dampers in bathrooms; c/n issued 10/25/2000 1:44:43 PM
|
BLD-Wall cover | 10/10/2000 | 10/11/2000 | 10/11/2000 | A | FAIL |
Jim Storey
|
|
|
Don Bryan, ###-#### supplys not supported / lights not wired / two dead bolts not allowed at main entry. 10/11/2000 4:18:16 PM
|
BLD-Framing/Rough-in | 9/28/2000 | 9/29/2000 | 9/29/2000 | A | PASS |
Jim Storey
|
|
|
Don Bryan, ###-#### ceilling fire stopped and ok for framing at attic. 9/29/2000 2:50:23 PM
|
BLD-Framing/Rough-in | 9/18/2000 | 9/18/2000 | 9/18/2000 | P | PART |
|
|
|
Don Bryan, ###-#### needto see firecaulking of the 2-hr ceiling prior to any fixture install 9/18/2000 2:35:50 PM
|
BLD-Framing/Rough-in | 9/12/2000 | 9/13/2000 | 9/13/2000 | P | NR |
|
|
|
Don Bryan, ###-#### work not complete enough for insp to be made 9/14/2000 9:23:21 AM
|
BLD-Framing/Rough-in | 9/8/2000 | 9/8/2000 | 9/8/2000 | P | PART |
|
|
|
Don Bryan, ###-#### ok to cover new ceiling only 9/8/2000 2:08:30 PM
|
BLD-Conference | 9/5/2000 | 9/5/2000 | 9/5/2000 | P | PART |
|
|
|
###-#### ok for thefront partition walls, need assy fr the 2-hr walls and deck as work has proceeded farther than planned 9/6/2000 9:37:51 AM
|
BLD-Framing/Rough-in | 8/29/2000 | 8/30/2000 | 8/30/2000 | P | FAIL |
Jim Storey
|
|
|
Don ###-#### arch. to address 2 hr. ceilling continuity of all walls top plates and ele,plm intagraty. 8/31/2000 12:22:40 PM
|
BLD-Foundation | 8/10/2000 | 8/11/2000 | 8/11/2000 | A | PART |
|
|
|
CONCRETE SLAB-- DON ###-#### sp insp not req per keith jones designd for 2500 psi 8/14/2000 8:12:50 AM
|
BLD-Framing/Rough-in | 8/8/2000 | 8/8/2000 | 8/8/2000 | P | PART |
|
|
|
Don ###-#### ok to hang rock on the demising wall with elec ok,s 8/8/2000 4:13:15 PM
|