BLD-Conference | 2/25/2002 | 2/25/2002 | 2/25/2002 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/25/2002 4:19:26 PM w/ 409 re final...fire ok
|
BLD-Final | 2/25/2002 | 2/25/2002 | 2/25/2002 | P | PASS |
Carl Dependahl
|
|
|
Cathy has the card; struct ok for c/o 2/25/2002 4:21:30 PM
|
Permanent Occupancy | | 2/25/2002 | 2/25/2002 | | DONE |
|
|
|
|
FIRE-Alarm Testing | 2/5/2002 | 2/6/2002 | 2/7/2002 | A | CANC |
Rick Jackson
|
|
|
###-#### BRETT per Dave Miller - not to sign for perm occupancy pending resolution of kitchen exhaust system 2/7/2002 3:55:43 PM
|
BLD-Final | 2/4/2002 | 2/5/2002 | 2/5/2002 | P | NR |
Carl Dependahl
|
|
|
christina-- ###-#### fn occ
|
FIRE-Final Inspection | 2/4/2002 | 2/5/2002 | 2/5/2002 | A | NR |
Rick Jackson
|
|
|
fn fire christina ###-#### will reschedule for 2/6 2/5/2002 3:31:27 PM
|
BLD-Conference | 1/28/2002 | 1/28/2002 | 1/28/2002 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/28/2002 9:46:30 AM w/GS re Schott's...south exit has had panic hdwe. installed
|
BLD-Final | 12/17/2001 | 12/18/2001 | 12/18/2001 | A | NR |
Carl Dependahl
|
|
|
BRET ###-####
|
BLD-Final | 12/18/2001 | 12/18/2001 | 12/18/2001 | P | NR |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 12/18/2001 11:44:00 AM ###-#### Brett...recall 12/18/2001 12:11:39 PM
|
BLD-Final | 12/18/2001 | 12/18/2001 | 12/18/2001 | P | NR |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 12/18/2001 2:37:55 PM ###-#### bret...need remove add'l latch at exit 12/18/2001 4:42:32 PM
|
BLD-Final | 11/29/2001 | 11/29/2001 | 11/29/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 11/29/2001 2:15:38 PM 2nd c/n re south exit doors, resolve grease duct issues; Notice & Order issued to complete c/n items or vacate (total 30 days)
|
BLD-Conference | 10/19/2001 | 10/19/2001 | 10/19/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 10/19/2001 2:27:01 PM w GS...need make corrections at exit door asap
|
BLD-Conference | 10/16/2001 | 10/16/2001 | 10/16/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 10/16/2001 2:01:33 PM w/ Brett re prior c/n
|
BLD-Conference | 10/9/2001 | 10/9/2001 | 10/9/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 10/9/2001 8:43:48 AM w/ GS re meeting w/ Ken Howell & Dave Miller...chimney/grease duct to be evaluated by Creighton Eng'g...keep c/n
|
BLD-Conference | 9/25/2001 | 9/25/2001 | 9/25/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 9/25/2001 4:52:41 PM re: Complaints of removal of exit & some exterior illumination; exit light must be provided, exterior is subject to "P&Z" or Historic review.
|
BLD-Conference | 8/28/2001 | 8/28/2001 | 8/28/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/28/2001 8:31:18 AM w/ Dave M & GS, re schotts grease duct
|
BLD-Conference | 8/20/2001 | 8/21/2001 | 8/21/2001 | A | PART |
Carl Dependahl
|
|
|
As per our phone call; W/ GS, need Fire Dept. clarification re grease duct. Keep c/n re exit door. 8/22/2001 10:09:28 AM
|
BLD-Conference | 8/17/2001 | 8/17/2001 | 8/17/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/17/2001 10:31:33 AM w/Christina re exit door, keep c/n.
|
BLD-Conference | 8/16/2001 | 8/16/2001 | 8/16/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/16/2001 8:08:17 AM w/ P Schott re c/n, UBC 1007.2.5 & 1003.3.1.1 re exit doors
|
BLD-Final | 8/14/2001 | 8/15/2001 | 8/15/2001 | P | FAIL |
Carl Dependahl
|
|
|
FN OCC KRISTINA- ###-#### c/n re exit door; partial insp only, need resolve kitchen exhaust issues w BFD, obtain all other perm ok's. 8/15/2001 1:17:24 PM
|
BLD-Framing/Rough-in | 8/1/2001 | 8/3/2001 | 8/3/2001 | A | NR |
Carl Dependahl
|
|
|
unable to contact; keep c/n (to meet w/ door hdwe sales at site ... called Brett to ask to reset insp 8/8/2001 4:35:41 PM 8/8/2001 4:36:34 PM
|
BLD-Conference | 7/11/2001 | 7/11/2001 | 7/11/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 7/11/2001 11:05:25 AM w/ Brett re south exit mod. install permanent door stop so doors don't conflict
|
BLD-Conference | 6/11/2001 | 6/11/2001 | 6/11/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 6/11/2001 2:18:03 PM w/ Sam Rogers...req'd exit should be ok if doorstop made permanent or appropriate method of blocking or coordinating door swing at "conflicting" doors to exterior
|
BLD-Final | 6/11/2001 | 6/11/2001 | 6/11/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 6/11/2001 4:25:41 PM Per UBC 1007 .2.5. install panic or "3-point" latch,(or approved equal) c/n issued to Peter Schott; also need permanent door stop from bsmt/banquet rm. exit
|
BLD-Final | 5/22/2001 | 5/23/2001 | 5/23/2001 | A | PART |
Jim Storey
|
|
|
Brett ###-#### panic hard ware back ordered for lobby exit to be maintaned/ handrail in 108 temp to be rechecked on perm instaltion. occ load signs temp to be check at perm occ. 5/23/2001 10:03:03 AM
|
FIRE-Final Inspection | 5/23/2001 | 5/23/2001 | 5/23/2001 | P | FAIL |
Rick Jackson
|
|
|
Brett ###-#### still on TCO. gas valve operated properly for kitchen hood system; door hardware still not compliant for bar area; exit signs need repair in banquest room; extinguishers need to hung and current inspection tag 5/23/2001 2:23:24 PM
|
BLD-Final | 5/22/2001 | 5/22/2001 | 5/22/2001 | P | FAIL |
Jim Storey
|
|
|
###-#### handrail and occ signage/ panic hardware to lobby pending fire sign off. 5/22/2001 4:14:08 PM
|
FIRE-Final Inspection | 5/22/2001 | 5/22/2001 | 5/22/2001 | P | PART |
Rick Jackson
|
|
|
###-#### Brett per agreement with Dave Miller and owner the kitchen system to be reviewed by engineer; okay to occupy bar 5/23/2001 9:12:15 AM
|
BLD-Final | 5/21/2001 | 5/21/2001 | 5/21/2001 | P | NR |
Carl Dependahl
|
|
|
###-#### Brett
|
FIRE-Final Inspection | 5/21/2001 | 5/21/2001 | 5/21/2001 | P | NR |
Rick Jackson
|
|
|
Brett ###-####
|
BLD-Framing/Rough-in | 4/17/2001 | 4/18/2001 | 4/18/2001 | A | CANC |
Jim Storey
|
|
|
cover for kitchen Ron ###-####
|
BLD-Conference | 4/17/2001 | 4/17/2001 | 4/17/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 4/17/2001 5:47:05 PM w/ bldr, owner (Schotts), hvac installer, etc.re kitchen finals
|
BLD-Conference | 4/9/2001 | 4/9/2001 | 4/9/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 4/9/2001 1:54:25 PM w/ contractor re c/n...& w/ Rick J. & GS re range grease duct/shaft...not part of project???
|
BLD-Conference | 4/3/2001 | 4/3/2001 | 4/3/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 4/3/2001 9:33:58 AM w/ Cary of A-1 lock...need approved plans for determination of hdwe...have plans onsite.
|
BLD-Framing/Rough-in | 3/29/2001 | 3/29/2001 | 3/29/2001 | P | PART |
Tom Arcoraci
|
|
|
1st floor ###-#### wip ok to cover lid in office behind elevator 3/29/2001 2:25:47 PM
|
BLD-Conference | 3/20/2001 | 3/20/2001 | 3/20/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 3/20/2001 10:02:27 AM w/ bldr re firestops at lids
|
BLD-Framing/Rough-in | 3/15/2001 | 3/16/2001 | 3/16/2001 | A | PART |
Carl Dependahl
|
|
|
1st floor ###-####; restaurant area lid ok, wine bar area lid only ok 3/16/2001 10:45:49 AM
|
BLD-Framing/Rough-in | 3/6/2001 | 3/7/2001 | 3/7/2001 | A | PART |
Carl Dependahl
|
|
|
###-#### ok to cover main bar area only 3/7/2001 4:28:33 PM
|
BLD-Framing/Rough-in | 3/6/2001 | 3/6/2001 | 3/6/2001 | P | PART |
Carl Dependahl
|
|
|
###-####; walls ok 3/6/2001 2:48:06 PM
|
BLD-Conference | 12/13/2000 | 12/14/2000 | 12/14/2000 | A | FAIL |
Carl Dependahl
|
|
|
c/n issued for PROFIT meeting 12/14/2000 2:42:45 PM
|