Permit Information
Permit NumberBLD00-02175
StatusFinaled
Name IDANHA PUB AND GRILL
Site Address 928 W MAIN ST
Project NameIDANHA
Customer Number 
ePlanReviewNo
Description
(IDANHA PUB & GRILL) This building is fire sprinklered, under the provisions of the 1994 UCBC, to allow it to be 10 feet and 2 stories too tall AND to be over area. To construct a bar (1,450 square feet) and a wine bar (500 square feet) on the first floor (Southwest corner) of the Idanha Building. Work is to include interior non-bearing walls, interior windows, interior doors, exterior doors, a new structural header, and millwork all per approved drawings, engineering, and plan review conditions on file. The fire sprinkler system shall comply with NFPA 13-1996 as regulated by the Fire Department. The maximum allowable occupant load of "Bar 108" (87) shall be posted near the main exit. PC-625-00 **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Conference2/25/20022/25/20022/25/2002PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 2/25/2002 4:19:26 PM w/ 409 re final...fire ok
BLD-Final2/25/20022/25/20022/25/2002PPASS
DetailsCarl Dependahl
Cathy has the card; struct ok for c/o 2/25/2002 4:21:30 PM
Permanent Occupancy 2/25/20022/25/2002 DONE
Details
FIRE-Alarm Testing2/5/20022/6/20022/7/2002ACANC
DetailsRick Jackson
###-#### BRETT per Dave Miller - not to sign for perm occupancy pending resolution of kitchen exhaust system 2/7/2002 3:55:43 PM
BLD-Final2/4/20022/5/20022/5/2002PNR
DetailsCarl Dependahl
christina-- ###-#### fn occ
FIRE-Final Inspection2/4/20022/5/20022/5/2002ANR
DetailsRick Jackson
fn fire christina ###-#### will reschedule for 2/6 2/5/2002 3:31:27 PM
BLD-Conference1/28/20021/28/20021/28/2002APASS
DetailsCarl Dependahl
Added by Inspector: 340 On 1/28/2002 9:46:30 AM w/GS re Schott's...south exit has had panic hdwe. installed
BLD-Final12/17/200112/18/200112/18/2001ANR
DetailsCarl Dependahl
BRET ###-####
BLD-Final12/18/200112/18/200112/18/2001PNR
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 12/18/2001 11:44:00 AM ###-#### Brett...recall 12/18/2001 12:11:39 PM
BLD-Final12/18/200112/18/200112/18/2001PNR
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 12/18/2001 2:37:55 PM ###-#### bret...need remove add'l latch at exit 12/18/2001 4:42:32 PM
BLD-Final11/29/200111/29/200111/29/2001PFAIL
DetailsCarl Dependahl
Added by Inspector: 340 On 11/29/2001 2:15:38 PM 2nd c/n re south exit doors, resolve grease duct issues; Notice & Order issued to complete c/n items or vacate (total 30 days)
BLD-Conference10/19/200110/19/200110/19/2001PPART
DetailsCarl Dependahl
Added by Inspector: 340 On 10/19/2001 2:27:01 PM w GS...need make corrections at exit door asap
BLD-Conference10/16/200110/16/200110/16/2001PPART
DetailsCarl Dependahl
Added by Inspector: 340 On 10/16/2001 2:01:33 PM w/ Brett re prior c/n
BLD-Conference10/9/200110/9/200110/9/2001APASS
DetailsCarl Dependahl
Added by Inspector: 340 On 10/9/2001 8:43:48 AM w/ GS re meeting w/ Ken Howell & Dave Miller...chimney/grease duct to be evaluated by Creighton Eng'g...keep c/n
BLD-Conference9/25/20019/25/20019/25/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 9/25/2001 4:52:41 PM re: Complaints of removal of exit & some exterior illumination; exit light must be provided, exterior is subject to "P&Z" or Historic review.
BLD-Conference8/28/20018/28/20018/28/2001APASS
DetailsCarl Dependahl
Added by Inspector: 340 On 8/28/2001 8:31:18 AM w/ Dave M & GS, re schotts grease duct
BLD-Conference8/20/20018/21/20018/21/2001APART
DetailsCarl Dependahl
As per our phone call; W/ GS, need Fire Dept. clarification re grease duct. Keep c/n re exit door. 8/22/2001 10:09:28 AM
BLD-Conference8/17/20018/17/20018/17/2001APASS
DetailsCarl Dependahl
Added by Inspector: 340 On 8/17/2001 10:31:33 AM w/Christina re exit door, keep c/n.
BLD-Conference8/16/20018/16/20018/16/2001APASS
DetailsCarl Dependahl
Added by Inspector: 340 On 8/16/2001 8:08:17 AM w/ P Schott re c/n, UBC 1007.2.5 & 1003.3.1.1 re exit doors
BLD-Final8/14/20018/15/20018/15/2001PFAIL
DetailsCarl Dependahl
FN OCC KRISTINA- ###-#### c/n re exit door; partial insp only, need resolve kitchen exhaust issues w BFD, obtain all other perm ok's. 8/15/2001 1:17:24 PM
BLD-Framing/Rough-in8/1/20018/3/20018/3/2001ANR
DetailsCarl Dependahl
unable to contact; keep c/n (to meet w/ door hdwe sales at site ... called Brett to ask to reset insp 8/8/2001 4:35:41 PM 8/8/2001 4:36:34 PM
BLD-Conference7/11/20017/11/20017/11/2001APART
DetailsCarl Dependahl
Added by Inspector: 340 On 7/11/2001 11:05:25 AM w/ Brett re south exit mod. install permanent door stop so doors don't conflict
BLD-Conference6/11/20016/11/20016/11/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 6/11/2001 2:18:03 PM w/ Sam Rogers...req'd exit should be ok if doorstop made permanent or appropriate method of blocking or coordinating door swing at "conflicting" doors to exterior
BLD-Final6/11/20016/11/20016/11/2001PFAIL
DetailsCarl Dependahl
Added by Inspector: 340 On 6/11/2001 4:25:41 PM Per UBC 1007 .2.5. install panic or "3-point" latch,(or approved equal) c/n issued to Peter Schott; also need permanent door stop from bsmt/banquet rm. exit
BLD-Final5/22/20015/23/20015/23/2001APART
DetailsJim Storey
Brett ###-#### panic hard ware back ordered for lobby exit to be maintaned/ handrail in 108 temp to be rechecked on perm instaltion. occ load signs temp to be check at perm occ. 5/23/2001 10:03:03 AM
FIRE-Final Inspection5/23/20015/23/20015/23/2001PFAIL
DetailsRick Jackson
Brett ###-#### still on TCO. gas valve operated properly for kitchen hood system; door hardware still not compliant for bar area; exit signs need repair in banquest room; extinguishers need to hung and current inspection tag 5/23/2001 2:23:24 PM
BLD-Final5/22/20015/22/20015/22/2001PFAIL
DetailsJim Storey
###-#### handrail and occ signage/ panic hardware to lobby pending fire sign off. 5/22/2001 4:14:08 PM
FIRE-Final Inspection5/22/20015/22/20015/22/2001PPART
DetailsRick Jackson
###-#### Brett per agreement with Dave Miller and owner the kitchen system to be reviewed by engineer; okay to occupy bar 5/23/2001 9:12:15 AM
BLD-Final5/21/20015/21/20015/21/2001PNR
DetailsCarl Dependahl
###-#### Brett
FIRE-Final Inspection5/21/20015/21/20015/21/2001PNR
DetailsRick Jackson
Brett ###-####
BLD-Framing/Rough-in4/17/20014/18/20014/18/2001ACANC
DetailsJim Storey
cover for kitchen Ron ###-####
BLD-Conference4/17/20014/17/20014/17/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 4/17/2001 5:47:05 PM w/ bldr, owner (Schotts), hvac installer, etc.re kitchen finals
BLD-Conference4/9/20014/9/20014/9/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 4/9/2001 1:54:25 PM w/ contractor re c/n...& w/ Rick J. & GS re range grease duct/shaft...not part of project???
BLD-Conference4/3/20014/3/20014/3/2001APASS
DetailsCarl Dependahl
Added by Inspector: 340 On 4/3/2001 9:33:58 AM w/ Cary of A-1 lock...need approved plans for determination of hdwe...have plans onsite.
BLD-Framing/Rough-in3/29/20013/29/20013/29/2001PPART
DetailsTom Arcoraci
1st floor ###-#### wip ok to cover lid in office behind elevator 3/29/2001 2:25:47 PM
BLD-Conference3/20/20013/20/20013/20/2001APASS
DetailsCarl Dependahl
Added by Inspector: 340 On 3/20/2001 10:02:27 AM w/ bldr re firestops at lids
BLD-Framing/Rough-in3/15/20013/16/20013/16/2001APART
DetailsCarl Dependahl
1st floor ###-####; restaurant area lid ok, wine bar area lid only ok 3/16/2001 10:45:49 AM
BLD-Framing/Rough-in3/6/20013/7/20013/7/2001APART
DetailsCarl Dependahl
###-#### ok to cover main bar area only 3/7/2001 4:28:33 PM
BLD-Framing/Rough-in3/6/20013/6/20013/6/2001PPART
DetailsCarl Dependahl
###-####; walls ok 3/6/2001 2:48:06 PM
BLD-Conference12/13/200012/14/200012/14/2000AFAIL
DetailsCarl Dependahl
c/n issued for PROFIT meeting 12/14/2000 2:42:45 PM