Permit Information
Permit NumberBLD00-03372
StatusFinaled
Name SCP GLOBAL TECHNOLOGIES
Site Address 8455 W WESTPARK ST
Project NameSCP GLOBAL TECH-#456
Customer Number 
ePlanReviewNo
Description
To divide existing building into 4 control areas, by construction of 1-hour occupancy separation walls between the designated areas, per footnote #1, Table's 3-D & 3-E, 1997 UBC. This is being done to allow the existing declared occupancy use groups to remain because each designated control area has been declared as having hazardous quantities of IPA (Isopropyl Alcohol @ 90 - 100 % concentration) within the exempt quantities of product allowed by UBC Table 3-D and 3-E, as per approved plans on file. Work to include upgrade of existing walls or construction of new walls, roof/ceiling or floor/ceiling, U.L. listed (or equal) 1-hour assemblies to create the required 1-hour occupancy separation to create the four control areas. Openings & penetrations W/I the occupancy separations SHALL have an equivalent fire resistive rating of 1-hour or greater. NOTE: This building is fully fire sprinklered for allowable area increase, considered to be one building of Type V-N construction, "B, S-1, F-1" Occupancies, 60 feet of open yard all around per Section 505.2 '97 UBC. (P.C.#958-00)/drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/21/200112/21/200112/21/2001PPASS
DetailsRuss Owen
Added by Inspector: 407 On 12/21/2001 12:06:43 PM ok perm oc work completed.
BLD-Final5/15/20015/15/20015/15/2001PPASS
DetailsJoe Tawney
Added by Inspector: 406 On 5/15/2001 3:50:17 PM Reinsp OK for certificate of completion
BLD-Final3/14/20013/15/20013/15/2001PPART
DetailsRuss Owen
###-####ok to occupy cont room 3/4 waiting for new door from ext building to new const. 3/15/2001 2:52:26 PM
FIRE-Final Inspection3/14/20013/15/20013/15/2001APART
DetailsJoe Tawney
###-#### Reinsp OK to occupy control areas 3 # 4 3/15/2001 1:17:19 PM
FIRE-Sprinkler Rough-in3/13/20013/14/20013/14/2001AFAIL
DetailsJoe Tawney
###-#### Reinsp Fail Doors not latching 3/14/2001 12:32:29 PM
FIRE-Final Inspection3/12/20013/13/20013/13/2001AFAIL
DetailsJoe Tawney
###-#### Final Fail smoke seals and adj closers. Install new rated door 3/13/2001 1:00:13 PM
BLD-Framing/Rough-in2/16/20012/20/20012/20/2001APART
DetailsRuss Owen
###-####partial insp of theshaft above control room #4. 2/20/2001 1:53:03 PM
BLD-Framing/Rough-in2/7/20012/8/20012/8/2001APART
DetailsRuss Owen
FR JEFF ###-#### shaft over control room,will recall for another insp 2/8/2001 1:33:23 PM
BLD-Framing/Rough-in1/3/20011/4/20011/4/2001APART
DetailsRuss Owen
fr jeff ###-####. inspections of control rooms 3&4 .work started w-out insp,sheetrock not inplace at ext side of control room #4 built against adjoinig room, will need submital for 1hr constuction at one side only, room #3 has 6 in pvc pipe in wall needs 1hr prot, also note both rooms req, 1hr metal fab shaft assemblys per er rpt #5301. c/ns noted with contractor. 1/4/2001 12:18:20 PM 1/4/2001 12:19:11 PM