Permit Number | BLD00-03527 |
Status | Finaled |
Name |
DIAMOND LINE DELIVERY
|
Site Address |
1004 W ROYAL BLVD
|
Project Name | |
Customer Number | |
ePlanReview | No |
Description |
*DIAMOND LINE DELIVERY* To install two 9' x 9' overhead doors in the existing concrete masonry wall on the west side of the building per approved plans on file. Existing 3,200 sq.ft. building is used for warehouse. Work to include installation of minimum 6" x 4" x 3/8" A36 Grade angle W/ minimum bearing of 8" on each end; bolted connection into grouted masonry; cut out and remove masonry below new angle; all per engineered design attached; and installation of OH doors. Angle to be installed before any masonry is removed. The angle is secured in place by an engineered connection system. Special inspection required per section 1701.5, #15, Special Cases. ENGINEERED DESIGN IS BASED ON MASONRY BLOCK BEING FULLY GROUTED. IF NOT GROUTED SOLID, FURTHER EVALUATION & DESIGN IS REQUIRED TO BE SUBMITTED TO THE BUILDING DEPT. FOR APPROVAL FROM THE STRUCTURAL ENGINEER & ARCHITECT WITH DESIGN DETAILS FOR CORRECTIONS BEFORE PROCEEDING W/ WORK. See attached plan review comments, considered part of the approved plans. NOTE: A "Letter of Completion / Compliance is required for this project scope. (P.C.#1007-00)/drs
|