BLD-Final | 2/13/2002 | 2/14/2002 | 2/14/2002 | A | PASS |
Carl Dependahl
|
|
|
mike ###-#### fn , card to Cathy 2/14/2002 1:42:29 PM
|
Permanent Occupancy | | 2/14/2002 | 2/14/2002 | | DONE |
|
|
|
|
BLD-Conference | 2/1/2002 | 2/1/2002 | 2/1/2002 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/1/2002 8:59:53 AM rec'd proper flood cert, ok
|
BLD-Conference | 1/31/2002 | 1/31/2002 | 1/31/2002 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/31/2002 10:51:51 AM need proper flood cert...from actual const floor levels; called bldr.
|
BLD-Final | 1/29/2002 | 1/30/2002 | 1/30/2002 | A | FAIL |
Carl Dependahl
|
|
|
DAVE ###-####, c/n handrail at main entry; rec'd spec insps'affidavit & flood cert 1/30/2002 11:42:47 AM
|
BLD-Final | 1/22/2002 | 1/23/2002 | 1/23/2002 | A | NR |
Tom Arcoraci
|
|
|
###-#### will recall for insp 1/23/2002 10:58:26 AM
|
Code Occupancy Approval | 1/22/2002 | 1/22/2002 | 1/22/2002 | P | CANC |
Wm. Michael Meloy
|
|
|
Scheduled by Inspector: WMM On 1/22/2002 3:31:51 PM
|
Code Occupancy Approval | 1/22/2002 | 1/22/2002 | 1/22/2002 | P | PASS |
Wm. Michael Meloy
|
|
|
Scheduled by Inspector: WMM On 1/22/2002 1:46:50 PM Passed 1/22/2002 1:47:53 PM
|
FIRE-Final Inspection | 1/16/2002 | 1/17/2002 | 1/17/2002 | A | PASS |
Rick Jackson
|
|
|
###-####
|
FIRE-Final Inspection | 1/8/2002 | 1/11/2002 | 1/11/2002 | P | FAIL |
Rick Jackson
|
|
|
JOHN ###-#### FIRE ALARM AND SAFTY c/n issued 1/11/2002 4:49:36 PM
|
FIRE-Final Inspection | 1/8/2002 | 1/11/2002 | 1/11/2002 | A | CANC |
Rick Jackson
|
|
|
JOHN ###-#### FIRE ALARM AND SAFTY rescheduled for pm 1/11/2002 6:24:08 AM
|
BLD-Conference | 1/8/2002 | 1/8/2002 | 1/8/2002 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/8/2002 12:41:53 PM w/ contractor & site eng'r re ramp: provide min 36 " wide x approx. 6' level at bottom
|
FIRE-Sprinkler Rough-in | 1/7/2002 | 1/8/2002 | 1/8/2002 | P | FAIL |
Rick Jackson
|
|
|
per rick around 1:30-- john-- ###-#### r/i- with GC - penetrations; need to test alarms; scheduled for 1/11 pm for final inspection 1/8/2002 3:08:27 PM
|
BLD-Conference | 1/3/2002 | 1/3/2002 | 1/3/2002 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/3/2002 8:11:04 AM w/ supt & framer...complete seal at smoke barriers; ok to chk at final
|
BLD-Framing/Rough-in | 12/31/2001 | 12/31/2001 | 12/31/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 12/31/2001 1:48:21 PM smoke walls ok; ok to place tiles.
|
BLD-Other | 12/31/2001 | 12/31/2001 | 12/31/2001 | P | PASS |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 12/31/2001 at 08:45:24. Contact: ###-####... ok for staff only to stock bldg & train, exits are maintained. 12/31/2001 1:50:20 PM
|
BLD-Conference | 12/28/2001 | 12/28/2001 | 12/28/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 12/28/2001 12:15:23 PM elec ok for grid; complete firestops at 1hr & smoke walls, prior to tiles ...many missed
|
BLD-Other | 12/28/2001 | 12/28/2001 | 12/28/2001 | P | FAIL |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 12/28/2001 at 09:20:57. Contact: ###-####....seal smoke barrier walls per 904, keep c/n 12/28/2001 5:10:42 PM
|
BLD-Framing/Rough-in | 12/27/2001 | 12/27/2001 | 12/27/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 12/27/2001 3:27:44 PM add wires, spreaders, as need ... get elec r/i ok'd.
|
BLD-Conference | 12/18/2001 | 12/18/2001 | 12/18/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 12/18/2001 12:09:52 PM w/ bldr re ADA ramp
|
BLD-Framing/Rough-in | 12/13/2001 | 12/13/2001 | 12/13/2001 | P | PART |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 12/13/2001 12:16:15 PM grid clg ok exc. add spreaders at loose ends...obtain hvac & elec oks, seal penetrations at rated smoke barriers
12/13/2001 3:12:46 PM
|
BLD-Conference | 12/12/2001 | 12/12/2001 | 12/12/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 12/12/2001 6:00:47 PM w/ supt...rec'd Mti's soils approval as requested... stamped by eng'r
|
BLD-Conference | 10/23/2001 | 10/23/2001 | 10/23/2001 | P | PASS |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 10/23/2001 12:09:53 PM w/ Dave re mech room issues...keep c/n. 10/23/2001 4:27:13 PM
|
BLD-Conference | 10/22/2001 | 10/22/2001 | 10/22/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 10/22/2001 9:25:26 AM w/ Kevin Of Roylance Eng's re soils report...need statement per c/n of 10-19, keep c/n.
|
BLD-Framing/Rough-in | 10/19/2001 | 10/19/2001 | 10/19/2001 | P | FAIL |
Carl Dependahl
|
|
|
###-#### dave..add'l c/n...clarify "occ. separations", dampers, eng's geo-tech & flood cert to be submitted. ok to begin cover, except at hvac areas. 10/19/2001 5:08:08 PM
|
BLD-Framing/Rough-in | 10/18/2001 | 10/18/2001 | 10/18/2001 | P | FAIL |
Carl Dependahl
|
|
|
###-#### DAVE c/n re smoke walls, dampers, other ok's...recall 10/18/2001 12:51:50 PM
|
BLD-Framing/Rough-in | 10/3/2001 | 10/3/2001 | 10/3/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 10/3/2001 11:12:07 AM keep c/n(s)...ext ok to place veneer
|
BLD-Conference | 9/20/2001 | 9/20/2001 | 9/20/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 9/20/2001 5:17:35 PM keep c/n re joist burn thru, reviewed mti report, soils ok
|
BLD-Conference | 9/4/2001 | 9/4/2001 | 9/4/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 9/4/2001 11:07:25 AM w/ Dave & proj mgr onsite...need eng's fix for steel burn thru at roof deck welds
|
BLD-Framing/Rough-in | 8/30/2001 | 8/30/2001 | 8/30/2001 | A | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/30/2001 10:17:30 AM c/n, burn thru at top chords bar joists, need "fix"; discussed smoke barrierconst w/ framer
|
BLD-Conference | 8/14/2001 | 8/14/2001 | 8/14/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/14/2001 11:37:27 AM w/ Dave...still need steel certs, masonry & apprropriate concrete reports
|
BLD-Conference | 8/7/2001 | 8/7/2001 | 8/7/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/7/2001 9:11:56 AM w/ bldr re c/n of 8-6
|
BLD-Conference | 8/7/2001 | 8/7/2001 | 8/7/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/7/2001 10:58:26 AM w/ Sonia of Outland Steel re c/n: will forward steel certs & "approved fabricator" staus for joist/truss manuf. (Vulcraft?) per UBC ch.17
|
BLD-Conference | 8/6/2001 | 8/6/2001 | 8/6/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/6/2001 3:44:03 PM w/ supt & mason foreman: need all lifts called for insp to city as req'd: need verify approved fab. status for steel roof framing; show flood cert.
|
BLD-Footing | 7/20/2001 | 7/20/2001 | 7/20/2001 | A | PASS |
Jim Storey
|
|
|
Added by Inspector: 301 On 7/20/2001 8:38:34 AM pad ft and wing walls for screen wall south ok pending mti report.
|
BLD-Footing | 7/19/2001 | 7/20/2001 | 7/20/2001 | A | PASS |
Jim Storey
|
|
|
###-#### north floor slab ok 7/20/2001 8:25:59 AM
|
BLD-Foundation | 7/19/2001 | 7/20/2001 | 7/20/2001 | P | PASS |
Jim Storey
|
|
|
###-#### slab on grade ok with foam and vapor barrior. 7/20/2001 3:38:42 PM
|
BLD-Footing | 7/18/2001 | 7/19/2001 | 7/19/2001 | P | CANC |
Jim Storey
|
|
|
Robert ###-#### called and canclled 7/19/2001 4:22:59 PM
|
BLD-Conference | 6/22/2001 | 6/22/2001 | 6/22/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 6/22/2001 11:35:33 AM met w/ bldr onsite, surgery suite project, pre-con partial
|
BLD-Footing | 6/21/2001 | 6/22/2001 | 6/22/2001 | A | PART |
Carl Dependahl
|
|
|
Robert ###-####; perim ftgs; ok pend MTI report. met w/ super onsite 6/22/2001 11:31:50 AM
|