BLD-Final | 11/30/2001 | 12/3/2001 | 12/3/2001 | A | PASS |
Tony Young
|
|
|
walter ###-####
ok for perm. occ. as long as others are ok 12/3/2001 11:43:36 AM
|
Permanent Occupancy | | 12/3/2001 | 12/3/2001 | | DONE |
|
|
|
|
BLD-Final | 11/29/2001 | 11/29/2001 | 11/29/2001 | P | FAIL |
Tony Young
|
|
|
WALTER ###-####
waiting on elevator final from the state and electrical 11/29/2001 2:15:47 PM
|
FIRE-Final Inspection | 11/27/2001 | 11/28/2001 | 11/28/2001 | P | PASS |
Rick Jackson
|
|
|
###-####
|
BLD-Final | 11/20/2001 | 11/20/2001 | 11/19/2001 | P | PART |
Tony Young
|
|
|
Ok for temp occ.. CN issued for temp. glass, ada compliance on ramps, special inspection final letter and other agency signoffs.
|
BLD-Final | 11/14/2001 | 11/15/2001 | 11/15/2001 | P | FAIL |
Tony Young
|
|
|
WALTER ###-####
c/n posted 11/15/2001 4:36:14 PM
|
FIRE-Final Inspection | 11/14/2001 | 11/15/2001 | 11/15/2001 | A | PASS |
Rick Jackson
|
|
|
###-####
|
FIRE-Final Inspection | 11/15/2001 | 11/15/2001 | 11/15/2001 | P | PART |
Rick Jackson
|
|
|
Added by Inspector: 409 On 11/15/2001 4:31:58 PM disregard the PASS on this date; temp occ approved pending fire control panel for detectors and elevator recall
|
FIRE-Final Inspection | 11/14/2001 | 11/14/2001 | 11/14/2001 | P | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 11/14/2001 4:05:41 PM elevator recall panel needed; need detector at smoke damper at stair enclosure
|
Code Occupancy Approval | 11/9/2001 | 11/8/2001 | 11/8/2001 | A | PASS |
Michael Garner
|
|
|
Added by Inspector: MSG On 11/9/2001 11:49:33 AM
|
BLD-Aging Inspection | 11/6/2001 | 11/6/2001 | 11/6/2001 | | PART |
Tony Young
|
|
|
wip 11/8/2001 9:25:47 AM
|
BLD-Framing/Rough-in | 9/5/2001 | 9/6/2001 | 9/6/2001 | P | PASS |
Tony Young
|
|
|
walter- ###-#### r/i
|
BLD-Energy code compliance | 8/28/2001 | 8/29/2001 | 8/29/2001 | P | PART |
Tony Young
|
|
|
###-####
ok to cover main level outside walls after tightening bolts, and ok to cover main level int. non bearing walls away from any mechanical work, (no mech. permit for ducting yet) 8/29/2001 3:17:40 PM
|
BLD-Framing/Rough-in | 8/27/2001 | 8/28/2001 | 8/28/2001 | P | PART |
Tony Young
|
|
|
###-####////c/n posted, ok to insulate unaffected areas, pending letter from eng. 8/28/2001 3:35:49 PM
|
BLD-Conference | 8/24/2001 | 8/27/2001 | 8/27/2001 | A | PASS |
Tony Young
|
|
|
for conf walter###-#### -per tony 10:00
met w/ greg w/ hummel, need structural to provide letter of compliance on as built, and talked about plan change drawings and alt. finish work, stairs, draft stopping, fire stops, etc 8/27/2001 11:03:36 AM
|
BLD-Framing/Rough-in | 8/23/2001 | 8/24/2001 | 8/24/2001 | P | FAIL |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 08/23/2001 at 17:32:14. Contact: ###-####.no mech. sign off, and need to meet arch. or strutural on job, go over special construction design 8/24/2001 2:50:35 PM
|
BLD-Framing/Rough-in | 8/20/2001 | 8/21/2001 | 8/21/2001 | A | PART |
Tony Young
|
|
|
###-#### PARTIAL
ok to drywall lid below vault area and elevator shaft and mech . room next to elevator, pending elec. sign off 8/21/2001 11:51:30 AM
|
BLD-Framing/Rough-in | 8/7/2001 | 8/8/2001 | 8/8/2001 | A | PASS |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 08/07/2001 at 16:50:00. Contact: ###-####. 8/8/2001 11:01:13 AM shear nialing on upper level ok to cover 8/8/2001 11:12:53 AM
|
BLD-Framing/Rough-in | 7/31/2001 | 8/1/2001 | 8/1/2001 | A | PART |
Tony Young
|
|
|
SHEAR WALL WALTER ###-####
shear ok on front areas, lower and some of upper 8/1/2001 11:32:45 AM
|
BLD-Concrete | 7/3/2001 | 7/5/2001 | 7/5/2001 | A | PART |
Tony Young
|
|
|
slab and a concrete wall Walter ###-####
poured already, s. i. was on site per walter 7/5/2001 10:51:40 AM
|
BLD-Foundation | 6/27/2001 | 6/28/2001 | 6/28/2001 | A | PART |
Tony Young
|
|
|
WAlter ###-####
pending special inspector report, already poured 6/28/2001 12:00:21 PM
|
BLD-Foundation | 6/25/2001 | 6/26/2001 | 6/26/2001 | P | PART |
Tony Young
|
|
|
Walter ###-####
already poured, confirmed w/ mti that they where there///pending report 6/26/2001 1:20:32 PM
|
BLD-Foundation | 6/20/2001 | 6/22/2001 | 6/22/2001 | A | PART |
Tony Young
|
|
|
###-####
already poured, pending s i report 6/22/2001 10:53:56 AM
|
BLD-Foundation | 6/20/2001 | 6/21/2001 | 6/21/2001 | A | PART |
Tony Young
|
|
|
slab and vertical walls ###-####
pending s. i. report 6/21/2001 10:50:16 AM
|
BLD-Foundation | 6/14/2001 | 6/15/2001 | 6/15/2001 | A | PASS |
Tony Young
|
|
|
###-####
pending s. i. report 6/15/2001 10:12:33 AM
|
BLD-Footing | 6/8/2001 | 6/11/2001 | 6/11/2001 | A | PART |
Dave Hannah
|
|
|
###-#### 6/11/2001 10:43:46 AM MTI is testing and inspecting 6/11/2001 10:44:37 AM
|
BLD-Foundation | 6/8/2001 | 6/11/2001 | 6/11/2001 | A | PART |
Dave Hannah
|
|
|
MTI inspected and tested 6/11/2001 10:45:13 AM
|
BLD-Other | 6/9/2001 | 6/11/2001 | 6/11/2001 | A | PASS |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 06/09/2001 at 19:02:30. Contact: ###-####.
|
FIRE-Supply Line Cover | 6/7/2001 | 6/8/2001 | 6/8/2001 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/07/2001 at 14:48:16. Contact: ###-####. work code entered by caller - no fire requested 6/8/2001 7:54:32 AM
|
BLD-Concrete | 6/4/2001 | 6/5/2001 | 6/5/2001 | A | PART |
Tom Arcoraci
|
|
|
###-#### wall PENDING SPEC INSP REPORTS 6/5/2001 11:02:21 AM
|
BLD-Concrete | 5/29/2001 | 5/30/2001 | 5/30/2001 | A | PART |
Tony Young
|
|
|
###-####
pend. report from s. i. 5/30/2001 11:49:20 AM
|
BLD-Concrete | 5/23/2001 | 5/24/2001 | 5/24/2001 | P | FAIL |
Tony Young
|
|
|
concrete wall walter ###-####
rebar above windows not per plan, pending s. i. report on fix 5/24/2001 1:47:50 PM
|
BLD-Concrete | 5/17/2001 | 5/18/2001 | 5/18/2001 | A | PART |
Tony Young
|
|
|
pouring at 8:00 Walter ###-####
pending s. i. report 5/18/2001 9:13:19 AM
|
BLD-Concrete | 5/11/2001 | 5/14/2001 | 5/14/2001 | A | PART |
Tony Young
|
|
|
###-#### wall
upper south retaining wall, ok pending s. i. report 5/14/2001 1:32:51 PM
|
BLD-Concrete | 5/7/2001 | 5/8/2001 | 5/8/2001 | P | PART |
Tony Young
|
|
|
pouring at 12:00 Walter ###-####
pending s.i. report 5/8/2001 1:58:30 PM
|
BLD-Concrete | 5/7/2001 | 5/8/2001 | 5/8/2001 | A | PART |
Tony Young
|
|
|
found. wall on top of retaining wall north 1/2, and found. wall around dumpster ok pending S. I. report 5/8/2001 10:49:24 AM
|
BLD-Foundation | 5/2/2001 | 5/3/2001 | 5/3/2001 | A | PART |
Tony Young
|
|
|
found-- walter- ###-####
looks ok, w/ verbal corrections, pending s. i. report 5/3/2001 10:34:37 AM
|
BLD-Concrete | 4/19/2001 | 4/19/2001 | 4/19/2001 | P | PART |
Tony Young
|
|
|
special inspectors on site walter ###-####
|
BLD-Concrete | 4/13/2001 | 4/16/2001 | 4/16/2001 | A | PART |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 04/13/2001 at 14:02:38. Contact: ###-####.
Special on site, ftgs for dumpster area, and retaining wall 2nd half 4/16/2001 12:09:53 PM
|
BLD-Footing | 4/11/2001 | 4/12/2001 | 4/12/2001 | A | PART |
Tony Young
|
|
|
special inspector on site Walter ###-#### pouring at 10:30
pending s. i. report, retaining wall ftgs 4/12/2001 10:41:04 AM
|
BLD-Concrete | 4/5/2001 | 4/5/2001 | 4/5/2001 | P | PART |
Tony Young
|
|
|
walter-- ###-#### concrete
wall rebar inspection while panels are off, looks good so far, pending s. i. report 4/5/2001 3:12:04 PM
|
BLD-Footing | 4/3/2001 | 4/3/2001 | 4/3/2001 | P | PART |
Tony Young
|
|
|
pending s.i. report 4/3/2001 2:16:57 PM
|
BLD-Footing | 3/27/2001 | 3/28/2001 | 3/28/2001 | A | PART |
Tony Young
|
|
|
work in progress, talked w/ S. I. about corrections that need to be addressed also t/w job foreman. 1/2 of footing were poured when I got here and some corrections where not done yet, s.i. and I talked, corrections are being made now, general conformance should be met 3/28/2001 11:44:00 AM
|
BLD-Grading Inspection | 3/28/2001 | 3/28/2001 | 3/28/2001 | | PASS |
Rita DeYoung
|
|
|
Footing subgrade has been approved by the geotechnical engineer.
|
BLD-Footing | 3/27/2001 | 3/27/2001 | 3/27/2001 | P | PART |
Tony Young
|
|
|
###-#### late pm
pending special inspector report, work in progress, verbal corrections, need to go back and verify 3/27/2001 2:56:30 PM
|