BLD-Final | 7/17/2002 | 7/18/2002 | 7/18/2002 | A | PASS |
Carl Dependahl
|
|
|
###-####; ok for perm occ. 7/18/2002 11:43:31 AM
|
Permanent Occupancy | | 7/18/2002 | 7/18/2002 | | DONE |
|
|
|
|
BLD-Final | 7/17/2002 | 7/17/2002 | 7/17/2002 | P | NR |
Carl Dependahl
|
|
|
need verify all shell reqs... 7/17/2002 8:21:53 PM
|
BLD-Conference | 7/16/2002 | 7/16/2002 | 7/16/2002 | P | NR |
Carl Dependahl
|
|
|
wendell 8668492
|
BLD-Final | 7/15/2002 | 7/16/2002 | 7/16/2002 | A | NR |
Carl Dependahl
|
|
|
|
BLD-Final | 7/16/2002 | 7/16/2002 | 7/16/2002 | P | CANC |
Carl Dependahl
|
|
|
wendall ###-####
|
FIRE-Conference | 7/10/2002 | 7/10/2002 | 7/10/2002 | P | PART |
Rick Jackson
|
|
|
wendel ###-#### told wendelll to get the occ cards turned in to Cathy 7/10/2002 2:41:21 PM
|
BLD-Conference | 6/25/2002 | 6/26/2002 | 6/26/2002 | A | PASS |
Carl Dependahl
|
|
|
Wendell ###-#### w/ Rick j...re final status 6/26/2002 4:12:39 PM
|
BLD-Conference | 6/24/2002 | 6/25/2002 | 6/25/2002 | P | PART |
Carl Dependahl
|
|
|
wendell ###-#### hvac not finalled 6/25/2002 5:09:05 PM ? fire?? 6/25/2002 5:09:30 PM
|
BLD-Conference | 6/19/2002 | 6/20/2002 | 6/20/2002 | A | NR |
Carl Dependahl
|
|
|
wendel ###-#### need verify status w/ fire; keep c/n & temp status til resolved. 6/20/2002 11:22:08 AM
|
BLD-Conference | 6/19/2002 | 6/20/2002 | 6/20/2002 | P | PART |
Carl Dependahl
|
|
|
wendel ###-#### need to confirm fire insp status prior to perm occ... 6/24/2002 1:38:29 PM
|
BLD-Conference | 6/17/2002 | 6/18/2002 | 6/18/2002 | A | PASS |
Carl Dependahl
|
|
|
###-#### wendell need verify all project permits as ok for final 6/17/2002 5:52:52 PM
|
BLD-Conference | 6/17/2002 | 6/18/2002 | 6/18/2002 | P | PASS |
Carl Dependahl
|
|
|
###-#### need verify other finals...complete expansion joint firestop install?? other finals? 6/18/2002 6:11:15 PM
|
FIRE-Final Inspection | 3/25/2002 | 3/26/2002 | 3/26/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/25/2002 at 17:36:59. Contact: ###-####. checked all of the new dampers installed as part of the airbalancing problem; all funtioned under zone "a" alarm 3/26/2002 2:56:03 PM
|
BLD-Final | 3/19/2002 | 3/20/2002 | 3/20/2002 | P | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 03/19/2002 at 17:17:08. Contact: ###-####.
|
BLD-Final | 3/6/2002 | 3/7/2002 | 3/7/2002 | A | PART |
Carl Dependahl
|
|
|
fn wendell ###-####--pending fire insp; ok for t/o; keep c/n. 3/7/2002 1:58:50 PM
|
FIRE-Final Inspection | 3/6/2002 | 3/7/2002 | 3/7/2002 | A | PASS |
Rick Jackson
|
|
|
wendell- ###-####
|
BLD-Conference | 3/6/2002 | 3/6/2002 | 3/6/2002 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 3/6/2002 4:50:17 PM w/ Rick J &supt...keep c/n , need fire final.
|
BLD-Final | 3/5/2002 | 3/5/2002 | 3/5/2002 | A | FAIL |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 3/5/2002 11:30:00 AM wendell ###-####; c/n need fire, achd, stairs, firestops,rails, etc. 3/5/2002 5:48:18 PM
|
BLD-Final | 3/4/2002 | 3/5/2002 | 3/5/2002 | A | NR |
Carl Dependahl
|
|
|
###-#### WENDELL FOR OCCUPANCY need fire, glass spec's, complete prior c/n 3/5/2002 11:30:53 AM
|
FIRE-Final Inspection | 3/4/2002 | 3/5/2002 | 3/5/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### WENDELL FOR OCCUPANCY standpipe in south stair obstructed by gaurdrail 3/6/2002 7:27:04 AM
|
BLD-Final | 3/1/2002 | 3/4/2002 | 3/4/2002 | A | FAIL |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 03/01/2002 at 16:53:38. Contact: ###-####. Partial insp only, c/n; LISTING FOR EXPANSION JOINT, GYP INSTALL AT SHAFTS, NEED LISTING FOR 2HR GLASS BLOCK ASSY, COMPLETE PRIOR C/N... 3/4/2002 1:44:53 PM
|
BLD-Final | 3/4/2002 | 3/4/2002 | 3/4/2002 | P | NR |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 3/4/2002 11:59:49 AM kee 3/4/2002 4:55:46 PM p c/n 3/4/2002 4:56:14 PM
|
FIRE-Final Inspection | 3/1/2002 | 3/4/2002 | 3/4/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/01/2002 at 16:52:45. Contact: ###-####. stair enclosure doors not latching 3/4/2002 4:48:08 PM
|
FIRE-Final Inspection | 2/27/2002 | 2/28/2002 | 2/28/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 02/27/2002 at 17:55:20. Contact: ###-####. items not complete from previous c/n 2/28/2002 4:43:44 PM
|
FIRE-Alarm Testing | 2/19/2002 | 2/20/2002 | 2/20/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 2/19/2002 4:26:16 PM Scheduled by Inspector: 409 On 2/19/2002 4:24:35 PM smokes in bathrooms on second floor to heat detectors; some dampers not closing 2/20/2002 11:42:18 AM
|
FIRE-Conference | 2/15/2002 | 2/19/2002 | 2/19/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 02/15/2002 at 13:40:37. Contact: ###-####. tested alarms; got to the third floor; need detectors at exhaust dampers on 4th floor; NAC on 4th floor not reporting battery loss trouble 2/19/2002 4:25:46 PM
|
BLD-Framing/Rough-in | 2/14/2002 | 2/15/2002 | 2/15/2002 | A | PART |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 2/14/2002 4:32:46 PM wendell 8668492; OK to place tiles at grid 1st & 2nd fl; Rec'd 2hr. glass block ass'y for occupancy separation wall at ambulance bay...will review w/ plan chk. Still req's spec. insp's affidavit for occupancy 2/19/2002 1:14:06 PM
|
FIRE-Alarm Testing | 2/14/2002 | 2/15/2002 | 2/15/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 02/14/2002 at 15:11:06. Contact: ###-####. See FIR01-00435 for notes 2/15/2002 12:35:47 PM
|
BLD-Wall cover | 2/14/2002 | 2/14/2002 | 2/14/2002 | P | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 02/14/2002 at 10:20:03. Contact: ###-####....need listing for glass block at 2hr wall 2/14/2002 4:37:02 PM
|
BLD-Framing/Rough-in | 2/11/2002 | 2/12/2002 | 2/12/2002 | A | FAIL |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 2/11/2002 4:19:02 PM wendell 8668492,c/n: verify/justify glazed block at 2hr wall at ambulance bay at north ext; complete firestops, chk stair rails... 2/12/2002 6:17:26 PM
|
BLD-Wall cover | 2/11/2002 | 2/11/2002 | 2/11/2002 | P | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 02/11/2002 at 08:33:23. Contact: ###-####.
|
BLD-Framing/Rough-in | 1/31/2002 | 1/31/2002 | 2/4/2002 | P | PART |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 1/31/2002 12:13:08 PM ###-####, wip, keep c/n. complete firestops at rated const. 2/4/2002 9:15:08 AM
|
BLD-Conference | 1/31/2002 | 2/1/2002 | 2/1/2002 | A | PASS |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 1/31/2002 5:55:22 PM , complete c/n prior to grid tile 2/1/2002 4:59:35 PM
|
BLD-Framing/Rough-in | 1/30/2002 | 1/31/2002 | 1/31/2002 | A | PART |
Carl Dependahl
|
|
|
WENDEL ###-####; w 1/31/2002 5:35:11 PM ip, keep c/n 1/31/2002 5:40:40 PM
|
BLD-Framing/Rough-in | 1/14/2002 | 1/14/2002 | 1/14/2002 | P | FAIL |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 1/14/2002 9:03:07 AM ###-#### c/n, firestops at walls , floors, grid clg, dampers, exit enclosures, etc. 1/14/2002 1:41:41 PM
|
BLD-Framing/Rough-in | 1/8/2002 | 1/9/2002 | 1/14/2002 | A | NR |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 1/8/2002 4:36:06 PM ###-####, need fire ok 1/14/2002 9:03:45 AM
|
BLD-Framing/Rough-in | 1/8/2002 | 1/8/2002 | 1/8/2002 | P | NR |
Carl Dependahl
|
|
|
###-#### complete firestopping thru-out, recall. no insp performed. 1/8/2002 5:57:36 PM
|
FIRE-Alarm Testing | 1/7/2002 | 1/8/2002 | 1/8/2002 | A | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 01/07/2002 at 14:59:07. Contact: ###-####. no alarm test; walked through building with Stan and Wendell; numerous penetrations 1/8/2002 11:34:25 AM
|
BLD-Framing/Rough-in | 12/21/2001 | 12/24/2001 | 12/24/2001 | A | PART |
Russ Owen
|
|
|
Scheduled by Inspector: 340 On 12/21/2001 7:07:32 PM ###-####...St Lukes; sorry, couldn't get to it Friday...c/n issued do not place grid seal penetrations in firewalls and smoke barriers. 12/24/2001 12:16:10 PM
|
BLD-Wall cover | 12/20/2001 | 12/21/2001 | 12/21/2001 | A | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 12/20/2001 at 10:28:08. Contact: ###-####. unable to contact at this time. 12/21/2001 7:07:59 PM
|
BLD-Framing/Rough-in | 12/19/2001 | 12/20/2001 | 12/20/2001 | A | NR |
Carl Dependahl
|
|
|
###-#### WENDLE ...recall 12/20/2001 3:04:08 PM
|
BLD-Aging Inspection | 12/12/2001 | 12/12/2001 | 12/12/2001 | | NR |
Carl Dependahl
|
|
|
st lukes NICU; wip 12/18/2001 3:49:32 PM
|
BLD-Framing/Rough-in | 10/11/2001 | 10/12/2001 | 10/12/2001 | A | NR |
Carl Dependahl
|
|
|
Scheduled by Inspector: 408 On 10/11/2001 1:37:37 PM taken by 408. 10/12/2001 11:36:01 AM
|
BLD-Framing/Rough-in | 10/12/2001 | 10/12/2001 | 10/12/2001 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by Inspector: 408 On 10/12/2001 10:37:47 AM 2nd floor plumbing pents ok for cover in walls section c and d 10/12/2001 11:10:28 AM
|
BLD-Wall cover | 10/10/2001 | 10/11/2001 | 10/11/2001 | A | NR |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 10/10/2001 at 12:28:39. Contact: ###-####.
|
BLD-Framing/Rough-in | 9/12/2001 | 9/12/2001 | 9/12/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 9/12/2001 1:53:39 PM soiled linen rm 1st fl, int penetrations ok...need chk dampers.
|
BLD-Conference | 9/7/2001 | 9/7/2001 | 9/7/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 9/7/2001 3:33:40 PM ok to use 3m pads at med gas teminations at rated walls
|
BLD-Framing/Rough-in | 9/7/2001 | 9/7/2001 | 9/7/2001 | P | PART |
Carl Dependahl
|
|
|
###-#### penetrations of med gas & elec ok at E-W 1st fl firewall ok. (corridor) 9/12/2001 1:52:27 PM
|
BLD-Wall cover | 8/20/2001 | 8/20/2001 | 8/20/2001 | P | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 08/20/2001 at 07:37:52. Contact: ###-####....need listing for gas outlet firestops, complete med gas r/i 8/21/2001 11:52:59 AM
|
BLD-Conference | 8/8/2001 | 8/8/2001 | 8/8/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 8/8/2001 4:42:11 PM w/ Wendall at site, re stair & elev shafts; complete r/i's for cover of other areas
|
BLD-Framing/Rough-in | 8/8/2001 | 8/8/2001 | 8/8/2001 | P | FAIL |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 08/08/2001 at 07:31:59. Contact: ###-####. c/n firestops, 1st fl areas c&d. ok to continue or begin wall cover. 8/9/2001 1:01:19 PM
|