BLD-Final | 12/14/2001 | 12/17/2001 | 12/17/2001 | A | PASS |
Tom Arcoraci
|
|
|
###-#### ok for perm 12/17/2001 9:30:38 AM hen others sign 12/17/2001 9:30:53 AM
|
Permanent Occupancy | | 12/17/2001 | 12/17/2001 | | DONE |
|
|
|
|
BLD-Final | 11/13/2001 | 11/13/2001 | 11/13/2001 | A | PASS |
Tom Arcoraci
|
|
|
Added by Inspector: 408 On 11/13/2001 11:36:42 AM ok for perm occ when others sign perm occ
|
BLD-Conference | 11/9/2001 | 11/9/2001 | 11/9/2001 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by Inspector: 408 On 11/9/2001 11:25:54 AM
|
BLD-Final | 11/9/2001 | 11/9/2001 | 11/9/2001 | P | CANC |
Tom Arcoraci
|
|
|
###-####this insp was added after 3 pm?????
11/9/2001 4:26:11 PM
|
FIRE-Final Inspection | 11/2/2001 | 11/5/2001 | 11/5/2001 | P | FAIL |
Troy Cobbley
|
|
|
add extinguisher at customer service and relocate one in the home stockroom, add exit sign at employee exit, repair exit sign in EPM, main entrance, and home entry, paint curbs and post signs, install knox box 11/6/2001 8:57:37 AM
|
FIRE-Final Inspection | 11/2/2001 | 11/5/2001 | 11/5/2001 | P | CANC |
Troy Cobbley
|
|
|
duplicate inspection 11/6/2001 8:55:29 AM
|
BLD-Framing/Rough-in | 9/27/2001 | 9/27/2001 | 9/27/2001 | P | FAIL |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 09/27/2001 at 08:30:13. Contact: ###-####. 9/27/2001 2:43:23 PM needs siezmic pods in kitchen. 9/27/2001 3:07:22 PM
|
BLD-Framing/Rough-in | 8/15/2001 | 8/15/2001 | 8/15/2001 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 08/15/2001 at 10:01:56. Contact: ###-####. partial grid inspection wip 8/15/2001 3:06:11 AM
|
BLD-Framing/Rough-in | 8/6/2001 | 8/6/2001 | 8/6/2001 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 08/06/2001 at 08:55:34. Contact: ###-####. wip 8/6/2001 4:48:34 AM
|
BLD-Framing/Rough-in | 7/23/2001 | 7/23/2001 | 7/23/2001 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 07/23/2001 at 09:44:53. Contact: ###-####. ok tocover food entry check for straps, grid in appls ok, ok to start cover at deli area has new detail for entrys 7/23/2001 2:49:28 AM
|
BLD-Framing/Rough-in | 7/16/2001 | 7/16/2001 | 7/16/2001 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 07/16/2001 at 07:48:05. Contact: ###-####. ITEMS FROM LAST CN COMPLETE 7/16/2001 5:05:14 AM
|
BLD-Conference | 7/12/2001 | 7/12/2001 | 7/12/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 7/12/2001 8:37:19 AM w/ bldr re c/n of 7-11.
|
BLD-Framing/Rough-in | 7/11/2001 | 7/11/2001 | 7/11/2001 | P | FAIL |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 07/11/2001 at 09:44:21. Contact: ###-####.c/n, need approved fabricator cert for steel joists, etc...1hr assy at req'd corridors to south side, wrap boxes, add web stiffeners; show frame diagram for entry ceilings, etc...not shown on plans 7/11/2001 6:38:20 PM
|
BLD-Framing/Rough-in | 7/5/2001 | 7/5/2001 | 7/5/2001 | P | PART |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 07/05/2001 at 08:43:45. Contact: ###-####. Check listing for corridor (1hr) Ceiling. Tenant walls and Misc walls 1 side and Recall for insp. 7/5/2001 3:26:46 PM
|
BLD-Conference | 6/25/2001 | 6/25/2001 | 6/25/2001 | A | PASS |
Tom Arcoraci
|
|
|
Added by Inspector: 408 On 6/25/2001 8:11:39 PM WIP OK
|
BLD-Wall cover | 6/20/2001 | 6/20/2001 | 6/20/2001 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 06/20/2001 at 10:44:21. Contact: ###-####. ok to cover west walls and messinine 6/20/2001 4:59:46 AM
|
BLD-Conference | 6/13/2001 | 6/13/2001 | 6/13/2001 | A | PASS |
Tom Arcoraci
|
|
|
Added by Inspector: 408 On 6/13/2001 10:49:45 PM mti on site eng aware of all discrips
|
BLD-Other | 5/30/2001 | 5/31/2001 | 5/31/2001 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 05/30/2001 at 13:56:27. Contact: ###-####. MTI ON SITE 5/31/2001 2:20:38 PM
|