Permanent Occupancy | | 9/5/2001 | 9/5/2001 | | DONE |
|
|
|
|
BLD-Other | 8/28/2001 | 8/28/2001 | 8/28/2001 | P | FAIL |
Jim Storey
|
|
|
1. (Stairway rise and run) The rise of steps and stairs shall not be less than 4 inches nor more than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. Except as permitted for circular, winding, and spiral stairways, the run shall not be less than 11 inches as measured horizontally between the vertical planes of the furthermost projection of adjacent treads or nosings. Stair treads shall be of uniform size and shape, except the largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. (1997 UBC 1003.3.3.3) Note the exception to tread and riser dimensions for private stairways and stairways to unoccupied roofs and. Also, note the exception to dimensions of risers adjoining a sloping public way.
|
FIRE-Final Inspection | 8/28/2001 | 8/28/2001 | 8/28/2001 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 08/28/2001 at 07:34:09. Contact: ###-####. storage over 20 ft in two areas; will have down for structural inspector 8/28/2001 1:47:40 PM
|
BLD-Other | 8/23/2001 | 8/23/2001 | 8/23/2001 | P | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/23/2001 at 07:43:41. Contact: ###-####. c/n on bld00955 aplies to this permit also. 8/23/2001 3:17:46 PM
|
FIRE-Final Inspection | 8/23/2001 | 8/23/2001 | 8/23/2001 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 08/23/2001 at 07:42:01. Contact: ###-####. exit blocked; storage height exceed 20 ft; extinguishers 8/23/2001 3:45:50 PM
|