Permit Information
Permit NumberBLD01-01349
StatusFinaled
Name JOE'S ALL AMERICAN GRILL (BASEMENT)
Site Address 100 S 6TH ST
Project NameJOE'S ALL AMERICAN GRILL
Customer Number 
ePlanReviewNo
Description
(JOE'S ALL AMERICAN GRILL - BASEMENT) Fire sprinklers substitute for 1-hr fire-resistive construction of the building. To remodel the basement (5,500 square feet) and prepare it for assembly occupancy. Work is to include a structural header at a door opening in an existing masonry wall, 2 restrooms accessible to the disabled, a 450 square foot raised platform, and new floor columns/beams all per approved drawings, engineering, and plan review conditions on file. The basement shall be fully fire sprinklered per NFPA 13-1999 as regulated by the Fire Department. A fire alarm system is required throughout the basement. The maximum occupant load for the basement is based on available exit width and use (1,657 square feet @ 1:15 and 2,307 square feet @ 1:7). The capacity of the basement (440) shall be posted in a conspicuous place on an approved sign near the main exit. PC-0429-01 **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/6/200112/7/200112/7/2001PPASS
DetailsCarl Dependahl
david ###-#### bsmt only 12/7/2001 4:06:30 PM
BLD-Final12/6/200112/7/200112/7/2001ACANC
DetailsCarl Dependahl
david ###-####
Permanent Occupancy 12/7/200112/7/2001 DONE
Details
BLD-Final10/26/200110/29/200110/29/2001APART
DetailsRuss Owen
###-#### DAVID. Appears all required signatures are on card , Mechanical has been finaled, need to know what 340 wanted else wise may need to lower restroom mirrors to 40 In. Will wait for 340 to return to work, Spoke with Dave at site. 10/29/2001 1:05:00 PM
BLD-Aging Inspection10/2/200110/2/200110/5/2001 NR
DetailsCarl Dependahl
met owner at site 10/5/2001 11:43:08 AM
BLD-Conference10/4/200110/4/200110/4/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 10/4/2001 3:54:05 PM w/OWNER re final status, will obtain all signatures
BLD-Conference10/2/200110/2/200110/2/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 10/2/2001 3:00:38 PM re obtaining final
BLD-Final8/2/20018/2/20018/2/2001PFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 08/02/2001 at 10:12:11. Contact: ###-####.c/n, base/wall finishes, ADA mirrors at restrms; clarify deletions/modifications; obtain all perm finals, etc. OK for t/o, card to contractor. 8/3/2001 2:39:02 PM
BLD-Other8/2/20018/2/20018/2/2001PPART
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 08/02/2001 at 10:15:10. Contact: ###-####...conf. w/ bldr 8/2/2001 5:39:02 PM
FIRE-Final Inspection8/1/20018/1/20018/1/2001PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 08/01/2001 at 09:14:22. Contact: . 8/1/2001 1:33:16 PM
FIRE-Final Inspection7/24/20017/24/20017/24/2001PFAIL
DetailsRick Jackson
Added by Inspector: 409 On 7/24/2001 3:40:25 PM plywood walls; emergency lighting; exit signs and alarm problems
BLD-Other7/16/20017/16/20017/16/2001PPART
DetailsJim Storey
Scheduled by a contractor via Hello! on 07/16/2001 at 09:31:56. Contact: ###-####. conf need others to sign off. 7/16/2001 4:11:33 PM
BLD-Conference7/2/20017/2/20017/2/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 7/2/2001 1:45:34 PM w/ owner need other finals 1st
BLD-Final6/29/20017/2/20017/2/2001ANR
DetailsRuss Owen
terry ###-####
BLD-Conference6/29/20016/29/20016/29/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 6/29/2001 2:18:00 PM w/ owner & contractor....need fire ok prior to struct. ok
BLD-Conference6/26/20016/26/20016/26/2001APART
DetailsCarl Dependahl
Added by Inspector: 340 On 6/26/2001 9:23:07 AM w/ 337....need Musgrove's letter re hvac design, consult w/ Westfall.
BLD-Conference6/26/20016/26/20016/26/2001PPASS
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 06/26/2001 at 08:19:34. Contact: ###-####. w/ owner & bldr....keep c/n; install fire dampers at r/a chase at bsmt lid as per 337....ok to mitigate nr, non-ducted r/a "shaft" 6/26/2001 3:06:05 PM
FIRE-Conference6/26/20016/26/20016/26/2001PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 06/26/2001 at 08:21:03. Contact: ###-####. exit requirement; exit signs and emergency lights; extinguishers, etc. 6/26/2001 2:23:29 PM
BLD-Framing/Rough-in6/21/20016/21/20016/21/2001PPART
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 06/21/2001 at 08:56:58. Contact: . ok to cover lids & over stage; need consult re hvac 6/21/2001 1:31:13 PM
BLD-Framing/Rough-in6/20/20016/20/20016/20/2001PFAIL
DetailsCarl Dependahl
###-####; c/n, masonry lintels, fireblocks, hvac?? 6/20/2001 4:56:34 PM