Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberBLD01-01560
StatusFinaled
Name EVANGELICAL LUTHERAN
Site Address 3115 N SYCAMORE DR
Project NameBOISE SAMARITAN VILLAGE
Customer Number 
ePlanReviewNo
Description
THE BOISE SAMARITAN VILLAGE ADDITION - TO CONSTRUCT A 6,746 SQ. FT. , ONE STORY, TYPE V1HR NURSING HOME BUILDING SEPARATED TO THE EXISTING STRUCTURE WITH A TWO HOUR AREA SEPARATION WALL. ALL WORK IS PER APPROVED PLANS AND ATTACHMENTS. THIS BUILDING IS FULLY FIRE SPRINKLERED FOR AREA.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 7/24/20027/24/2002 DONE
Details
BLD-Final4/23/20024/24/20024/24/2002PPASS
DetailsDave Hannah
Scheduled by a contractor via Hello! on 04/23/2002 at 16:18:54. Contact: ###-####.ok for perm occ 4/24/2002 2:57:39 PM
FIRE-Alarm Testing4/19/20024/22/20024/22/2002PCANC
DetailsTroy Cobbley
duplicate inspection 4/23/2002 11:50:57 AM
FIRE-Final Inspection4/19/20024/22/20024/22/2002PPASS
DetailsTroy Cobbley
life safety, fire alarm and fire sprinkler finaled 4/23/2002 11:50:32 AM
BLD-Wall cover3/10/20023/11/20023/11/2002APART
DetailsRuss Owen
Scheduled by a contractor via Hello! on 03/10/2002 at 09:58:01. Contact: ###-####. Ok to rock drop ceiling in kitchen. 3/11/2002 10:55:54 AM
BLD-Wall cover3/8/20023/8/20023/8/2002PFAIL
DetailsDave Hannah
Scheduled by a contractor via Hello! on 03/08/2002 at 08:29:46. Contact: ###-####. needs to fire caulk around penetrations walls and ceiling 3/8/2002 3:27:13 PM
BLD-Wall cover3/4/20023/4/20023/4/2002PPASS
DetailsTony Young
Scheduled by a contractor via Hello! on 03/04/2002 at 08:53:10. Contact: ###-####.
BLD-Wall cover3/1/20023/1/20023/1/2002PFAIL
DetailsRuss Owen
Scheduled by a contractor via Hello! on 03/01/2002 at 10:01:55. Contact: ###-####. corridor back to back boxes req protection also there are side mounted fire dampers with pipe penetrations near them with no protection and other sheetrock holes. Talked with job supper will correct and recall. 3/1/2002 5:10:22 PM
BLD-Wall cover2/25/20022/26/20022/26/2002APART
DetailsJim Storey
Scheduled by a contractor via Hello! on 02/25/2002 at 18:59:01. Contact: ###-####. need to start 2 hr assemby for insp. steel ele boxes need protection of thrur pendatratinon exit head height min 7 ft. okto start coridor gyp but not with out reinsp of 2 hr.. 2/26/2002 11:59:03 AM
BLD-Conference2/19/20022/20/20022/20/2002ADONE
DetailsDave Hannah
Scheduled by a contractor via Hello! on 02/19/2002 at 16:47:53. Contact: . contractor added walls in attic space cutting off path of smoke to alarms needs to remove walls and bld as per plans so smoke det will work will mantain 1hr construction 2/20/2002 11:24:37 AM
BLD-Wall cover2/12/20022/13/20022/13/2002APART
DetailsTony Young
Scheduled by a contractor via Hello! on 02/12/2002 at 16:13:23. Contact: .
ok to cover main hall pending electrical rouph 2/13/2002 3:01:59 PM
BLD-Framing/Rough-in2/7/20022/8/20022/8/2002APART
DetailsTony Young
Scheduled by a contractor via Hello! on 02/07/2002 at 16:39:06. Contact: .
ok to insulate main room, may need to remove some areas for trades, and fire caulking at top plate 2/8/2002 10:00:03 AM
BLD-Conference2/5/20022/5/20022/5/2002APASS
DetailsCarl Dependahl
Added by Inspector: 340 On 2/5/2002 10:33:16 AM firestopping, prior c/n w/ Tony & Joel at site
BLD-Framing/Rough-in2/4/20022/5/20022/5/2002APART
DetailsTony Young
Scheduled by a contractor via Hello! on 02/04/2002 at 12:52:24. Contact: ###-####.
ok to cover north rooms 2/5/2002 10:26:20 AM
BLD-Framing/Rough-in1/28/20021/28/20021/28/2002PPART
DetailsTony Young
Scheduled by a contractor via Hello! on 01/28/2002 at 08:35:45. Contact: .
ok to cover south and west walls, pending trades 1/28/2002 3:43:07 PM
BLD-Framing/Rough-in1/23/20021/23/20021/23/2002PPART
DetailsTony Young
Scheduled by a contractor via Hello! on 01/23/2002 at 08:06:48. Contact: ###-####.see c/n for remaining items 1/23/2002 4:37:29 PM
BLD-Framing/Rough-in1/14/20021/15/20021/15/2002AFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 01/14/2002 at 15:51:31. Contact: .c/n: hd's, beam support details, 1hr assemblies not done...ok to pre-rock mech chase w/ other trade ok's. Partial insp. only. 1/15/2002 12:32:12 PM
BLD-Framing/Rough-in1/9/20021/10/20021/10/2002APART
DetailsTony Young
Scheduled by a contractor via Hello! on 01/09/2002 at 15:37:08. Contact: .
ext shear ok 1/10/2002 11:58:21 AM
BLD-Framing/Rough-in1/8/20021/9/20021/9/2002AFAIL
DetailsTony Young
Scheduled by a contractor via Hello! on 01/08/2002 at 14:03:22. Contact: .
ext. shear needs more nailing per plans 1/9/2002 11:41:37 AM
BLD-Framing/Rough-in12/19/200112/20/200112/20/2001PPART
DetailsTony Young
Scheduled by a contractor via Hello! on 12/19/2001 at 14:29:57. Contact: .
roof nailing, wip, ok 12/20/2001 3:52:12 PM
BLD-Foundation11/25/200111/26/200111/26/2001APART
DetailsTony Young
Scheduled by a contractor via Hello! on 11/25/2001 at 05:47:53. Contact: .
wip, pending si report 11/26/2001 10:25:06 AM
BLD-Foundation11/19/200111/20/200111/20/2001APART
DetailsTony Young
Scheduled by a contractor via Hello! on 11/19/2001 at 11:33:51. Contact: .
pan deck? pending si report 11/20/2001 11:33:34 AM
BLD-Foundation11/1/200111/2/200111/2/2001APART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 11/01/2001 at 13:16:24. Contact: . wip pending report from strata 11/2/2001 10:21:13 AM
BLD-Footing10/26/200110/26/200110/26/2001PPART
DetailsTony Young
Scheduled by a contractor via Hello! on 10/26/2001 at 09:54:24. Contact: .
wip, pending si report 10/26/2001 2:49:58 PM
BLD-Footing10/23/200110/24/200110/24/2001APART
DetailsTony Young
Scheduled by a contractor via Hello! on 10/23/2001 at 13:32:00. Contact: .
pending si report 10/24/2001 12:05:42 PM