BLD-Aging Inspection | 12/8/2003 | 12/8/2003 | 12/8/2003 | | PASS |
Jim Storey
|
|
|
|
BLD-Conference | 6/19/2003 | 6/30/2003 | 6/30/2003 | A | DONE |
Carl Dependahl
|
|
|
aging follow-up...record shows final 6/30/2003 9:20:22 AM
|
BLD-Final | 1/17/2003 | 1/21/2003 | 1/21/2003 | A | PASS |
Jim Storey
|
|
|
ALLAN ###-#### Internet Inspection Request from: Marsha Smylie
|
Permanent Occupancy | | 1/21/2003 | 1/21/2003 | | DONE |
|
|
|
|
Code Occupancy Approval | | | 1/13/2003 | | PASS |
|
|
|
Compliance met.
|
BLD-Other | 12/19/2002 | 12/19/2002 | 12/19/2002 | P | PASS |
Jim Storey
|
|
|
resubmital ok and archived.
|
FIRE-Final Inspection | 12/4/2002 | 12/4/2002 | 12/4/2002 | P | PASS |
Rick Jackson
|
|
|
|
BLD-Final | 10/15/2002 | 10/16/2002 | 10/16/2002 | P | PART |
Russ Owen
|
|
|
Phone #: ###-#### Internet Inspection Request from: Amy Lawsonok temp oc c/n posted. 10/16/2002 4:34:13 PM
|
FIRE-Final Inspection | 10/15/2002 | 10/16/2002 | 10/16/2002 | P | PART |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Amy Lawson temp occ approved per Ren Ross pending resolution of the FDC location 10/16/2002 4:24:21 PM
|
FIRE-Final Inspection | 10/14/2002 | 10/15/2002 | 10/15/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### alan alarms not installed per plans; need to test emergency lights; FDC not within 40 ft of road 10/15/2002 6:06:41 PM
|
FIRE-Final Inspection | 10/11/2002 | 10/11/2002 | 10/11/2002 | P | FAIL |
Rick Jackson
|
|
|
10/11/2002 4:47:51 PM need exit signs to work on battery; need to test alarms/sprinklers; knox box; test emergency lights 10/11/2002 4:49:00 PM
|
Code Occupancy Approval Temp | 10/10/2002 | 10/10/2002 | 10/10/2002 | P | FAIL |
Wm. Michael Meloy
|
|
|
Discussed bonding with Allen, ###-####. The landscaping is estimated at slightly over $49,000. I said that he could post a bond at $54,000 for temp occupancy. 10/10/2002 1:37:59 PM 10/10/2002 1:38:55 PM
|
BLD-Wall cover | 6/19/2002 | 6/19/2002 | 6/19/2002 | P | PASS |
Steven Webb
|
|
|
Scheduled by a contractor via Hello! on 06/19/2002 at 07:31:47. Contact: ###-####. Ok to cover 6/19/2002 3:22:29 PM
|
FIRE-Final Inspection | 6/18/2002 | 6/19/2002 | 6/19/2002 | A | CANC |
Rick Jackson
|
|
|
ALAN ###-#### wrong type inspection; see sprinkler r/i for this date 6/19/2002 8:11:19 AM
|
FIRE-Sprinkler Rough-in | 6/19/2002 | 6/19/2002 | 6/19/2002 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 6/19/2002 8:09:46 AM okay to cover
|
BLD-Framing/Rough-in | 6/14/2002 | 6/14/2002 | 6/14/2002 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Framing/Rough-in | 6/13/2002 | 6/14/2002 | 6/14/2002 | A | NR |
Carl Dependahl
|
|
|
allan ###-####- re-insp fr ...need ICBO interpretation re return airs...ok per GS? keep 420's c/n. 6/14/2002 2:55:28 PM
|
FIRE-Sprinkler Rough-in | 6/14/2002 | 6/14/2002 | 6/14/2002 | A | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 6/14/2002 11:00:34 AM r/i okay; not approved for cover pending tenting of wet sprinkler piping
|
BLD-Framing/Rough-in | 6/13/2002 | 6/13/2002 | 6/13/2002 | P | FAIL |
Steven Webb
|
|
|
allan ###-#### fr C/N posted in job trailer 6/13/2002 4:15:06 PM
|
BLD-Framing/Rough-in | 5/20/2002 | 5/21/2002 | 5/21/2002 | A | PART |
Steven Webb
|
|
|
shear allen- ###-#### Ext. Shear--Ok to cover 5/21/2002 11:33:18 AM
|
BLD-Framing/Rough-in | 5/17/2002 | 5/20/2002 | 5/20/2002 | P | FAIL |
Steven Webb
|
|
|
###-#### C/N issued. Nail above hd, nailing light per plans at misc. locations. 5/20/2002 4:21:58 PM
|
Permanent Occupancy | | 4/30/2002 | 4/30/2002 | | DONE |
|
|
|
|
BLD-Footing | 4/23/2002 | 4/24/2002 | 4/24/2002 | A | PASS |
Steven Webb
|
|
|
###-####
|
BLD-Footing | 4/18/2002 | 4/19/2002 | 4/19/2002 | A | PASS |
Steven Webb
|
|
|
###-####
|
BLD-Footing | 4/17/2002 | 4/18/2002 | 4/18/2002 | P | PART |
Steven Webb
|
|
|
###-#### not ready for entire inspection--conferenced with p. manager in regards to upcoming construction. 4/18/2002 4:14:40 PM
|