Permit Information
Permit NumberBLD01-02848
StatusFinaled
Name MICRON TECHNOLOGY INC
Site Address 8000 S FEDERAL WAY
Project NameMICRON MASK SHOP
Customer NumberPCS3278
ePlanReviewNo
Description
MICRON MASK SHOP TENANT IMPROVEMENT (PCS #80-20003278) * TO FINISH THE MICRON MASK SHOP 80,350 SQUARE FOOT, TWO STORY WITH 26,870 BASEMENT FABRICATION AND OFFICE SHELL BUILDING FOR OCCUPANCY. THIS BUILDING WILL CONTAIN A 13,725 SQUARE FOOT, ONE STORY OFFICE AREA AND THE REMAINDER OF THE BUILDING WILL BE A TWO STORY WITH BASEMENT FABRICATION AND STORAGE AREA. THE OFFICE AREA IS BEING SEPARATED FROM THE FABRICATION AREAS BY A TWO-HOUR FIRE-RESISTIVE AREA SEPARATION WALL. THE BASEMENT AREAS ARE PRIMARILY NORMALLY UNOCCUPIED CHEMICAL STORAGE, SUPPLY AND RECOVERY AREAS. THE SECOND FLOOR IS PRIMARILY NORMALLY UNOCCUPIED MECHANICAL AND FAN DECK AREAS. THIS BUILDING IS FULLY FIRE SPRINKLED. ALL CONSTRUCTION PER THE APPROVED PLANS AND ATTACHED COMMENT LIST. THE SHELL BUILDING WAS CONSTRUCTED UNDER PERMIT BLD01-02222. DRH01-00127/CUP01-00077/PC#822-01/JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection12/9/200312/9/200312/9/2003 PASS
DetailsJim Storey
passed on 10/18/02 12/9/2003 8:10:28 AM
BLD-Final10/17/200210/18/200210/18/2002PPASS
DetailsJim Storey
Permanent Occupancy 10/18/200210/18/2002 DONE
Details
BLD-Final10/17/200210/17/200210/17/2002PCANC
DetailsJim Storey
###-#### les
BLD-Final10/14/200210/15/200210/15/2002AFAIL
DetailsJim Storey
missing 3 inch plastic pipe collor at h-3 occ. 10/15/2002 10:39:43 AM
BLD-Final10/11/200210/14/200210/14/2002ANR
DetailsJim Storey
BLD-Final10/11/200210/14/200210/14/2002ANR
DetailsJim Storey
Code Occupancy Approval10/14/200210/14/200210/14/2002PPASS
DetailsWm. Michael Meloy
Approved 10/14/2002 2:57:45 PM
BLD-Final10/11/200210/11/200210/11/2002PNR
DetailsJim Storey
les; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
BLD-Final10/11/200210/11/200210/11/2002PNR
DetailsJim Storey
les; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIRE-Final Inspection10/11/200210/11/200210/11/2002PPASS
DetailsRick Jackson
les; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
BLD-Final10/8/200210/9/200210/9/2002PFAIL
DetailsJim Storey
les; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie h2 wall protection/ door grout/ wire glazing sub fab. 10/9/2002 3:53:46 PM
FIRE-Final Inspection10/8/200210/9/200210/9/2002PCANC
DetailsRick Jackson
les; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIRE-Final Inspection10/3/200210/4/200210/4/2002PFAIL
DetailsRick Jackson
###-#### LES fire stop new shower water line in chem room; EQ main sprinkler riser 10/4/2002 4:53:45 PM
FIRE-Final Inspection10/2/200210/3/200210/3/2002ANR
DetailsRick Jackson
FN LES ###-#### met with Les and will have to test the alarms; will reschedule 10/3/2002 10:16:30 AM
BLD-Other8/8/20028/8/20028/8/2002PPASS
DetailsJim Storey
LES ; Phone #: ###-####temp occ of hpm area and upper and lower fab space. card on file with scope of areas. 8/8/2002 4:23:16 PM
FIRE-Alarm Testing8/8/20028/8/20028/8/2002PPART
DetailsRick Jackson
LES AND FINAL; Phone #: ###-#### okay to occupy/use the subfab HPM corridor and third floor corridors per letter from Earthtech 8/8/2002 4:21:21 PM
BLD-Final8/6/20028/7/20028/7/2002PFAIL
DetailsJim Storey
Scheduled by a contractor via Hello! on 08/06/2002 at 13:19:22. Contact: ###-####.fire chalk/ door closer/ exit sign/ fire wrap band and termanation atchement. 8/7/2002 4:46:50 PM
FIRE-Final Inspection8/6/20028/7/20028/7/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 08/06/2002 at 13:20:06. Contact: ###-####. met with Les and Jim Story to go over the requirements for the next phase of occupancy - fan deck and HPM corridor; will need dampers/detectors working on fan deck, exit signs and doors installed per metting with Les in HPM corridor 8/7/2002 5:01:58 PM
BLD-Final8/1/20028/2/20028/2/2002APART
DetailsJim Storey
10:00 am apointment. temp occ for exit path around fab on first floor and all stair inclosers.for tool instal in the fab. no chem load in the bldg. with out approval and sign off for total bldg. occ. 8/2/2002 1:04:24 PM
FIRE-Final Inspection8/1/20028/2/20028/2/2002APART
DetailsRick Jackson
###-#### with Jim Storey; approved use of corridor on level one and stair towers 8/2/2002 1:32:53 PM
BLD-Final8/1/20028/1/20028/1/2002PPART
DetailsJim Storey
Las; Phone #: ###-####
BLD-Final7/25/20027/26/20027/26/2002PCANC
DetailsJim Storey
Scheduled by a contractor via Hello! on 07/25/2002 at 13:09:21. Contact: ###-####.ul chem valve isue. 7/26/2002 1:48:52 PM
FIRE-Final Inspection7/25/20027/26/20027/26/2002PCANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 07/25/2002 at 13:14:28. Contact: ###-####. received a call from Jim Storey to cancel 7/26/2002 3:44:05 PM
BLD-Final7/18/20027/19/20027/19/2002PPART
DetailsJim Storey
LES; Phone #: ###-####office only per condition list/ 7/19/2002 4:30:14 PM
FIRE-Final Inspection7/22/20027/19/20027/19/2002APART
DetailsRick Jackson
Added by Inspector: 409 On 7/22/2002 9:56:40 AM okay to occupy offices areas as identified on letter from Micron; the areas approved on letter are the only areas to occupy
FIRE-Final Inspection7/18/20027/19/20027/19/2002AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 07/18/2002 at 13:58:00. Contact: ###-####. tested the VSES and EAS - okay; still not ready for final - lighting; exit signs; extension cords; etc. 7/19/2002 10:10:14 AM
BLD-Final7/17/20027/18/20027/18/2002AFAIL
DetailsJim Storey
Scheduled by a contractor via Hello! on 07/17/2002 at 13:40:45. Contact: ###-####.doors and fire stopping/ chem room wall repair, 7/18/2002 12:29:02 PM
FIRE-Alarm Testing7/17/20027/17/20027/17/2002AFAIL
DetailsRick Jackson
Added by Inspector: 409 On 7/17/2002 10:33:11 AM completed alarm testing; panel in trouble due to main board problem; vses and eas not complete;
FIRE-Final Inspection7/15/20027/16/20027/16/2002AFAIL
DetailsRick Jackson
LES ###-#### strobes obstructed in fan deck level; will continue av testing 7/17; all devices tested okay - complete with all device testing; exiting from subfab into stairs obstructed by plastic sheeting; need walls to conceal open areas between RF's in subfab; 7/16/2002 6:12:07 PM
BLD-Framing/Rough-in7/15/20027/15/20027/15/2002PFAIL
DetailsJim Storey
les ###-#### fr les ###-#### fr insulated piping not per asslembly. 7/15/2002 5:19:19 PM
FIRE-Final Inspection7/15/20027/15/20027/15/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 07/15/2002 at 09:35:09. Contact: ###-####. continued to test the alarms; will continue on 7/16 7/16/2002 9:48:21 AM
BLD-Other7/12/20027/12/20027/12/2002PCANC
DetailsJim Storey
temp occup ###-#### les called and will resch. 7/12/2002 4:23:41 PM
FIRE-Final Inspection7/10/20027/12/20027/12/2002AFAIL
DetailsRick Jackson
###-#### started testing detectors - didn't shut down MAU's; will continue on 7/15 7/12/2002 3:44:29 PM
BLD-Framing/Rough-in7/10/20027/11/20027/11/2002ANR
DetailsJim Storey
###-####
BLD-Framing/Rough-in7/11/20027/11/20027/11/2002PNR
DetailsJim Storey
###-#### les
FIRE-Final Inspection7/10/20027/11/20027/11/2002PFAIL
DetailsRick Jackson
###-#### tested pull stations and sprinkler tampers/flows; labels for some pull stations not correct 7/11/2002 4:34:40 PM
FIRE-Conference7/9/20027/10/20027/10/2002APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 07/09/2002 at 13:06:40. Contact: ###-####. met with GC about getting leter in for temporary occupancy to Dave Miller 7/10/2002 11:00:04 AM
BLD-Framing/Rough-in7/9/20027/9/20027/9/2002PFAIL
DetailsJim Storey
fr les- ###-#### fr les- ###-#### chem trays not per listing 2 hr not patched. 7/9/2002 3:49:46 PM
BLD-Framing/Rough-in7/2/20027/3/20027/3/2002APART
DetailsJim Storey
ceiling insp- les- ###-#### main office only 7/3/2002 10:22:37 AM
BLD-Framing/Rough-in7/1/20027/1/20027/1/2002PPART
DetailsJim Storey
les- ###-####fr inspclean rm ceilling grid ok/ fire wall at rain leader needs patch at unastrut and chec pipe penatration. 7/1/2002 3:45:03 PM
BLD-Framing/Rough-in6/24/20026/25/20026/25/2002PFAIL
DetailsJim Storey
###-#### LES fire stopping. 6/25/2002 4:04:07 PM
BLD-Framing/Rough-in6/18/20026/19/20026/19/2002APART
DetailsJim Storey
###-#### ###-####2 hr north ele penatration next to duct. 6/19/2002 5:24:31 PM
BLD-Framing/Rough-in6/17/20026/18/20026/18/2002PCANC
DetailsJim Storey
FIRE WALL ###-#### LES called work not done will re-sch. 6/18/2002 2:51:14 PM
BLD-Other6/14/20026/14/20026/14/2002PCANC
DetailsJim Storey
###-#### ###-#### less called and cancled. 6/14/2002 3:27:50 PM
FIRE-Conference6/11/20026/11/20026/11/2002PPART
DetailsRick Jackson
###-#### met with Les and went over exit signs and requirements for occupancy; reviewed alarm plans and locations of devices; will need additional strobes in main electrical room and dectector for damper in boiler room wall 6/12/2002 7:39:01 AM
BLD-Framing/Rough-in3/13/20026/6/20026/6/2002ANR
DetailsJim Storey
###-#### or ###-#### Les c/n stands. 6/6/2002 12:06:39 PM
BLD-Framing/Rough-in3/13/20025/30/20025/30/2002ANR
DetailsJim Storey
###-#### or ###-#### Les ###-#### or wip.###-#### Les 5/30/2002 12:53:47 PM
BLD-Framing/Rough-in3/13/20025/23/20025/23/2002APART
DetailsJim Storey
###-#### or ###-#### Les all lateral bracing ok in all exterior ok to cover balance of interior side of walls./ raillroad seam and new ele penatration in east side of 2 hr wall north end./ drinking foutian in 2 hr wall c/n resolved / srair 6 wall alinment needed to maintaine wall assemblie./ ele fire stopping submitals pending review. 5/23/2002 11:59:39 AM
BLD-Framing/Rough-in5/17/20025/17/20025/17/2002PPASS
DetailsJim Storey
les ###-####south 2 nd floor exterior wall ok for cover and north 2nd floor / west stair mech shaft wall and stair incloser ok for cover fire stopping ok. 5/17/2002 3:59:39 PM
BLD-Framing/Rough-in3/13/20025/16/20025/16/2002ANR
DetailsJim Storey
###-#### or ###-#### Les
FIRE-Conference5/15/20025/16/20025/16/2002ACANC
DetailsRick Jackson
Scheduled by Inspector: 409 On 5/15/2002 12:41:19 PM
BLD-Framing/Rough-in5/13/20025/14/20025/14/2002APART
DetailsJim Storey
###-#### les ###-#### lesrain leader at 2 hr wall gyp repair ok 5/14/2002 9:35:57 AM
BLD-Framing/Rough-in5/9/20025/10/20025/10/2002AFAIL
DetailsJim Storey
LES ###-#### OR ###-#### c/n stands. 5/10/2002 11:23:19 AM
BLD-Framing/Rough-in3/13/20025/9/20025/9/2002ANR
DetailsJim Storey
###-#### or ###-#### Les c/n stands. 5/9/2002 10:40:53 AM
BLD-Conference5/7/20025/7/20025/7/2002AFAIL
DetailsJim Storey
1. (Wall through penetrations that prevent passage of flame & hot gases) Where the penetrating items are steel, ferrous, or copper pipes or steel conduits, the material used to fill the annular space shall prevent the passage of flame and hot gases sufficient to ignite cotton waste when subjected to 1997 UBC Standard 7-1 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch of water column at the location of the penetration for the time period equivalent to the fire rating of the construction penetrated. (1997 UBC 709.6.1 Exception #2)

2. (Wall membrane penetrations) Membrane penetrations of fire-resistive walls shall comply with 1997 UBC Section 709.6 as required for wall through penetrations. (1997 UBC 709.7)

3. submit fire stopping listing for all trades for insp.
BLD-Energy code compliance5/3/20025/7/20025/7/2002APART
DetailsJim Storey
###-#### ###-####west side of 2 hr wall assemblie ok/ 5/7/2002 11:24:35 AM
BLD-Wall cover5/2/20025/3/20025/3/2002PFAIL
DetailsJim Storey
###-#### LES 2 hr wall /rain leader/seam lap and screw sch./box and fire shuder in loby corridor. 5/3/2002 4:42:58 PM
BLD-Framing/Rough-in3/13/20025/2/20025/2/2002AFAIL
DetailsJim Storey
1. (Fire-resistive walls) Fire-resistive walls and partitions shall be assumed to have the fire-resistance ratings set forth in 1997 UBC Table 7-B. (1997 UBC 709.1) Generic fire-resistance ratings (those not designated as PROPRIETARY in the listing) in the "Fire-Resistance Design Manual", Fourteenth Edition, dated April 1994, as published by the Gypsum Association, may also be accepted. (1997 UBC Table 7-B footnote a) Selected systems shall be completely described or detailed on the drawings (including attachments).butt joints and lap distances not achived on 2 hr wall on g line as well as screw sch. remove finsh layer and repair.
BLD-Framing/Rough-in3/13/20024/25/20024/25/2002AFAIL
DetailsJim Storey
4/25/2002 1:18:06 PM gyp on area septration wa;ll at each end needs lap of 24 horrizontal. 4/25/2002 1:46:20 PM
BLD-Framing/Rough-in3/13/20024/18/20024/18/2002AFAIL
DetailsJim Storey
1. (Stairway rise and run) The rise of steps and stairs shall not be less than 4 inches nor more than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. Except as permitted for circular, winding, and spiral stairways, the run shall not be less than 11 inches as measured horizontally between the vertical planes of the furthermost projection of adjacent treads or nosings. Stair treads shall be of uniform size and shape, except the largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. (1997 UBC 1003.3.3.3) Note the exception to tread and riser dimensions for private stairways and stairways to unoccupied roofs and. Also, note the exception to dimensions of risers adjoining a sloping public way. 2. need engineering for previous c/n.
BLD-Concrete4/16/20024/16/20024/16/2002PFAIL
DetailsJim Storey
lap splice at 3/e not achived at cold joint. provide splice or engineered repair.
BLD-Framing/Rough-in3/13/20024/11/20024/11/2002ACANC
DetailsJim Storey
###-#### or ###-#### Les
BLD-Concrete4/4/20024/4/20024/4/2002PPART
DetailsJim Storey
rebar les- ###-#### covered with special insp 4/5/2002 7:36:16 AM
BLD-Framing/Rough-in3/13/20024/4/20024/4/2002APART
DetailsJim Storey
###-#### or ###-#### Les pending special inspction. 4/4/2002 12:10:30 PM
BLD-Framing/Rough-in3/13/20024/4/20024/4/2002ACANC
DetailsJim Storey
###-#### or ###-#### Les
BLD-Framing/Rough-in3/13/20023/28/20023/28/2002APART
DetailsJim Storey
###-#### or ###-#### Les roof decks ok 3/28/2002 4:41:54 PM
BLD-Framing/Rough-in3/25/20023/25/20023/25/2002PPART
DetailsJim Storey
###-#### LES c/n made ok archived info from engoineer into file/cup roof deck welding ok pending special insp. report on area not complet./diphram on office roof to be checed thursday. 3/25/2002 4:10:18 PM
BLD-Framing/Rough-in3/13/20023/21/20023/21/2002APART
DetailsJim Storey
###-#### or ###-#### Les c/n stands.wip 3/21/2002 11:00:39 AM
BLD-Concrete3/18/20023/18/20023/18/2002PPART
DetailsJim Storey
###-#### ok pending si report. 3/18/2002 3:54:11 PM
BLD-Framing/Rough-in3/13/20023/14/20023/14/2002AFAIL
DetailsJim Storey
###-#### or ###-#### Les c/n missing hair pin at n/4 . steel fit up justify substanal contact peramitor by engineer./ rfi to prefab to spec. diphram screw sch. 3/14/2002 10:30:40 AM 3/14/2002 10:35:39 AM