BLD-Final | 3/8/2002 | 3/11/2002 | 3/11/2002 | A | FAIL |
Jim Storey
|
|
|
LARRY ###-#### need 5/8 gyp on shell side of tennet wall. 3/11/2002 9:08:44 AM
|
BLD-Final | 3/11/2002 | 3/11/2002 | 3/11/2002 | P | PASS |
Russ Owen
|
|
|
fn occ ###-####- larry ok perm co. 3/11/2002 4:57:00 PM
|
FIRE-Final Inspection | 3/8/2002 | 3/11/2002 | 3/11/2002 | A | PASS |
Troy Cobbley
|
|
|
Fire life/safety and fire alarm finaled 3/11/2002 2:10:00 PM
|
Permanent Occupancy | | 3/11/2002 | 3/11/2002 | | DONE |
|
|
|
|
BLD-Final | 3/7/2002 | 3/8/2002 | 3/8/2002 | P | NR |
Carl Dependahl
|
|
|
###-#### LARRY FOR OCCUPANCY
|
FIRE-Final Inspection | 3/7/2002 | 3/8/2002 | 3/8/2002 | A | FAIL |
Troy Cobbley
|
|
|
add sprinkler pendant in cooler and in kitchen, mount fire extinguisher, provide air balance report for hood, provide power to hood so shut down can be verified, contact fire dept to corrdinate key for lock box 3/8/2002 1:22:38 PM
|
BLD-Framing/Rough-in | 2/13/2002 | 2/14/2002 | 2/14/2002 | A | PASS |
Dave Hannah
|
|
|
###-#### LARRY GRID ceiling grid ok to cover 2/14/2002 11:23:50 AM
|
BLD-Framing/Rough-in | 1/15/2002 | 1/16/2002 | 1/16/2002 | A | PASS |
Tom Arcoraci
|
|
|
WALL COVER LARRY ok to cover 1/16/2002 9:36:35 AM
|
BLD-Wall cover | 1/10/2002 | 1/11/2002 | 1/11/2002 | A | PART |
Tony Young
|
|
|
###-####
ok to cover int. walls, c/n posted on demising wall and soffit areas 1/11/2002 10:26:02 AM
|