BLD-Final | 7/2/2004 | 7/2/2004 | 7/2/2004 | P | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 7/2/2004 at 9:32:46 AM. Contact: ###-####. C/C issued. 7/2/2004 3:50:51 PM
|
BLD-Other | 6/22/2004 | 6/23/2004 | 6/23/2004 | A | PART |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 6/22/2004 at 11:27:20 AM. Contact: ###-####. 6/23/2004 11:28:18 AM Call Steve.....Meet in Lobby. checking Mfg walls for bracing. 6/23/2004 11:29:59 AM
|
BLD-Final | 3/31/2004 | 4/1/2004 | 4/1/2004 | P | FAIL |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 3/31/2004 at 11:51:00 AM. Contact: ###-####. Needs the electrical permit finaled, which is expired, electrical inspector has talked with tri-state electric. Also the tops of the pre-fab walls, hve not been tied off. 4/1/2004 12:28:02 AM
|
BLD-Final | 3/24/2004 | 3/25/2004 | 3/25/2004 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 3/24/2004 at 2:48:10 PM. Contact: ###-####. needs elec final and plumb final maybe ,ok for final when these are complete 3/25/2004 9:18:08 AM 3/25/2004 9:19:57 AM
|
FIRE-Final Inspection | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire life safety, fire alarm and fire sprinklers finaled
|
BLD-Aging Inspection | 1/13/2004 | 1/13/2004 | 1/13/2004 | | CANC |
Russ Owen
|
|
|
Fire /life safety will check out. 1/20/2004 1:24:36 PM
|
BLD-Conference | 5/13/2003 | 5/13/2003 | 5/13/2003 | A | CANC |
Russ Owen
|
|
|
talked with steve he has submitted plans to the fire life/safety plan review division.
|
BLD-Aging Inspection | 3/26/2003 | 3/26/2003 | 3/26/2003 | | CANC |
Russ Owen
|
|
|
called steve will be submitting plans in about 2 weeks to resolve fire/life safety insp. 3/27/2003 3:16:44 PM
|
FIRE-Final Inspection | 12/23/2002 | 12/30/2002 | 12/30/2002 | P | FAIL |
Troy Cobbley
|
|
|
###-#### STEVE The fire door for the 2nd floor freight elevator does not latch when the fire alarm system is activated, provide a/v's within 15' of the ends of the corridors on the first and second floors, provide verification of fire/smoke damper activation per review comment #6, revise zone description and the FACP text so they match the device test and then retest, verify signals with the monitoring company, verify with the inspector the current draw on the notification circuits, provide map per review note #7, test the initiating devices. No area or duct smoke detectors were tested due to zone descriptions not matching. Do not final permit until the owner has the approved building plans on site 12/30/2002 4:23:28 PM
|
FIRE-Final Inspection | 4/12/2002 | 4/19/2002 | 4/19/2002 | A | FAIL |
Troy Cobbley
|
|
|
wall mounted device are wrong candella, wall listed devices mounted on ceiling. Review comments were not followed. Elevator recalled is wrong. I stopped inspection. Entire inspection needs to be started over. 4/19/2002 12:48:22 PM
|
BLD-Framing/Rough-in | 3/28/2002 | 3/29/2002 | 3/29/2002 | A | PART |
Russ Owen
|
|
|
###-####- steve r/i 2nd floor south side partition ok after ele. 3/29/2002 12:28:21 PM
|
BLD-Other | 2/20/2002 | 2/21/2002 | 2/21/2002 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 02/20/2002 at 16:27:59. Contact: ###-####.
|
BLD-Framing/Rough-in | 2/7/2002 | 2/7/2002 | 2/7/2002 | P | PASS |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 02/07/2002 at 10:12:02. Contact: ###-####.
|
BLD-Other | 1/29/2002 | 1/29/2002 | 1/29/2002 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 01/29/2002 at 08:58:25. Contact: ###-####.grid work in lower flor east side small arae on plans. 1/30/2002 9:15:40 AM
|
BLD-Framing/Rough-in | 1/22/2002 | 1/23/2002 | 1/23/2002 | A | NR |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 01/22/2002 at 14:34:32. Contact: ###-####.need trades signed off 1/23/2002 11:00:44 AM
|
BLD-Framing/Rough-in | 1/23/2002 | 1/23/2002 | 1/23/2002 | P | PART |
Russ Owen
|
|
|
Scheduled by Inspector: 415 On 1/23/2002 10:57:35 AM steve 321--9168. most new walls are complete. 1/24/2002 9:50:20 AM
|