Permit Information
Permit NumberBLD02-00031
StatusFinaled
Name ADA COUNTY CORONER (MORGUE)
Site Address 5550 W MORRIS HILL RD
Project Name 
Customer Number
ePlanReviewNo
Description
(ADA COUNTY CORONER - MORGUE) This building is fire sprinklered for area increase. To construct a 3,450 square foot morgue within an existing 24,000 square foot warehouse/office building to be used by the Ada County Coroner's Office. The Coroner will occupy the 3,450 square foot morgue, the 2,400 square foot 1st floor office area, and the 2,000 square foot 2nd floor office area (7,850 square feet total). Work is to include 2 toilet/shower rooms accessible to the disabled, a wheelchair lift accessible to the disabled, 2 restrooms modified to be more accessible to the disabled, interior nonbearing walls, a 300 square foot mechanical mezzanine, replaced concrete slabs, foam plastic freezer/cooler, and suspended ceilings all per approved drawings, engineering, and plan review conditions on file. The fire sprinkler system shall comply with NFPA 13-1999 as regulated by the Fire Department. Zoning approval by Scott Spjute. PC02-0012 **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/26/200212/27/200212/27/2002APASS
DetailsTom Arcoraci
###-#### ok for perm pending fire insp 12/26/2002 3:12:28 PM
FIRE-Final Inspection12/27/200212/27/200212/27/2002PPASS
DetailsRick Jackson
FIRE-Final Inspection12/26/200212/27/200212/27/2002AFAIL
DetailsRick Jackson
###-#### dave tested alarms; see FIR02-00463 for corrections 12/27/2002 10:55:11 AM
Permanent Occupancy 12/27/200212/27/2002 DONE
Details
BLD-Final11/12/200211/12/200211/12/2002PPART
DetailsTom Arcoraci
dave; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok for temp when fire signs card 11/12/02 3:19:31 PM
FIRE-Final Inspection11/12/200211/12/200211/12/2002PFAIL
DetailsTroy Cobbley
provide fire alarm drawings 11/12/2002 3:59:01 PM
FIRE-Final Inspection11/4/200211/4/200211/4/2002PFAIL
DetailsTroy Cobbley
provide approved hardware on the north corridor door, provide automatic shutdown for the hvac units. These detectors to be connected to the building fire alarm system and may require submittals to Boise city for approvals, provide manual pull station and relocate smoke detector from the wall to the deck. This also may require submittals to the city. Have the alarm contractor contact Sam Roger at ###-#### with any questions. Provide annual inspection report for the fire alarm system
BLD-Framing/Rough-in10/3/200210/3/200210/3/2002PPASS
DetailsTom Arcoraci
ceiling grid; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
BLD-Framing/Rough-in9/25/20029/25/20029/25/2002PPART
DetailsTom Arcoraci
ceiling grid; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok 9/25/2002 3:46:31 PM
BLD-Framing/Rough-in8/26/20028/28/20028/28/2002APART
DetailsTom Arcoraci
dave; Phone #: ###-#### ok to cover from bath to coolers check struts after duct work is installed no other places inspected 8/28/2002 1:55:55 PM
BLD-Footing7/22/20027/23/20027/23/2002APASS
DetailsTom Arcoraci
###-#### dave