Permanent Occupancy | | 1/16/2004 | 1/16/2004 | | DONE |
|
|
|
|
FIRE-Final Inspection | 12/31/2003 | 12/31/2003 | 12/31/2003 | P | PASS |
Rick Jackson
|
|
|
|
BLD-Final | 11/13/2003 | 11/14/2003 | 11/14/2003 | A | DONE |
Dave Hannah
|
|
|
fn john-- ###-####
|
FIRE-Final Inspection | 11/3/2003 | 11/3/2003 | 11/3/2003 | P | PART |
Rick Jackson
|
|
|
###-#### verified doors to elevator lobby and they all release on fire alarm and have positive latching 11/3/2003 3:18:38 PM
|
FIRE-Final Inspection | 10/9/2003 | 10/9/2003 | 10/9/2003 | P | PART |
Rick Jackson
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs tested elevator lobby doors for release with fire alarm and that is okay but doors don't remain latched as strike is released on fire; fire doors to remain latched but release lock 10/9/2003 4:36:41 PM
|
FIRE-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 | A | PART |
Rick Jackson
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie per Dave Miller fire/life safety will be on temp occupancy until the access control system is tested and disables with fire alarm activation and approval of the pressure reducing valve is submitted and approved by plan review 10/2/2003 9:14:25 AM
|
BLD-Final | 9/30/2003 | 10/1/2003 | 10/1/2003 | P | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 9/30/2003 at 6:24:44 PM. Contact: ###-####. ok for temp occ 10/1/2003 7:34:26 PM
|
BLD-Final | 9/30/2003 | 10/1/2003 | 10/1/2003 | A | CANC |
Dave Hannah
|
|
|
|
FIRE-Final Inspection | 9/30/2003 | 10/1/2003 | 10/1/2003 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/30/2003 at 6:23:04 PM. Contact: ###-####. doors not latching; need smoke seals on electrical room doors; left list with John with other items 10/1/2003 4:44:04 PM
|
BLD-Final | 9/26/2003 | 9/29/2003 | 9/29/2003 | P | PART |
Dave Hannah
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore walk project with john made a punch list 9/30/2003 11:25:03 AM
|
FIRE-Final Inspection | 9/26/2003 | 9/29/2003 | 9/29/2003 | A | FAIL |
Rick Jackson
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need to verify phase reversal for fire pump; wasn't a final but tested all sprinkler tampers and flows for exsisting and new systems; see previous final for correction list 9/29/2003 10:25:20 AM
|
FIRE-Final Inspection | 9/25/2003 | 9/26/2003 | 9/26/2003 | A | FAIL |
Rick Jackson
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs 9/26/2003 12:11:47 PM smoke seal on all rated doors; need floor drain, emergency lights and heat in fire pump room; stair signage; sprinkler heads fire proofed in stairs and elevator machine room; fire extinguishers require current inspection tag; see alarm permit for other items 9/26/2003 12:14:47 PM
|
FIRE-Final Inspection | 9/24/2003 | 9/25/2003 | 9/25/2003 | A | FAIL |
Rick Jackson
|
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Annette Moore started testing the alarms; see FIR03-00104 for info 9/25/2003 12:23:43 PM
|
BLD-Wall cover | 9/22/2003 | 9/23/2003 | 9/23/2003 | A | PART |
Dave Hannah
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Wall cover | 9/19/2003 | 9/19/2003 | 9/19/2003 | P | CANC |
Dave Hannah
|
|
|
JOHN; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
|
BLD-Wall cover | 9/17/2003 | 9/18/2003 | 9/18/2003 | A | PASS |
Dave Hannah
|
|
|
allen; Phone #: ###-#### Internet Inspection Request from: Annette Moore 4th floor elev shaft #1 ok to hang lid 9/18/2003 10:22:18 AM
|
BLD-Conference | 9/17/2003 | 9/17/2003 | 9/17/2003 | P | DONE |
Dave Hannah
|
|
|
list of items that need tobe completed for final 9/17/2003 4:32:28 PM
|
BLD-Wall cover | 9/15/2003 | 9/15/2003 | 9/15/2003 | P | NR |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
FIRE-Supply Line Cover | 9/15/2003 | 9/15/2003 | 9/15/2003 | P | FAIL |
Rick Jackson
|
|
|
JOHN CEILING COVER FIRE; Phone #: ###-#### Internet Inspection Request from: Marc Lileks not a supply line cover; penetrations in corridors still need work on all floors 9/15/2003 2:02:03 PM
|
BLD-Wall cover | 9/12/2003 | 9/12/2003 | 9/12/2003 | P | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
|
BLD-Conference | 9/11/2003 | 9/11/2003 | 9/11/2003 | A | DONE |
Dave Hannah
|
|
|
meeting on final occ and what needs tobe completed 9/11/2003 1:56:15 PM
|
BLD-Framing/Rough-in | 9/11/2003 | 9/11/2003 | 9/11/2003 | P | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
BLD-Framing/Rough-in | 9/9/2003 | 9/9/2003 | 9/9/2003 | P | PART |
Dave Hannah
|
|
|
john// ceiling cover; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 9/9/2003 4:34:42 PM
|
FIRE-Sprinkler Rough-in | 9/9/2003 | 9/9/2003 | 9/9/2003 | P | FAIL |
Rick Jackson
|
|
|
john// ceiling cover; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corridors not approved for cover - many penetrations require firestopping 9/9/2003 2:54:29 PM
|
BLD-Conference | 9/5/2003 | 9/5/2003 | 9/5/2003 | P | DONE |
Dave Hannah
|
|
|
|
BLD-Wall cover | 8/28/2003 | 8/28/2003 | 8/28/2003 | P | PART |
Dave Hannah
|
|
|
john shed; Phone #: ###-#### Internet Inspection Request from: Barbara Moore stair shafts ok fo second layer on one inside first on out stair 2 second on insde 8/29/2003 8:55:37 AM
|
BLD-Wall cover | 8/20/2003 | 8/21/2003 | 8/21/2003 | A | PART |
Dave Hannah
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
BLD-Conference | 8/19/2003 | 8/20/2003 | 8/20/2003 | A | DONE |
Dave Hannah
|
|
|
8:30am meeting with john and rick
|
FIRE-Conference | 8/19/2003 | 8/20/2003 | 8/20/2003 | A | PART |
Rick Jackson
|
|
|
met with Dave Hannah, John Shed, JP and subs about final requirements for occupancy. John Shed will provide checklist for final sign off 8/20/2003 10:43:50 AM
|
BLD-Wall cover | 8/14/2003 | 8/15/2003 | 8/15/2003 | A | PART |
Dave Hannah
|
|
|
|
BLD-Framing/Rough-in | 8/13/2003 | 8/13/2003 | 8/13/2003 | P | PART |
Dave Hannah
|
|
|
|
BLD-Wall cover | 8/13/2003 | 8/13/2003 | 8/13/2003 | P | PART |
Dave Hannah
|
|
|
Phone #: ###-#### Internet Inspection Request from: Linda Hartwell
|
BLD-Wall cover | 8/11/2003 | 8/11/2003 | 8/11/2003 | P | FAIL |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 2hr expansion joint between floors 8/11/2003 3:36:31 PM
|
BLD-Conference | 8/8/2003 | 8/8/2003 | 8/8/2003 | P | PASS |
Carl Dependahl
|
|
|
still need joint detail as req'd 8/8/2003 2:58:18 PM
|
BLD-Framing/Rough-in | 8/7/2003 | 8/8/2003 | 8/8/2003 | A | NR |
Carl Dependahl
|
|
|
alan, expansion joint info...mfr's spec doesn't show 5" gap for 2hr system....resubmit 8/8/2003 11:52:13 AM
|
BLD-Other | 8/6/2003 | 8/7/2003 | 8/7/2003 | A | NR |
Carl Dependahl
|
|
|
expansion joint
|
BLD-Framing/Rough-in | 8/5/2003 | 8/6/2003 | 8/7/2003 | A | FAIL |
Carl Dependahl
|
|
|
alan for cover; Phone #: ###-#### Internet Inspection Request from: Darla Downs...need listing & install info, product for 2hr expansion joint not as plans show...submit. This is main exp joint thru entire bldg... 8/7/2003 11:56:04 AM
|
BLD-Framing/Rough-in | 8/6/2003 | 8/6/2003 | 8/6/2003 | P | NR |
Carl Dependahl
|
|
|
|
BLD-Framing/Rough-in | 8/1/2003 | 8/1/2003 | 8/1/2003 | P | NR |
Dave Hannah
|
|
|
|
BLD-Wall cover | 8/1/2003 | 8/1/2003 | 8/1/2003 | P | NR |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 7/30/2003 | 7/30/2003 | 7/30/2003 | P | PART |
Dave Hannah
|
|
|
allen; Phone #: ###-#### Internet Inspection Request from: Annette Moore 4th floor west side shafts all ok but for one in unit nw corner stair towers ok to put first layer on outsid second layer on inside ok 7/31/2003 10:06:29 AM
|
BLD-Framing/Rough-in | 7/18/2003 | 7/21/2003 | 7/21/2003 | A | PART |
Dave Hannah
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Wall cover | 7/21/2003 | 7/21/2003 | 7/21/2003 | P | PART |
Dave Hannah
|
|
|
4th floor west half ok to cover all but shafts 7/21/2003 2:13:28 PM
|
BLD-Wall cover | 7/15/2003 | 7/16/2003 | 7/16/2003 | A | PART |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore se stair tower ok to cover with second layer of sheet rock 7/16/2003 10:46:06 AM
|
BLD-Wall cover | 7/14/2003 | 7/15/2003 | 7/15/2003 | A | PART |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 4th floor west half c/n with allin and se stair shaft first layer of rock 7/15/2003 10:58:28 AM
|
BLD-Framing/Rough-in | 7/10/2003 | 7/11/2003 | 7/11/2003 | A | PART |
Carl Dependahl
|
|
|
alan ceiling cover ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore; ok to tile fl. 1 corridor pending other insps. 7/11/2003 2:26:18 PM
|
BLD-Final | 7/10/2003 | 7/10/2003 | 7/10/2003 | P | NR |
Carl Dependahl
|
|
|
ALLAN; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Framing/Rough-in | 7/10/2003 | 7/10/2003 | 7/10/2003 | P | PART |
Carl Dependahl
|
|
|
ok to tile clg at east portion 1st fl corridor, to model apts....pending elec, etc.
|
FIRE-Final Inspection | 7/8/2003 | 7/9/2003 | 7/9/2003 | A | PART |
Rick Jackson
|
|
|
first floor office/laundry/etc area okay to occupy 7/10/2003 12:57:41 PM
|
BLD-Wall cover | 7/8/2003 | 7/8/2003 | 7/8/2003 | P | DONE |
Dave Hannah
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
FIRE-Final Inspection | 7/8/2003 | 7/8/2003 | 7/8/2003 | P | FAIL |
Rick Jackson
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need closures on doors to corridor; door to lobby locks and is required exit 7/8/2003 4:26:18 PM
|
BLD-Wall cover | 7/7/2003 | 7/7/2003 | 7/7/2003 | P | CANC |
Dave Hannah
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
FIRE-Final Inspection | 7/7/2003 | 7/7/2003 | 7/7/2003 | P | CANC |
Rick Jackson
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore received call from Allen and he said they won't be ready until 7/8 and he would reschedule 7/7/2003 3:45:13 PM
|
BLD-Wall cover | 7/2/2003 | 7/3/2003 | 7/3/2003 | P | PART |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore third floor west half first floor elev loby se corner 7/7/2003 9:39:47 AM
|
BLD-Wall cover | 7/1/2003 | 7/2/2003 | 7/2/2003 | P | FAIL |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore fire proofing not ready 7/3/2003 7:31:15 AM
|
BLD-Framing/Rough-in | 6/23/2003 | 6/24/2003 | 6/24/2003 | P | PART |
Dave Hannah
|
|
|
###-#### 4th floor east half ok to cover rooms only 6/25/2003 7:49:11 AM
|
BLD-Wall cover | 6/19/2003 | 6/23/2003 | 6/23/2003 | P | PART |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore 4th floor ne 1/4 rooms only no shafts ok to cover 6/23/2003 4:11:32 PM
|
FIRE-Sprinkler Rough-in | 6/23/2003 | 6/23/2003 | 6/23/2003 | P | PART |
Rick Jackson
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore discussed requirements for first floor occupancy; need sprinkler plans submitted and alarms working 6/23/2003 3:58:23 PM
|
BLD-Wall cover | 6/19/2003 | 6/20/2003 | 6/20/2003 | P | PART |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore ground floor area ok to cover walls 6/20/2003 2:12:03 PM
|
BLD-Framing/Rough-in | 6/17/2003 | 6/17/2003 | 6/17/2003 | P | PART |
Dave Hannah
|
|
|
dennis 2nd story west side; Phone #: ###-#### Internet Inspection Request from: Barbara Moore s.w 1/4 2nd floor ok to cover rooms leave shafts open 6/17/2003 5:00:10 PM
|
BLD-Wall cover | 6/12/2003 | 6/13/2003 | 6/13/2003 | A | CANC |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore out of time 6/13/2003 12:30:47 PM
|
BLD-Wall cover | 6/13/2003 | 6/13/2003 | 6/13/2003 | P | PART |
Dave Hannah
|
|
|
fris floor noth west 1/4 romms only and sec floor north west 1/4 rooms 6/16/2003 9:50:05 AM
|
BLD-Wall cover | 6/9/2003 | 6/10/2003 | 6/10/2003 | P | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Wall cover | 6/6/2003 | 6/9/2003 | 6/9/2003 | P | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 1st floor north west 1/4 ok to cover rooms 6/9/2003 10:08:31 PM
|
BLD-Wall cover | 6/3/2003 | 6/4/2003 | 6/4/2003 | P | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD-Framing/Rough-in | 6/2/2003 | 6/3/2003 | 6/3/2003 | A | PART |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to cover shafts on east half of fist and second floors 6/3/2003 1:02:40 PM
|
BLD-Framing/Rough-in | 6/3/2003 | 6/3/2003 | 6/3/2003 | P | DONE |
Dave Hannah
|
|
|
|
BLD-Framing/Rough-in | 5/27/2003 | 5/28/2003 | 5/28/2003 | A | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 5/28/2003 | 5/28/2003 | 5/28/2003 | P | PART |
Dave Hannah
|
|
|
3rd floor ne half rooms ok all but for shafts and elec conduit main runs also se half 3rd floor same as ne section allen has punch list 5/28/2003 2:19:54 PM
|
BLD-Wall cover | 5/22/2003 | 5/23/2003 | 5/23/2003 | A | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore second floor east half 5/23/2003 12:55:09 PM
|
BLD-Framing/Rough-in | 5/16/2003 | 5/19/2003 | 5/19/2003 | P | PART |
Dave Hannah
|
|
|
ALLEN--OK TO COVER ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie second floor area b south half ok to cover al but bath rooms 5/19/2003 5:22:07 PM
|
BLD-Wall cover | 5/15/2003 | 5/16/2003 | 5/16/2003 | P | PART |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore second floor north east 1/4 ok to start covering all but bath room ares 5/16/2003 4:15:21 PM
|
BLD-Other | 5/13/2003 | 5/14/2003 | 5/14/2003 | P | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 5/13/2003 at 12:59:54 PM. Contact: ###-####. rooms 100,01,02/04/06,145,146.48/50 ok to cover 5/14/2003 5:46:28 PM
|
BLD-Framing/Rough-in | 5/9/2003 | 5/12/2003 | 5/12/2003 | A | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD-Framing/Rough-in | 5/6/2003 | 5/7/2003 | 5/7/2003 | P | PART |
Dave Hannah
|
|
|
ALAN; Phone #: ###-#### Internet Inspection Request from: Darla Downs rooms 136,138,140,142,144,145 ok to cover 5/7/2003 3:40:34 PM
|
BLD-Framing/Rough-in | 5/1/2003 | 5/2/2003 | 5/2/2003 | A | DONE |
Dave Hannah
|
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 5/2/2003 | 5/2/2003 | 5/2/2003 | P | DONE |
Dave Hannah
|
|
|
|
BLD-Framing/Rough-in | 4/28/2003 | 4/29/2003 | 4/29/2003 | A | DONE |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 4/28/2003 at 12:07:40 PM. Contact: ###-####.
|
BLD-Conference | 4/22/2003 | 4/23/2003 | 4/23/2003 | A | DONE |
Dave Hannah
|
|
|
###-#### john MOC UP APPT 1HR FIRE WALLS 4/23/2003 12:19:21 PM
|
BLD-Framing/Rough-in | 4/22/2003 | 4/22/2003 | 4/22/2003 | P | CANC |
Carl Dependahl
|
|
|
john level one ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD-Framing/Rough-in | 4/18/2003 | 4/18/2003 | 4/18/2003 | P | DONE |
Dave Hannah
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD-Framing/Rough-in | 4/17/2003 | 4/17/2003 | 4/17/2003 | P | PART |
Dave Hannah
|
|
|
|
FIRE-Sprinkler Rough-in | 4/11/2003 | 4/11/2003 | 4/11/2003 | P | PART |
Rick Jackson
|
|
|
area B on first floor okay to cover
|
BLD-Conference | 3/25/2003 | 3/26/2003 | 3/26/2003 | A | DONE |
Dave Hannah
|
|
|
|
BLD-Framing/Rough-in | 3/25/2003 | 3/25/2003 | 3/25/2003 | P | DONE |
Dave Hannah
|
|
|
|
BLD-Conference | 3/19/2003 | 3/20/2003 | 3/20/2003 | A | DONE |
Dave Hannah
|
|
|
###-#### PER MIKE PHILLIPS
|
BLD-Conference | 3/20/2003 | 3/20/2003 | 3/20/2003 | P | CANC |
Dave Hannah
|
|
|
|
BLD-Conference | 3/17/2003 | 3/18/2003 | 3/18/2003 | P | DONE |
Dave Hannah
|
|
|
at 1:30
|
BLD-Conference | 3/17/2003 | 3/18/2003 | 3/18/2003 | P | PASS |
Carl Dependahl
|
|
|
at 1: 30 w/ Dave H. other trades & PCL supt at site. 3/18/2003 5:30:06 PM
|
BLD-Conference | 3/13/2003 | 3/13/2003 | 3/13/2003 | P | DONE |
Dave Hannah
|
|
|
john ###-####
|
BLD-Conference | 3/11/2003 | 3/12/2003 | 3/12/2003 | P | DONE |
Dave Hannah
|
|
|
###-#### fire stopping 3/12/2003 4:49:32 PM
|
BLD-Conference | 3/12/2003 | 3/12/2003 | 3/12/2003 | P | DONE |
Dave Hannah
|
|
|
|
BLD-Conference | 3/10/2003 | 3/10/2003 | 3/10/2003 | P | DONE |
Dave Hannah
|
|
|
talked wiyh john about fire proofing 3/10/2003 5:34:40 PM
|
BLD-Conference | 3/4/2003 | 3/4/2003 | 3/4/2003 | A | DONE |
Dave Hannah
|
|
|
|
BLD-Conference | 2/25/2003 | 2/26/2003 | 2/26/2003 | A | DONE |
Dave Hannah
|
|
|
###-####
|
BLD-Framing/Rough-in | 2/12/2003 | 2/13/2003 | 2/13/2003 | P | PART |
Dave Hannah
|
|
|
|
BLD-Conference | 2/12/2003 | 2/12/2003 | 2/12/2003 | P | DONE |
Dave Hannah
|
|
|
|
BLD-Conference | 12/13/2002 | 12/13/2002 | 12/13/2002 | P | DONE |
Dave Hannah
|
|
|
on site to walk project and check spec inspection reports
|
FIRE-Conference | 12/5/2002 | 12/9/2002 | 12/9/2002 | P | PART |
Rick Jackson
|
|
|
###-#### met with GC and owners rep about requirements during construction; told them to get plans for the standpipe requirements for additional floors 12/10/2002 10:44:37 AM
|
BLD-Footing | 11/21/2002 | 11/22/2002 | 11/22/2002 | A | PART |
Jim Storey
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie coered with special insp. 11/22/2002 10:23:37 AM
|
BLD-Conference | 11/12/2002 | 11/12/2002 | 11/12/2002 | A | PASS |
Carl Dependahl
|
|
|
Need P.T. eng's direction for possible nicked cables, q.c. for welded assy's...etc. 11/12/02 11:48:35 AM
|
BLD-Conference | 11/8/2002 | 11/11/2002 | 11/11/2002 | P | CANC |
Carl Dependahl
|
|
|
|
BLD-Conference | 11/7/2002 | 11/8/2002 | 11/8/2002 | A | FAIL |
Dave Hannah
|
|
|
c/n posted #1 stop drilling holes in p/t deck #2 need engineer or architect of record to submit a plan for drilling the p/t deck #3 need engineer to check three holes that crew may have hit p/t cables in and make recommendations 11/8/2002 2:52:04 PM
|
BLD-Conference | 11/6/2002 | 11/7/2002 | 11/7/2002 | A | DONE |
Dave Hannah
|
|
|
trying to get a meeting set up 11/7/2002 3:45:18 PM
|
BLD-Conference | 11/5/2002 | 11/6/2002 | 11/6/2002 | P | CANC |
Steven Webb
|
|
|
|
BLD-Conference | 11/5/2002 | 11/6/2002 | 11/6/2002 | P | CANC |
Steven Webb
|
|
|
|
BLD-Conference | 11/5/2002 | 11/6/2002 | 11/6/2002 | P | CANC |
Steven Webb
|
|
|
Randy, ###-#### Requested conference for 11/7/02 a.m not 11/6/02 p.m. 11/6/2002 2:03:35 PM
|
BLD-Conference | 11/4/2002 | 11/5/2002 | 11/5/2002 | A | PASS |
Carl Dependahl
|
|
|
Randy....need spec insp procedure, eng's guidelines for drilling existing P.T. deck, etc. 11/8/02 4:13:06 PM
|
BLD-Conference | 11/1/2002 | 11/4/2002 | 11/4/2002 | A | DONE |
Dave Hannah
|
|
|
|
BLD-Conference | 11/4/2002 | 11/4/2002 | 11/4/2002 | P | PART |
Carl Dependahl
|
|
|
Pre-con w/ Dave & Randy Jordan: need all changes, RFI's, etc onsite; provide special insp "schedule"...req's further review/for inspection operation. 11/4/02 4:23:45 PM
|
BLD-Conference | 10/31/2002 | 11/1/2002 | 11/1/2002 | A | CANC |
Carl Dependahl
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
BLD-Conference | 11/1/2002 | 11/1/2002 | 11/1/2002 | A | CANC |
Dave Hannah
|
|
|
|
BLD-Conference | 11/1/2002 | 11/1/2002 | 11/1/2002 | A | CANC |
Carl Dependahl
|
|
|
###-####
|
BLD-Conference | 11/1/2002 | 11/1/2002 | 11/1/2002 | A | CANC |
Dave Hannah
|
|
|
rescheduled from 11-1
|