BLD-Final | 5/11/2004 | 5/11/2004 | 5/11/2004 | A | PASS |
Dave Hannah
|
|
|
|
Permanent Occupancy | | 5/11/2004 | 5/11/2004 | | DONE |
|
|
|
|
BLD-Final | 2/24/2004 | 2/25/2004 | 2/25/2004 | A | PART |
Dave Hannah
|
|
|
RANDY; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok for temp occ 2/25/2004 12:37:33 PM
|
FIRE-Final Inspection | 2/24/2004 | 2/25/2004 | 2/25/2004 | A | PASS |
Rick Jackson
|
|
|
RANDY; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
BLD-Final | 2/23/2004 | 2/24/2004 | 2/24/2004 | A | CANC |
Dave Hannah
|
|
|
Dennis; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD-Final | 2/20/2004 | 2/23/2004 | 2/23/2004 | A | FAIL |
Dave Hannah
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
Code Occupancy Approval | | | 2/23/2004 | | DONE |
|
|
|
|
BLD-Final | 2/19/2004 | 2/20/2004 | 2/20/2004 | A | FAIL |
Troy James
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Annette Moore Checked doors for closure, seal and hardware. 2/20/2004 11:13:53 AM
|
BLD-Final | 2/17/2004 | 2/18/2004 | 2/18/2004 | A | NR |
Dave Hannah
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIRE-Final Inspection | 2/17/2004 | 2/18/2004 | 2/18/2004 | A | FAIL |
Rick Jackson
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:43:29 PM 2/18/2004 3:44:23 PM
|
BLD-Final | 2/9/2004 | 2/9/2004 | 2/9/2004 | P | NR |
Dave Hannah
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Framing/Rough-in | 2/4/2004 | 2/4/2004 | 2/4/2004 | P | PART |
Dave Hannah
|
|
|
dennis ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD-Aging Inspection | 8/20/2003 | 8/20/2003 | 8/20/2003 | | PASS |
Carl Dependahl
|
|
|
PA2 wip 8/20/2003 9:33:29 AM
|
BLD-Conference | 6/20/2003 | 6/20/2003 | 6/20/2003 | P | PASS |
Carl Dependahl
|
|
|
need modification detail for shaft 6/20/2003 5:15:40 PM
|
BLD-Framing/Rough-in | 6/19/2003 | 6/20/2003 | 6/20/2003 | A | PART |
Carl Dependahl
|
|
|
4hr wall, wip, ok. 6/20/2003 2:32:16 PM
|
BLD-Framing/Rough-in | 5/5/2003 | 5/9/2003 | 5/9/2003 | A | CANC |
Carl Dependahl
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 5/5/2003 | 5/8/2003 | 5/9/2003 | A | PART |
Carl Dependahl
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore; prelim only, wip. 5/9/2003 11:55:50 AM
|
BLD-Framing/Rough-in | 5/5/2003 | 5/7/2003 | 5/7/2003 | A | PART |
Carl Dependahl
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore...rec'd eng's ok for ISI's eng'd design of 4hr wall framing...wip ok, extend to/thru corridors as req'd. 5/7/2003 5:00:40 PM
|
BLD-Framing/Rough-in | 5/5/2003 | 5/6/2003 | 5/6/2003 | A | PART |
Carl Dependahl
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore firewall wip 5/6/2003 3:50:50 PM
|
BLD-Conference | 4/18/2003 | 4/21/2003 | 4/21/2003 | P | PASS |
Carl Dependahl
|
|
|
Need stamped eng'g & arch's ok for altered framing 4/21/2003 5:00:49 PM
|
BLD-Conference | 4/14/2003 | 4/14/2003 | 4/14/2003 | P | PASS |
Carl Dependahl
|
|
|
re 4hr walls...build per eng'g 4/14/2003 5:45:50 PM
|
BLD-Conference | 3/25/2003 | 3/25/2003 | 3/25/2003 | P | PASS |
Carl Dependahl
|
|
|
met arch onsite...keep c/n re struct obsevation; Margie will obtain eng's schedule of insps....will advise 3/25/2003 5:44:00 PM
|