Permit Information
Permit NumberBLD02-00691
StatusFinaled
Name KIMBALL PROPERTES LTD PTNRSHIP
Site Address 456 N KIMBALL PL
Project NameKIMBALL PLAZA
Customer Number 
ePlanReviewNo
Description
(CAPITAL ONE)(KIMBALL PLAZA) Interior remodel in an existing 65,212 sq.ft. one story office building by creating some new enclosed offices, a new work room, a new mail room, and a new game room per approved plans on file. Work to include some minor interior demolition work, a new cased opening in existing interior concrete shear wall, some new interior walls, some new interior doors, interior finish, some suspended ceiling work, new counters, fire sprinkler work, fire alarm work, mechanical work, plumbing work, and electrical work. A NEW CERTIFICATE OF OCCUPANCY IS TO BE ISSUED WHEN COMPLETED AND APPROVED. NOTE: This building is fully fire sprinklered for area increase. (PC#0189-02) JCB
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/20/200212/23/200212/23/2002APASS
DetailsRuss Owen
Don, ###-####Ok for a permanent oc. 12/23/2002 9:25:12 AM
Permanent Occupancy 12/23/200212/23/2002 DONE
Details
FIRE-Alarm Testing12/19/200212/20/200212/20/2002PPASS
DetailsTroy Cobbley
fire life safety finaled 12/20/2002 2:23:21 PM
BLD-Final11/12/200211/12/200211/12/2002PPART
DetailsRuss Owen
Don Bryan, ###-####. needs fire/life safety before a perm oc. 11/12/2002 3:35:56 PM
FIRE-Final Inspection10/22/200210/23/200210/23/2002PFAIL
DetailsTroy Cobbley
provide a/v's in the storage turned conference rooms, relocate new duct detectors to the supply side of the duct and get the supervisory signals to the central station figured out 10/24/2002 11:07:20 AM
FIRE-Sprinkler Rough-in8/13/20028/14/20028/14/2002AFAIL
DetailsTroy Cobbley
This inspection was done under FIR02-00215 but I left a correction notice for the addition of duct detectors, per review notes 3 and 18, per Don the general contractors request 8/14/2002 8:51:42 AM
FIRE-Conference8/9/20028/13/20028/13/2002ADONE
DetailsTroy Cobbley
I went over the fire life safety notes with the contractor 8/13/2002 11:19:28 AM
BLD-Framing/Rough-in5/31/20026/3/20026/3/2002PPART
DetailsRuss Owen
Don, ###-####. needs electrical and braces at top walls. 6/3/2002 4:56:46 PM