Permit Information
Permit NumberBLD02-01481
StatusFinaled
Name KWAL HOWELL PAINT
Site Address 8515 W WESTPARK DR
Project Name 
Customer Number 
ePlanReviewNo
Description
(KWAL HOWELL PAINT) To conduct minor interior remodel and establish occupancy for an existing 6,550 sq.ft. retail paint sales and storage per approved plans on file. Work to include relocation of east wall of restroom in retail sales area to make more accessible by providing new accessible 3'-0" x 6'-8" door assembly and provide five foot diameter maneuvering clearance in front of existing sink & water closet. NOTE: This building is fully fire sprinklered for area increase. The original shell building and this tenant space were constructed in Ada County and annexed into Boise City in 1987. A 'Certificate of Occupancy' for this tenant is required as a condition of this permit. Quantities, storage & use of Flammable & Combustible materials are governed by the UFC for Wholesale & Retail Sales Uses. PC#02-383/drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/2/20034/3/20034/3/2003APASS
DetailsRuss Owen
###-####. Ok for a perm oc. 4/3/2003 9:48:48 AM
Permanent Occupancy 4/3/20034/3/2003 DONE
Details
BLD-Final3/27/20033/28/20033/28/2003PPART
DetailsRuss Owen
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore This is ok for a temporary oc, new c/n for 2 items. All other signatures have been approved and signed off. 3/28/2003 2:56:07 PM
FIRE-Final Inspection3/27/20033/27/20033/27/2003PPASS
DetailsRick Jackson
FIRE-Final Inspection1/27/20031/28/20031/28/2003PFAIL
DetailsTroy Cobbley
MARK; Phone #: ###-#### Fire sprinkler monitoring system still needs to be approved and installed and the bottom support for the riser needs to be installed. It is currently a block of wood. 1/28/2003 1:08:27 PM
BLD-Final12/6/200212/9/200212/9/2002AFAIL
DetailsRuss Owen
###-#### mark.> Left c/n for racks and rest room, but can not ok temp oc untill fire/life safety has done so. 12/9/2002 12:39:03 PM
FIRE-Final Inspection12/6/200212/9/200212/9/2002AFAIL
DetailsTroy Cobbley
The fire alarm system does not meet current code requirements. Provide approved fire alarm submittals prior to installation of code compliant system. Provide code compliant support for the fire sprinkler riser. The sprinkler pendant on the east side of the remodeled restroom is too close to the wall and must be relocated. The sprinkler pendant in front of the north entrance in the show room is too close to the wall and is painted. It must be replaced and relocated. The upright sprinkler heads on the west side of the wall that separates the ware house from the show room exceed the maximum allowable distance from the wall. Additional sprinkler heads will be required. The upright sprinkler head under the overhead door in the warehouse is overspaced. An additional upright or sidewall head will be required. Remove the manual flush bolts from both sets of the entry/exit doors in the showroom. Only one set of these doors is allowed to have key locking hardware. The other must have approved hardware (crash bar, lever, pad) 12/9/2002 3:38:23 PM
BLD-Final12/3/200212/6/200212/6/2002PNR
DetailsRuss Owen
mark; Phone #: ###-#### Internet Inspection Request from: Darla DownsThis needs fire/life safety /plumbing/electrical,as I have told this in person to contractor 12/6/2002 12:29:32 PM
BLD-Final12/3/200212/6/200212/6/2002PNR
DetailsRuss Owen
mark; Phone #: ###-#### Internet Inspection Request from: Darla DownsThis needs fire/life safety /plumbing/electrical,as I have told this in person to contractor 12/6/2002 12:29:32 PM
BLD-Final12/5/200212/5/200212/5/2002PNR
DetailsRuss Owen
went over req to obtain final. 12/5/2002 2:52:13 PM