BLD-Final | 4/2/2003 | 4/3/2003 | 4/3/2003 | A | PASS |
Russ Owen
|
|
|
###-####. Ok for a perm oc. 4/3/2003 9:48:48 AM
|
Permanent Occupancy | | 4/3/2003 | 4/3/2003 | | DONE |
|
|
|
|
BLD-Final | 3/27/2003 | 3/28/2003 | 3/28/2003 | P | PART |
Russ Owen
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore This is ok for a temporary oc, new c/n for 2 items. All other signatures have been approved and signed off. 3/28/2003 2:56:07 PM
|
FIRE-Final Inspection | 3/27/2003 | 3/27/2003 | 3/27/2003 | P | PASS |
Rick Jackson
|
|
|
|
FIRE-Final Inspection | 1/27/2003 | 1/28/2003 | 1/28/2003 | P | FAIL |
Troy Cobbley
|
|
|
MARK; Phone #: ###-#### Fire sprinkler monitoring system still needs to be approved and installed and the bottom support for the riser needs to be installed. It is currently a block of wood. 1/28/2003 1:08:27 PM
|
BLD-Final | 12/6/2002 | 12/9/2002 | 12/9/2002 | A | FAIL |
Russ Owen
|
|
|
###-#### mark.> Left c/n for racks and rest room, but can not ok temp oc untill fire/life safety has done so. 12/9/2002 12:39:03 PM
|
FIRE-Final Inspection | 12/6/2002 | 12/9/2002 | 12/9/2002 | A | FAIL |
Troy Cobbley
|
|
|
The fire alarm system does not meet current code requirements. Provide approved fire alarm submittals prior to installation of code compliant system. Provide code compliant support for the fire sprinkler riser. The sprinkler pendant on the east side of the remodeled restroom is too close to the wall and must be relocated. The sprinkler pendant in front of the north entrance in the show room is too close to the wall and is painted. It must be replaced and relocated. The upright sprinkler heads on the west side of the wall that separates the ware house from the show room exceed the maximum allowable distance from the wall. Additional sprinkler heads will be required. The upright sprinkler head under the overhead door in the warehouse is overspaced. An additional upright or sidewall head will be required. Remove the manual flush bolts from both sets of the entry/exit doors in the showroom. Only one set of these doors is allowed to have key locking hardware. The other must have approved hardware (crash bar, lever, pad) 12/9/2002 3:38:23 PM
|
BLD-Final | 12/3/2002 | 12/6/2002 | 12/6/2002 | P | NR |
Russ Owen
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Darla DownsThis needs fire/life safety /plumbing/electrical,as I have told this in person to contractor 12/6/2002 12:29:32 PM
|
BLD-Final | 12/3/2002 | 12/6/2002 | 12/6/2002 | P | NR |
Russ Owen
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Darla DownsThis needs fire/life safety /plumbing/electrical,as I have told this in person to contractor 12/6/2002 12:29:32 PM
|
BLD-Final | 12/5/2002 | 12/5/2002 | 12/5/2002 | P | NR |
Russ Owen
|
|
|
went over req to obtain final. 12/5/2002 2:52:13 PM
|