BLD-Final | 8/19/2003 | 8/20/2003 | 8/20/2003 | A | PASS |
Russ Owen
|
|
|
austin; Phone #: ###-#### Internet Inspection Request from: Darla Downs Ok perm oc. 8/20/2003 11:34:31 AM
|
Permanent Occupancy | | 8/20/2003 | 8/20/2003 | | DONE |
|
|
|
|
BLD-Final | 8/18/2003 | 8/19/2003 | 8/19/2003 | A | FAIL |
Russ Owen
|
|
|
AUSTIN; Phone #: ###-#### Internet Inspection Request from: Darla Downsneed to attach fasteners to studs at shelves went over this with austin. 8/19/2003 10:52:39 AM
|
BLD-Final | 8/1/2003 | 8/1/2003 | 8/1/2003 | P | NR |
Russ Owen
|
|
|
jefferson; Phone #: ###-#### Internet Inspection Request from: Barbara MooreNew plans wanted some screws at 6 foot metal shelves to walls went over plan with person on site. 8/1/2003 4:09:33 PM
|
BLD-Final | 7/30/2003 | 7/31/2003 | 7/31/2003 | A | FAIL |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 7/30/2003 at 3:01:02 PM. . needs some bolts in floor plates. 7/31/2003 1:53:56 PM
|
BLD-Final | 7/28/2003 | 7/29/2003 | 7/29/2003 | P | PART |
Russ Owen
|
|
|
###-#### austin, C/n given to tennant for bolting racks to floor, lower restroom mirror, remove t-bar ceiling or repair in break room area. Ok for a temp oc.7/29/2003 5:35:46 PM 7/29/2003 5:35:58 PM
|
FIRE-Final Inspection | 7/28/2003 | 7/29/2003 | 7/29/2003 | A | PASS |
Troy Cobbley
|
|
|
fire life safety finaled 7/29/2003 11:51:53 AM
|
BLD-Framing/Rough-in | 6/16/2003 | 6/17/2003 | 6/17/2003 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 6/16/2003 at 1:05:53 PM. Contact: ###-####.
|
FIRE-Final Inspection | 6/16/2003 | 6/17/2003 | 6/17/2003 | A | FAIL |
Troy Cobbley
|
|
|
austin; Phone #: ###-#### The inspection was for the fire sprinkler portion of the permit. Pendant sprinklers are overspace in numerous locations in the merchandizing areas.A sprinkler pendant needs to be provided in the closet or the ceiling is to be removed. Tire storage in the wharehouse to be less than 5'. Wood storage to be less than 10'. I could not verify a minimum .2 gpm over 130 sq. ft. density sprinkler design as the sticker on the riser is missing. I went over some life safety issues with the tenant 6/17/2003 2:02:30 PM
|
BLD-Framing/Rough-in | 5/15/2003 | 5/15/2003 | 5/15/2003 | P | PASS |
Russ Owen
|
|
|
austin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore.ok to cover bathroom. 5/15/2003 4:44:38 PM
|
BLD-Framing/Rough-in | 4/21/2003 | 4/21/2003 | 4/21/2003 | P | PART |
Russ Owen
|
|
|
austin; Phone #: ###-#### Internet Inspection Request from: Annette Moore. needs to complete misc in left rest room other ok. 4/21/2003 3:36:37 PM
|
BLD-Wall cover | 4/17/2003 | 4/18/2003 | 4/18/2003 | P | FAIL |
Russ Owen
|
|
|
austin; Phone #: ###-#### Internet Inspection Request from: Annette Moore. needs electrical insp and shore up 1 area over rest room went over this with Austin told him to recall when done. 4/18/2003 3:58:41 PM
|
BLD-Conference | 3/19/2003 | 3/20/2003 | 3/20/2003 | P | PART |
Russ Owen
|
|
|
JEANNE; Phone #: ###-#### Internet Inspection Request from: Annette Moore. went over front ddoors 3/20/2003 4:43:26 PM
|