Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberBLD02-01845
StatusFinaled
Name BOISE CITY
Site Address 10895 W EMERALD ST
Project NameFIRE STATION #11
Customer Number 
ePlanReviewNo
Description
Boise Fire Station #11 * To remodel existing fire station and add a 652 sq.ft. one story Type VN addition to the south side of the existing building per approved plans and attachments. DRH02-00011
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final9/26/20039/29/20039/29/2003APASS
DetailsJim Sly
Cathy has the card - everyone signed off - need final from you - please let me know if approved! Thanks ~ : ) ok for perm. occ. :) 9/29/2003 11:33:21 AM
Permanent Occupancy 9/29/20039/29/2003 DONE
Details
BLD-Final7/24/20037/25/20037/25/2003AFAIL
DetailsJim Sly
dave; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Re-call when Plumbing is Finaled. (talked to Dave). 7/25/2003 11:15:52 AM
BLD-Final4/30/20035/1/20035/1/2003APART
DetailsRuss Owen
I will approve a temp oc, I have inspected into the attic area, and have a correction to repair a draft stop and notch top of exterior wall blocking and to provide the 2 roof vents as shown also nee to see the truss calcs. On site with contractor. 5/2/2003 7:39:47 AM 5/2/2003 7:40:02 AM
BLD-Conference4/29/20034/29/20034/29/2003APART
DetailsRuss Owen
I talked with the Architect, he has been on site for visits during construction. He will not write a letter for the contractor in reguards to the framing, But has indicated he feels that there are no structural issues. As all exterior walls are bearing . I will meet again with the contractor on site to resolve. 5/2/2003 7:37:26 AM
BLD-Final4/28/20034/28/20034/28/2003PCANC
DetailsRuss Owen
dave ; Phone #: ###-#### Internet Inspection Request from: Annette Moore. The contrator has stated that the Architect of record will not confirm farming was as per plans. I sugested they talk with George Slane. 4/28/2003 2:40:00 PM 4/28/2003 2:40:53 PM
FIRE-Final Inspection4/24/20034/25/20034/25/2003APASS
DetailsTroy Cobbley
dave; Phone #: ###-#### Life safety finaled 4/25/2003 2:41:32 PM
Code Occupancy Approval4/25/20034/24/20034/24/2003PPASS
DetailsScott M.Brown
FINAL SIGNED OFF. 4/25/2003 1:23:52 PM
BLD-Final4/23/20034/23/20034/23/2003AFAIL
DetailsTroy Cobbley
There is now access to the link for the fire door but while I was performing the inspection, Hobson Mechanical was installing a duct smoke detector. The plans show the unit at only 1850 cfm but per this contractor the mechanical engineer stated it was actually over 2000 cfm and to install a duct smoke detector. I won't final until it is installed and tested.
FIRE-Final Inspection4/21/20034/21/20034/21/2003PFAIL
DetailsTroy Cobbley
dave; Phone #: ###-#### Provide better access to the fire damper for verifiction of link or provide letter from the mechanical engineer stating proper function of the fire damper 4/21/2003 1:50:00 PM
BLD-Final4/18/20034/18/20034/18/2003PFAIL
DetailsRuss Owen
This has only had a shear nailing inspection at that time gas piping,elctrical and plumbing had not been approved for cover see records. once these items had approval they coverd all. Job is now finished contractors responce was they thought since I had done a shear wall inspection that framing was approved. I asked them why they thought I would approve the inside with out any other trades signed off. I said that I was unaware of any place in this area that would allow that. So at this point only solution is to have the architect of record write a letter stating that framing was done in accordance with plans. also still needs fire and zoning. at this final now there are no approved plans on site. Carl D on site with me at this inspection. 4/18/2003 5:19:26 PM
BLD-Final4/17/20034/18/20034/18/2003PFAIL
DetailsCarl Dependahl
w/ 407... 4/18/2003 2:41:01 PM
FIRE-Final Inspection4/18/20034/18/20034/18/2003PFAIL
DetailsTroy Cobbley
###-#### dave No approved plans on site. No inspection done. 4/18/2003 2:00:28 PM
BLD-Framing/Rough-in2/12/20032/12/20032/12/2003PPART
DetailsRuss Owen
dave; Phone #: ###-#### Internet Inspection Request from: Marsha SmylieOK FOR EXTERIOR WALL COVER. 2/12/2003 3:35:24 PM
BLD-Framing/Rough-in2/10/20032/10/20032/10/2003PFAIL
DetailsRuss Owen
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung .c/n posted. 2/10/2003 4:05:35 PM
BLD-Foundation12/30/200212/30/200212/30/2002PPASS
DetailsRuss Owen
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung. ok but hold downs not yet in place. 12/30/2002 4:16:59 PM
BLD-Foundation12/27/200212/27/200212/27/2002PFAIL
DetailsRuss Owen
###-#### dave C/n posted, exceeds 12in spaceing at horiz bars, column footing reqs addnl stirups, dowl not in place at existing walls, hold downs shown on plans none on site, also location is not clearley indicated on plans. Contractor on site. 12/27/2002 3:31:20 PM
BLD-Footing12/16/200212/17/200212/17/2002APART
DetailsRuss Owen
90% complete needs post support completed. 12/17/2002 11:11:54 AM
BLD-Footing12/17/200212/17/200212/17/2002PPASS
DetailsRuss Owen
BLD-Footing12/16/200212/16/200212/16/2002PNR
DetailsRuss Owen
###-#### dave
BLD-Conference12/9/200212/9/200212/9/2002PPART
DetailsRuss Owen
###-####