BLD-Final | 9/30/2003 | 9/30/2003 | 9/30/2003 | P | PASS |
Jim Sly
|
|
|
fn - ###-####- doug 9/30/2003 2:46:10 PM OK for Perm occ. 9/30/2003 2:46:53 PM
|
Permanent Occupancy | | 9/30/2003 | 9/30/2003 | | DONE |
|
|
|
|
BLD-Final | 9/26/2003 | 9/29/2003 | 9/29/2003 | A | NR |
Russ Owen
|
|
|
Cathy has occ. req. card - please call if approved! Thanks ~ : ) There are no approved plans. talked with tennant will getthem and recall 9/29/2003 7:11:56 PM
|
FIRE-Final Inspection | 8/15/2003 | 8/15/2003 | 8/15/2003 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm system has been finaled. Permanent occupancy is ok for Fitness 19
|
FIRE-Conference | 3/11/2003 | 3/12/2003 | 3/12/2003 | A | DONE |
Troy Cobbley
|
|
|
pendant in front of space is still overspaced and the fire alarm plans are still an issue 3/12/2003 9:17:39 AM
|
FIRE-Conference | 3/12/2003 | 3/12/2003 | 3/12/2003 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with dave millers permission until the fire alarm plans have been approved and the changes made and inspected 3/12/2003 3:49:32 PM
|
BLD-Final | 3/7/2003 | 3/7/2003 | 3/7/2003 | P | NR |
Tom Arcoraci
|
|
|
PER JIM SLY OKAY FOR FINAL ###-#### needs fire ok 3/7/2003 4:08:04 PM
|
BLD-Framing/Rough-in | 3/6/2003 | 3/7/2003 | 3/7/2003 | A | PASS |
Jim Sly
|
|
|
###-#### ceiling Ceiling OK. 3/7/2003 10:33:54 AM
|
FIRE-Final Inspection | 3/7/2003 | 3/7/2003 | 3/7/2003 | P | FAIL |
Troy Cobbley
|
|
|
provide EQ bracing and hanger per code in the new tenant space, provide annual inspection for the fire sprinkler system, provide one additional sprinkler pendant near the front exit, provide approved fire alarm plans showing the two new duct smoke detectors supervised by the existing fire alarm system 3/7/2003 4:05:30 PM
|
BLD-Framing/Rough-in | 2/10/2003 | 2/10/2003 | 2/10/2003 | P | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 2/10/2003 at 7:06:42 AM. Contact: ###-####.
|
BLD-Conference | 2/7/2003 | 2/7/2003 | 2/7/2003 | A | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 2/7/2003 at 7:06:35 AM. Contact: ###-####. Talked about change on plans. 2/7/2003 11:07:33 AM
|