FIRE-Final Inspection | 3/10/2004 | 3/11/2004 | 3/11/2004 | A | PASS |
Rick Jackson
|
|
|
Please call 30 mins prior to inspection///robbie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore fire/life safety okay 3/11/2004 8:33:59 AM
|
Permanent Occupancy | | 3/11/2004 | 3/11/2004 | | DONE |
|
|
|
|
FIRE-Final Inspection | 3/9/2004 | 3/10/2004 | 3/10/2004 | A | FAIL |
Troy Cobbley
|
|
|
Duct smoke detectors have been installed but they do not shut down the hvac units when activated 3/10/2004 9:57:06 AM
|
BLD-Final | 2/12/2004 | 2/12/2004 | 2/12/2004 | A | PART |
Tom Arcoraci
|
|
|
ok pending fire final
|
BLD-Framing/Rough-in | 2/10/2004 | 2/12/2004 | 2/12/2004 | A | CANC |
Tom Arcoraci
|
|
|
Robbie; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
FIRE-Final Inspection | 2/10/2004 | 2/12/2004 | 2/12/2004 | A | FAIL |
Troy Cobbley
|
|
|
provide duct smoke detectors for unit shut down on both units 2/12/2004 10:23:23 AM
|
BLD-Final | 7/25/2003 | 7/25/2003 | 7/25/2003 | P | NR |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 7/25/2003 at 11:14:25 AM. Contact: ###-####.Went to job card does not have all required signatures. 7/25/2003 3:27:21 PM
|
BLD-Final | 7/25/2003 | 7/25/2003 | 7/25/2003 | P | PART |
Tom Arcoraci
|
|
|
Ok for temp. occ.
|
BLD-Final | 7/16/2003 | 7/18/2003 | 7/18/2003 | A | NR |
Tom Arcoraci
|
|
|
###-#### jed
|
FIRE-Final Inspection | 7/16/2003 | 7/17/2003 | 7/17/2003 | P | FAIL |
Troy Cobbley
|
|
|
###-#### jed Provide the second fire hydrant as per plan sheet C1.0. Provide automatic shutdown for the hvac units. Provide "No Parking-Fire Dept. Turn Around" sign on fence between builidings. Provide approved door hardware on doors for access to the common restrooms and conference room 7/17/2003 4:18:41 PM
|
FIRE-Final Inspection | 7/15/2003 | 7/16/2003 | 7/16/2003 | A | FAIL |
Rick Jackson
|
|
|
jed - ###-#### shell permit not signed off; will need address and suite numbers 7/16/2003 8:35:59 AM
|
BLD-Framing/Rough-in | 3/27/2003 | 3/27/2003 | 3/27/2003 | P | FAIL |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 3/27/2003 at 9:39:21 AM. Contact: ###-####. cn posted ok to insulate walls only 3/27/2003 3:43:08 PM
|