Permit Information
Permit NumberBLD02-03091
StatusFinaled
Name KEVIN THOMAS (CHLN INC)
Site Address 2288 N GARDEN ST
Project Name 
Customer Number 
ePlanReviewNo
Description
(JOE'S CRAB SHACK) To remodel a 6,943 sq.ft. restaurant for new owner per approved plans on file and DRH02-00249. Work to include, complete interior remodel, construction of a new canopy over entrance, all new kitchen equipment, new type-1 hood and grease duct shaft, remove stairs from second floor loft and create mechnical loft only, add permanent access ladder, modify exterior exit door, infill windows exterior wall, all work to be per the approved plans and engineering. NOTE: This building is fully fire sprinklered for one-hour fire-resistive construction. (pc#827-02) rmh
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 10/18/200510/18/2005 DONE
Details
FIRE-Final Inspection9/28/20059/28/20059/28/2005APASS
DetailsForrest France
Pump flow test performed with Jim Danes of DeBest fire, verified satisfactory residual pressure at 100% rated flow.
BLD-Aging Inspection8/12/20058/12/20058/12/2005 CANC
DetailsTom Arcoraci
BLD-Aging Inspection6/8/20056/8/20056/13/2005 DONE
DetailsForrest France
Spoke today with Brian Burgar of Garden City Public Works, he explained an additional valve in the area has been opened and should increase the available flow. I called Jim Danes with De Best fire, he is to schedule an inspection to verify 1500gpm fire flow.
BLD-Aging Inspection3/30/20053/30/20054/6/2005 DONE
DetailsForrest France
Per sam rogers the pump does not need to hit the 150 percent to meet code. All we need is verification of water flow from the hydrant for the on site water demand
BLD-Aging Inspection10/7/200410/7/200410/7/2004 PASS
DetailsRick Jackson
PDS fire code office is working with Garden City water department to get a flow test of the area to determine water available as it is in question due to the fire pump not being able to pump 750 gpm; this may require an additional pump flow test 10/7/2004 9:26:29 AM
BLD-Aging Inspection7/26/20047/26/20047/26/2004 PART
DetailsRick Jackson
Awaiting info on water supply 7/26/2004 10:03:06 AM
BLD-Aging Inspection5/17/20045/17/20045/17/2004 NR
DetailsTom Arcoraci
BLD-Conference5/17/20045/17/20045/17/2004PPASS
DetailsRick Jackson
Fire PDS is working with owner and fire sprinkler contractor to get this resolved 5/17/2004 12:27:00 PM
BLD-Aging Inspection3/17/20043/17/20043/17/2004 NR
DetailsTom Arcoraci
per dave miller 3/17/2004 7:58:38 AM
BLD-Aging Inspection1/16/20041/16/20041/16/2004 PASS
DetailsTom Arcoraci
BLD-Aging Inspection10/24/200310/24/200310/24/2003 NR
DetailsTom Arcoraci
needs fire final 10/24/2003 11:18:32 AM
FIRE-Final Inspection10/24/200310/24/200310/24/2003PPART
DetailsRick Jackson
this is on a temp ?????????? tom awaiting Garden City to retrofit the water pump for thaqt area; letter on file to Dave Miller addressing this situation and theya re to remain on temp until the water situation is fixed 10/24/2003 1:08:09 PM
FIRE-Final Inspection8/20/20038/20/20038/20/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 8/20/2003 at 7:15:30 AM. Contact: ###-####. need fire pump data and jockey/fire pump controller test lines to drain; fire pump couldn't pump to 150 percent capacity as the suction was at zero 8/20/2003 4:13:27 PM
BLD-Final7/25/20037/25/20037/25/2003APART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 7/25/2003 at 6:12:53 AM. Contact: ###-####. ok for temp and ok for perm when others sign perm 7/25/2003 10:42:10 AM 7/25/2003 10:42:34 AM
FIRE-Final Inspection7/25/20037/25/20037/25/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/25/2003 at 6:11:24 AM. Contact: ###-####. temp occupancy approved per Dave Miller and the requirement for a fire watch until the fire pump is installed and tested with fire alarm monitoring; will need the NFPA 72 record of completion 7/25/2003 3:15:24 PM
BLD-Final7/24/20037/24/20037/24/2003PFAIL
DetailsTroy Cobbley
JOHN ###-####--PENDING BLD FN See correction notice 7/24/2003 2:47:29 PM
BLD-Final7/24/20037/24/20037/24/2003PNR
DetailsTom Arcoraci
JOHN ###-#### PENDING FIR FN needs fire 7/24/2003 3:11:12 PM
BLD-Conference7/21/20037/21/20037/21/2003APASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 7/21/2003 at 7:30:20 AM. Contact: ###-####.
FIRE-Conference7/21/20037/21/20037/21/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/21/2003 at 7:29:51 AM. Contact: ###-####. met with John and Troy about final requirements; heads moved up to ceiling in main lobby; frozen head in freezer and obstructed; gaurds on heads; exit sign lowered and need additional one in kitchen; repair and relocate exit sign by bar; storage in mezzanine not allowed; occupant load sign; hanging decorations may not be in comliance with UFC for decorations 7/21/2003 4:41:16 PM
BLD-Other7/2/20037/2/20037/2/2003APASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 7/2/2003 at 6:13:41 AM. Contact: ###-####. part grid ok 7/2/2003 10:33:57 AM
FIRE-Conference7/2/20037/2/20037/2/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/2/2003 at 6:12:18 AM. Contact: ###-####. Debest fire will have to complete submittals for fire sprinklers and have permit isssued and alarm submittals aren't complete - don't show fire pump and controller and have the permit issued 7/2/2003 4:03:25 PM
BLD-Other6/3/20036/3/20036/3/2003APART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 6/3/2003 at 7:07:35 AM. Contact: ###-####. wip ok needs header ?? at mez floor west side 6/3/2003 9:20:41 AM
BLD-Wall cover5/27/20035/27/20035/27/2003APART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 5/27/2003 at 6:40:27 AM. Contact: ###-####. ok to cover walls need eng ok for g-lam attachment 5/27/2003 11:09:14 AM
BLD-Wall cover5/23/20035/23/20035/23/2003PFAIL
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/23/2003 at 7:18:18 AM. Contact: ###-####. Need Electr R/I approval. 5/23/2003 3:06:58 PM
BLD-Wall cover5/23/20035/23/20035/23/2003PFAIL
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/23/2003 at 7:18:18 AM. Contact: ###-####. Talked to Electr inspector.....PART....only select walls to cover.......Told contr to obtain complete Electr R/I approval prior to calling for frame. 5/23/2003 2:07:04 PM
BLD-Footing4/28/20034/29/20034/29/2003APASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 4/28/2003 at 4:40:30 PM. Contact: ###-####.