Permanent Occupancy | | 10/18/2005 | 10/18/2005 | | DONE |
|
|
|
|
FIRE-Final Inspection | 9/28/2005 | 9/28/2005 | 9/28/2005 | A | PASS |
Forrest France
|
|
|
Pump flow test performed with Jim Danes of DeBest fire, verified satisfactory residual pressure at 100% rated flow.
|
BLD-Aging Inspection | 8/12/2005 | 8/12/2005 | 8/12/2005 | | CANC |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 6/8/2005 | 6/8/2005 | 6/13/2005 | | DONE |
Forrest France
|
|
|
Spoke today with Brian Burgar of Garden City Public Works, he explained an additional valve in the area has been opened and should increase the available flow. I called Jim Danes with De Best fire, he is to schedule an inspection to verify 1500gpm fire flow.
|
BLD-Aging Inspection | 3/30/2005 | 3/30/2005 | 4/6/2005 | | DONE |
Forrest France
|
|
|
Per sam rogers the pump does not need to hit the 150 percent to meet code. All we need is verification of water flow from the hydrant for the on site water demand
|
BLD-Aging Inspection | 10/7/2004 | 10/7/2004 | 10/7/2004 | | PASS |
Rick Jackson
|
|
|
PDS fire code office is working with Garden City water department to get a flow test of the area to determine water available as it is in question due to the fire pump not being able to pump 750 gpm; this may require an additional pump flow test 10/7/2004 9:26:29 AM
|
BLD-Aging Inspection | 7/26/2004 | 7/26/2004 | 7/26/2004 | | PART |
Rick Jackson
|
|
|
Awaiting info on water supply 7/26/2004 10:03:06 AM
|
BLD-Aging Inspection | 5/17/2004 | 5/17/2004 | 5/17/2004 | | NR |
Tom Arcoraci
|
|
|
|
BLD-Conference | 5/17/2004 | 5/17/2004 | 5/17/2004 | P | PASS |
Rick Jackson
|
|
|
Fire PDS is working with owner and fire sprinkler contractor to get this resolved 5/17/2004 12:27:00 PM
|
BLD-Aging Inspection | 3/17/2004 | 3/17/2004 | 3/17/2004 | | NR |
Tom Arcoraci
|
|
|
per dave miller 3/17/2004 7:58:38 AM
|
BLD-Aging Inspection | 1/16/2004 | 1/16/2004 | 1/16/2004 | | PASS |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 10/24/2003 | 10/24/2003 | 10/24/2003 | | NR |
Tom Arcoraci
|
|
|
needs fire final 10/24/2003 11:18:32 AM
|
FIRE-Final Inspection | 10/24/2003 | 10/24/2003 | 10/24/2003 | P | PART |
Rick Jackson
|
|
|
this is on a temp ?????????? tom awaiting Garden City to retrofit the water pump for thaqt area; letter on file to Dave Miller addressing this situation and theya re to remain on temp until the water situation is fixed 10/24/2003 1:08:09 PM
|
FIRE-Final Inspection | 8/20/2003 | 8/20/2003 | 8/20/2003 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 8/20/2003 at 7:15:30 AM. Contact: ###-####. need fire pump data and jockey/fire pump controller test lines to drain; fire pump couldn't pump to 150 percent capacity as the suction was at zero 8/20/2003 4:13:27 PM
|
BLD-Final | 7/25/2003 | 7/25/2003 | 7/25/2003 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 7/25/2003 at 6:12:53 AM. Contact: ###-####. ok for temp and ok for perm when others sign perm 7/25/2003 10:42:10 AM 7/25/2003 10:42:34 AM
|
FIRE-Final Inspection | 7/25/2003 | 7/25/2003 | 7/25/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 7/25/2003 at 6:11:24 AM. Contact: ###-####. temp occupancy approved per Dave Miller and the requirement for a fire watch until the fire pump is installed and tested with fire alarm monitoring; will need the NFPA 72 record of completion 7/25/2003 3:15:24 PM
|
BLD-Final | 7/24/2003 | 7/24/2003 | 7/24/2003 | P | FAIL |
Troy Cobbley
|
|
|
JOHN ###-####--PENDING BLD FN See correction notice 7/24/2003 2:47:29 PM
|
BLD-Final | 7/24/2003 | 7/24/2003 | 7/24/2003 | P | NR |
Tom Arcoraci
|
|
|
JOHN ###-#### PENDING FIR FN needs fire 7/24/2003 3:11:12 PM
|
BLD-Conference | 7/21/2003 | 7/21/2003 | 7/21/2003 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 7/21/2003 at 7:30:20 AM. Contact: ###-####.
|
FIRE-Conference | 7/21/2003 | 7/21/2003 | 7/21/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 7/21/2003 at 7:29:51 AM. Contact: ###-####. met with John and Troy about final requirements; heads moved up to ceiling in main lobby; frozen head in freezer and obstructed; gaurds on heads; exit sign lowered and need additional one in kitchen; repair and relocate exit sign by bar; storage in mezzanine not allowed; occupant load sign; hanging decorations may not be in comliance with UFC for decorations 7/21/2003 4:41:16 PM
|
BLD-Other | 7/2/2003 | 7/2/2003 | 7/2/2003 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 7/2/2003 at 6:13:41 AM. Contact: ###-####. part grid ok 7/2/2003 10:33:57 AM
|
FIRE-Conference | 7/2/2003 | 7/2/2003 | 7/2/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 7/2/2003 at 6:12:18 AM. Contact: ###-####. Debest fire will have to complete submittals for fire sprinklers and have permit isssued and alarm submittals aren't complete - don't show fire pump and controller and have the permit issued 7/2/2003 4:03:25 PM
|
BLD-Other | 6/3/2003 | 6/3/2003 | 6/3/2003 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 6/3/2003 at 7:07:35 AM. Contact: ###-####. wip ok needs header ?? at mez floor west side 6/3/2003 9:20:41 AM
|
BLD-Wall cover | 5/27/2003 | 5/27/2003 | 5/27/2003 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 5/27/2003 at 6:40:27 AM. Contact: ###-####. ok to cover walls need eng ok for g-lam attachment 5/27/2003 11:09:14 AM
|
BLD-Wall cover | 5/23/2003 | 5/23/2003 | 5/23/2003 | P | FAIL |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 5/23/2003 at 7:18:18 AM. Contact: ###-####. Need Electr R/I approval. 5/23/2003 3:06:58 PM
|
BLD-Wall cover | 5/23/2003 | 5/23/2003 | 5/23/2003 | P | FAIL |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 5/23/2003 at 7:18:18 AM. Contact: ###-####. Talked to Electr inspector.....PART....only select walls to cover.......Told contr to obtain complete Electr R/I approval prior to calling for frame. 5/23/2003 2:07:04 PM
|
BLD-Footing | 4/28/2003 | 4/29/2003 | 4/29/2003 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 4/28/2003 at 4:40:30 PM. Contact: ###-####.
|