Permanent Occupancy | | 3/23/2004 | 3/23/2004 | | DONE |
|
|
|
|
BLD-Final | 12/23/2003 | 12/23/2003 | 12/23/2003 | P | FAIL |
Jim Sly
|
|
|
Joan; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes 12/23/2003 3:53:53 PM Check all Previous notes (history) Need CDHD final verified, and final on Zoning (note: Bonded for landscaping)...... OK to final for Perm. Occ. (in computer) when CDHD and Zoning verified for Perm. 12/23/2003 4:37:07 PM 12/23/2003 4:39:58 PM
|
BLD-Final | 12/11/2003 | 12/11/2003 | 12/11/2003 | P | PART |
Jim Sly
|
|
|
Joan --- please call first for access.+; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes 12/11/2003 12:48:32 PM 12/11/2003 1:45:58 PM OK for Temp Occ. Need CDHD and Plumb final for Perm. Occ. Verify zoning OK..... C/N Need all req signatures for Perm. Occ. within 90 days of this notice. Structural OK when all sinatures received. 12/11/2003 2:02:08 PM
|
BLD-Final | 12/9/2003 | 12/10/2003 | 12/10/2003 | A | FAIL |
Jim Sly
|
|
|
Joan -- please call first for access.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Need all req. signatures. 12/10/2003 9:14:42 AM
|
FIRE-Final Inspection | 12/9/2003 | 12/9/2003 | 12/9/2003 | P | PASS |
Rick Jackson
|
|
|
Joan; Phone #: ###-####, please call first for access. thanks. Internet Inspection Request from: Aimee Hughes
|
BLD-Final | 11/26/2003 | 11/28/2003 | 11/28/2003 | A | CANC |
George Slane
|
|
|
joan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
FIRE-Final Inspection | 11/26/2003 | 11/28/2003 | 11/28/2003 | A | FAIL |
Rick Jackson
|
|
|
joan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need address; fire extinguishers at both levels; NE exit must be openable from the inside without special knowledge and SE exit has deadbolt to be removed; stagjing exit to be lever type; need duct detectors for AC 1 and 2 with remote indicators; need "Door to Remian unlocked..." above main exit double doors 11/28/2003 11:33:21 AM
|
BLD-Framing/Rough-in | 11/20/2003 | 11/20/2003 | 11/20/2003 | P | FAIL |
Jim Sly
|
|
|
joan; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Eng provided for ledgers and attachment.....OK. C/N Eng to advise for bottom chord bracing.....can check at final..... 11/20/2003 2:25:24 PM 11/20/2003 2:27:12 PM
|
BLD-Framing/Rough-in | 11/12/2003 | 11/12/2003 | 11/12/2003 | P | FAIL |
Jim Sly
|
|
|
phillip-- ###-#### C/N Nail roof sheath to blocks or Eng fix (E wall) Blocks and nailing of sheathing at W wall?....Eng to advise fireblock at HVAC chase. 11/12/2003 4:04:53 PM
|
BLD-Framing/Rough-in | 11/5/2003 | 11/5/2003 | 11/5/2003 | P | FAIL |
Jim Sly
|
|
|
joan; Phone #: ###-#### Internet Inspection Request from: Annette Moore C/N Roof/truss not per appr plan.....Eng to provide detail for truss bearing at CMU wall....and attachment.....E wood firred wall ...bearing wall? or Eng to detail ledger and attach for truss bearing? ....Do not cover these areas....need truss eng. 11/5/2003 2:48:19 PM
|
BLD-Concrete | 10/22/2003 | 10/22/2003 | 10/22/2003 | P | PART |
Jim Sly
|
|
|
joan; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Slab......Still need special insp ...unless letter provided from Engineer. 10/22/2003 5:08:15 PM
|
BLD-Concrete | 10/7/2003 | 10/8/2003 | 10/8/2003 | P | PART |
Jim Sly
|
|
|
joan; Phone #: ###-#### Internet Inspection Request from: Annette Moore 10/8/2003 12:18:46 PM OK pending special insp (strata) reports and appr. 10/8/2003 3:21:29 PM
|
BLD-Footing | 10/2/2003 | 10/6/2003 | 10/6/2003 | A | PART |
Jim Sly
|
|
|
joan-- ###-#### C/N Need either spec insp or letter from Eng lowering conc PSI from 3000 to 2500 rebar etc appears OK. 10/6/2003 8:58:18 AM
|