BLD-Final | 3/31/2004 | 3/31/2004 | 3/31/2004 | P | PASS |
Dave Hannah
|
|
|
I have the card and all others have signed off for permanent. Please let me know if you have any outstanding issues. Thanks, Cathy ~ok for perm occ 3/31/2004 4:36:22 PM
|
Permanent Occupancy | | 3/31/2004 | 3/31/2004 | | DONE |
|
|
|
|
FIRE-Final Inspection | 3/25/2004 | 3/30/2004 | 3/30/2004 | P | PASS |
Rick Jackson
|
|
|
Larry, ###-#### Hood system connected to fire alarm panel; fire/life safety final okay 3/30/2004 3:09:22 PM
|
FIRE-Final Inspection | 3/23/2004 | 3/24/2004 | 3/24/2004 | A | NR |
Rick Jackson
|
|
|
Eric, ###-#### Need to test the hood extinguishing system with the new alarm panel/permit; Larry will schedule for next week to test the alarm permit work 3/24/2004 11:12:07 AM
|
BLD-Final | 12/23/2003 | 12/24/2003 | 12/24/2003 | P | PART |
Dave Hannah
|
|
|
ERIC; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok for temp occ 12/24/2003 2:02:14 PM
|
FIRE-Final Inspection | 12/23/2003 | 12/24/2003 | 12/24/2003 | A | PART |
Rick Jackson
|
|
|
temp occupancy approved per Dave Miller pending completion of the fire alarm upgrade to connect the extinguishing system and adding fire sprinkler in the walk-in cooler 12/24/2003 11:29:06 AM
|
FIRE-Final Inspection | 12/22/2003 | 12/23/2003 | 12/23/2003 | A | FAIL |
Rick Jackson
|
|
|
ERick; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes need panic on exit as shown on plans; remove exit sign at north exit; occupant load sign; emergency lighting needed; sprinkler head in cooler; door hardware on kitchen door 12/23/2003 10:27:40 AM
|
BLD-Final | 12/19/2003 | 12/22/2003 | 12/22/2003 | P | FAIL |
Dave Hannah
|
|
|
erik; Phone #: ###-#### Internet Inspection Request from: Darla Downs needs fire sign offs and one mec finaled 12/22/2003 2:18:04 PM
|
BLD-Framing/Rough-in | 12/2/2003 | 12/3/2003 | 12/3/2003 | A | PART |
Dave Hannah
|
|
|
John; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes int nonload bearing walls ok to cover 12/3/2003 1:33:34 PM
|