BLD-Final | 9/24/2004 | 9/24/2004 | 9/24/2004 | P | PASS |
Tom Arcoraci
|
|
|
tim ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIRE-Final Inspection | 9/24/2004 | 9/24/2004 | 9/24/2004 | P | PASS |
Troy Cobbley
|
|
|
life safety finaled 9/24/2004 10:28:34 AM
|
Code Occupancy Approval | 9/23/2004 | 9/23/2004 | 9/23/2004 | P | PASS |
Scott M.Brown
|
|
|
ALL IN AS REQUIRED FINAL SIGNED 9/23/2004 2:58:02 PM
|
Permanent Occupancy | | 9/23/2004 | 9/23/2004 | | DONE |
|
|
|
|
FIRE-Final Inspection | 9/10/2004 | 9/10/2004 | 9/10/2004 | P | FAIL |
Troy Cobbley
|
|
|
Provide two emergency lights in the open office area as per plans and provide correct door hardware on the main entry/exit 9/10/2004 4:39:28 PM
|
BLD-Framing/Rough-in | 8/16/2004 | 8/16/2004 | 8/16/2004 | P | PART |
Lane Manuel
|
|
|
TIM; Phone #: ###-#### Internet Inspection Request from: Annette Moore
offices 13 thru 16 t-bar ok 8/16/2004 2:30:20 PM
|
BLD-Framing/Rough-in | 8/5/2004 | 8/6/2004 | 8/6/2004 | A | PART |
Lane Manuel
|
|
|
tim ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. t-bar passed. contr. to leave 3 areas exposed for c/n mech, per dixie. 8/6/2004 10:16:36 AM
|
FIRE-Conference | 8/4/2004 | 8/4/2004 | 8/4/2004 | P | DONE |
Troy Cobbley
|
|
|
A duct smoke detector is to be added to RTU8 8/4/2004 4:27:18 PM
|
BLD-Framing/Rough-in | 7/29/2004 | 7/29/2004 | 7/29/2004 | P | PART |
Tom Arcoraci
|
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wip ok to cover beam 7/29/2004 3:27:59 PM
|
BLD-Final | 7/26/2004 | 7/27/2004 | 7/27/2004 | A | NR |
Tom Arcoraci
|
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
FIRE-Final Inspection | 7/26/2004 | 7/27/2004 | 7/27/2004 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for multiple rooms in the next phase of the project. See city approved plans, sheets A2.2, A2.3 and A2.5 for the specific rooms and deficiencies. There are card readers and door magnets being installed. I contacted Nick with Synergy and Jason with AEI about IFC and IBC requirements for access controlled egress doors. These items are not shown on the approved fire alarm plans. Plans will require possible resubmittals. 7/27/2004 10:27:32 AM
|
BLD-Framing/Rough-in | 7/22/2004 | 7/22/2004 | 7/22/2004 | P | PART |
Tom Arcoraci
|
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes gid ok partial 7/22/2004 2:35:42 PM
|
BLD-Framing/Rough-in | 7/15/2004 | 7/15/2004 | 7/15/2004 | P | PART |
Tom Arcoraci
|
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles north west side ok for cover needs eng letter for beam hanger change 7/15/2004 12:40:17 PM
|
BLD-Conference | 7/2/2004 | 7/2/2004 | 7/2/2004 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 7/2/2004 at 8:44:16 AM. Contact: ###-####.
|
BLD-Final | 7/2/2004 | 7/2/2004 | 7/2/2004 | P | PASS |
Tom Arcoraci
|
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for temp occ of phase 2 7/2/2004 1:23:15 PM
|
FIRE-Final Inspection | 7/2/2004 | 7/2/2004 | 7/2/2004 | P | PART |
Troy Cobbley
|
|
|
Phase II ok to occupy. Still need to test the main fire alarm system. 7/2/2004 9:58:40 AM
|
FIRE-Final Inspection | 7/2/2004 | 7/2/2004 | 7/2/2004 | P | CANC |
Troy Cobbley
|
|
|
duplicate inspection 7/2/2004 9:56:19 AM
|
BLD-Conference | 7/1/2004 | 7/1/2004 | 7/1/2004 | A | PASS |
Tom Arcoraci
|
|
|
contractor repairing 1 hr in old building 7/1/2004 9:46:31 AM
|
BLD-Other | 6/28/2004 | 6/28/2004 | 6/28/2004 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 6/28/2004 at 6:26:33 AM. Contact: ###-####. old building not V-a only all new construction in this area inspected as V-a 6/28/2004 10:28:19 AM 6/28/2004 10:29:03 AM
|
BLD-Framing/Rough-in | 6/24/2004 | 6/25/2004 | 6/25/2004 | A | PART |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 6/24/2004 at 1:30:21 PM. Contact: ###-####. Roof/ceiling assembly OK above restroom hard lid ceilings....Note Need to add blocks to create double top plate and firecaulk edge of rock on ceiling, - or - rock face of Non bearing interior walls above hard lid. ( Restroom to the North). 6/25/2004 12:31:20 PM 6/25/2004 12:32:58 PM 6/25/2004 12:34:26 PM
|
BLD-Conference | 6/22/2004 | 6/22/2004 | 6/22/2004 | P | DONE |
Troy James
|
|
|
Scheduled by a contractor via Hello! on 6/22/2004 at 8:35:27 AM. Contact: ###-####.
|
BLD-Final | 6/14/2004 | 6/14/2004 | 6/14/2004 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 6/14/2004 at 6:04:11 AM. Contact: ###-####. ok first phase 6/14/2004 10:17:41 AM
|
FIRE-Conference | 6/10/2004 | 6/11/2004 | 6/11/2004 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 6/10/2004 at 6:15:55 PM. Contact: ###-####. Scheduled for first phase this afternoon 6/11/2004 2:36:04 PM
|
FIRE-Final Inspection | 6/11/2004 | 6/11/2004 | 6/11/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 6/11/2004 at 10:22:38 AM. Contact: ###-####. Phase I okay to occupy 6/11/2004 2:45:57 PM
|
Code Occupancy Approval Temp | 6/8/2004 | 6/8/2004 | 6/7/2004 | A | DONE |
Scott M.Brown
|
|
|
SIGNEDE OFF TEMP CCUPANCY DUE TO UTILITY WORK, THEY CLAIM PARKING LOT AND LAND SCAPE TO BE IN PLACE IN 2-3- WEEKS, DUE TO BEING PHASE WORK I DID NOT REQUIRED BOND BECAUSE WE HAVE OTHER PERMITS/OCCUPANCY TO HOLD. 6/8/2004 9:28:23 AM
|
BLD-Other | 6/5/2004 | 6/7/2004 | 6/7/2004 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 6/5/2004 at 4:35:18 PM. Contact: ###-####. grid and firestop above ok 6/7/2004 10:15:32 AM
|
FIRE-Conference | 6/4/2004 | 6/4/2004 | 6/4/2004 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 6/4/2004 at 7:00:34 AM. Contact: ###-####. This is a phased project and the GC wanted to know about occupying the new addition without having the new parking lot completed - the area must have FD vehicle access surface; smoke/fire dampers are installed in new addition and there isn't a plan as to how they are activated - GC will contact architect 6/4/2004 10:57:13 AM
|
BLD-Other | 5/6/2004 | 5/7/2004 | 5/7/2004 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 5/6/2004 at 8:20:16 PM. Contact: ###-####.
|
BLD-Energy code compliance | 5/5/2004 | 5/6/2004 | 5/6/2004 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 5/5/2004 at 4:40:58 PM. Contact: ###-####.
|
BLD-Framing/Rough-in | 5/6/2004 | 5/6/2004 | 5/6/2004 | A | PART |
Tom Arcoraci
|
|
|
framing ok check fire chalk at walls check ceiling and corr at grid 5/6/2004 8:54:01 AM
|
BLD-Framing/Rough-in | 5/5/2004 | 5/6/2004 | 5/6/2004 | A | CANC |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 5/5/2004 at 4:39:32 PM. Contact: ###-####.
|
BLD-Framing/Rough-in | 5/5/2004 | 5/5/2004 | 5/5/2004 | A | NR |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 5/5/2004 at 7:26:31 AM. Contact: ###-####. called contractor can find no approval to insulate walls, and now almost complete with insulatiom, he will recall when insulation is complete and they are out of the building,and 408 will be back for job history check to verify framing , as noted ceiling insulation only by last entry. 5/5/2004 2:53:56 PM
|
BLD-Framing/Rough-in | 4/29/2004 | 4/29/2004 | 4/29/2004 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 4/29/2004 at 8:04:36 AM. Contact: ###-####. ok to insulate ceiling 4/29/2004 2:20:46 PM
|
BLD-Framing/Rough-in | 4/28/2004 | 4/28/2004 | 4/28/2004 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 4/28/2004 at 6:42:11 AM. Contact: ###-####. ext shear ok 4/28/2004 9:42:48 AM
|
BLD-Framing/Rough-in | 4/28/2004 | 4/28/2004 | 4/28/2004 | P | PART |
Tom Arcoraci
|
|
|
|
BLD-Foundation | 3/18/2004 | 3/18/2004 | 3/18/2004 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 3/18/2004 at 9:19:16 AM. Contact: ###-####. wip 3/18/2004 3:34:05 PM
|
BLD-Footing | 3/16/2004 | 3/16/2004 | 3/16/2004 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 3/16/2004 at 7:20:51 AM. Contact: ###-####. spec insp on site 3/16/2004 10:27:44 AM 3/16/2004 10:27:57 AM
|