BLD-Aging Inspection | 6/19/2006 | 6/19/2006 | 6/19/2006 | | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Finaled | 6/19/2006 | 6/19/2006 | 6/19/2006 | P | PASS |
Mike Jordan
|
|
|
life/safety has finaled. ok.
|
Permanent Occupancy | | 6/19/2006 | 6/19/2006 | | DONE |
|
|
|
|
BLD-Aging Inspection | 4/10/2006 | 4/10/2006 | 4/10/2006 | | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Expired | 4/10/2006 | 4/10/2006 | 4/10/2006 | A | DONE |
Mike Jordan
|
|
|
|
BLD-Final | 9/9/2005 | 9/9/2005 | 9/9/2005 | P | NR |
Mike Jordan
|
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Aging Inspection | 7/25/2005 | 7/25/2005 | 7/25/2005 | | NR |
Tom Arcoraci
|
|
|
exp
|
BLD-Aging Inspection | 5/23/2005 | 5/23/2005 | 5/23/2005 | | PASS |
Tom Arcoraci
|
|
|
ok for final now that fire is finaled
|
FIRE-Final Inspection | 2/8/2005 | 2/8/2005 | 2/8/2005 | P | PASS |
Troy Cobbley
|
|
|
fire life safety finaled 2/8/2005 12:26:24 PM
|
FIRE-Final Inspection | 2/3/2005 | 2/3/2005 | 2/3/2005 | P | PART |
Troy Cobbley
|
|
|
Scott; Phone #: ###-#### A temporary occupancy was given until the arrows are fixed in the exit sign in the spa or it has been turned. 2/3/2005 2:44:52 PM
|
FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | FAIL |
Troy Cobbley
|
|
|
Repair the emergency light at the main entrance. Repair the exit sign at the north end of the back corridor. Install fire extinguisher at the front entrance. Turn the exit sign in the spa area to point the right way or delete arrow. 2/2/2005 3:38:19 PM
|
FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | FAIL |
Troy Cobbley
|
|
|
Repair the emergency light at the main entrance. Repair the exit sign at the north end of the back corridor. Install fire extinguisher at the front entrance. Turn the exit sign in the spa area to point the right way or delete arrow. 2/2/2005 3:38:19 PM
|
FIRE-Final Inspection | 2/1/2005 | 2/1/2005 | 2/1/2005 | P | FAIL |
Rick Jackson
|
|
|
Fire sprinkler anti-freeze okay per test reports from Grinnel; need fire extinguishers; key lock at main exit; add exit signs per plans and relocate one; need to test exit signs and emergency lights for battery back-up 2/1/2005 3:05:39 PM
|
BLD-Final | 1/31/2005 | 1/31/2005 | 1/31/2005 | P | PART |
Lane Manuel
|
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice
Temp. C of O OK pending fire insp. temp. occ. approval. 1/31/2005 4:03:45 PM
|
BLD-Framing/Rough-in | 11/29/2004 | 11/29/2004 | 11/29/2004 | P | PART |
Lane Manuel
|
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice
framing @ Interior "dome" ok per eng. design. 11/29/2004 1:41:38 PM
|
BLD-Framing/Rough-in | 11/17/2004 | 11/18/2004 | 11/18/2004 | P | FAIL |
Lane Manuel
|
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner
need to provide additional firestopping mat'l @ rear of space.
need rough fire sprinkler approval ? 11/18/2004 1:35:22 PM
|
BLD-Framing/Rough-in | 11/15/2004 | 11/16/2004 | 11/16/2004 | A | FAIL |
Jim Sly
|
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice C/N posted. 11/16/2004 5:02:45 PM
|
BLD-Final | 10/26/2004 | 10/27/2004 | 10/27/2004 | A | CANC |
Jim Storey
|
|
|
brian --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Final | 10/26/2004 | 10/27/2004 | 10/27/2004 | A | CANC |
Jim Storey
|
|
|
brian --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIRE-Final Inspection | 10/27/2004 | 10/27/2004 | 10/27/2004 | P | FAIL |
Troy Cobbley
|
|
|
Tamper zone was set up as a trouble zone not a supervisory zone. Monitoring station did not receive all of the trouble signals. Need junction box at valve for the wire splices. 10/27/2004 4:02:38 PM
|
BLD - Request for Extension | 10/21/2004 | 10/22/2004 | 10/22/2004 | | PASS |
Tom Arcoraci
|
|
|
Still working on this project Kim Stark ###-####
|
BLD-Aging Inspection | 6/3/2004 | 6/3/2004 | 6/3/2004 | | NR |
Troy James
|
|
|
|