Permit NumberBLD03-02995
StatusFinaled
Name VIZIATO (SPA/SALON)
Site Address 8655 W FRANKLIN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
(VIZIATO) This building is fire sprinklered for building area increase. To remodel an existing 3,392 square foot tenant space for a spa/salon tenant. This space was formerly used for the retail sales of mattresses. Work is to include 2 shower/toilet rooms accessible to the disabled, interior nonbearing walls, millwork, and finishes all per the approved drawings and the plan review report on file. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection6/19/20066/19/20066/19/2006 DONE
DetailsMike Jordan
DOC - Permit Finaled6/19/20066/19/20066/19/2006PPASS
DetailsMike Jordan
life/safety has finaled. ok.
Permanent Occupancy 6/19/20066/19/2006 DONE
Details
BLD-Aging Inspection4/10/20064/10/20064/10/2006 DONE
DetailsMike Jordan
DOC - Permit Expired4/10/20064/10/20064/10/2006ADONE
DetailsMike Jordan
BLD-Final9/9/20059/9/20059/9/2005PNR
DetailsMike Jordan
scott; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
BLD-Aging Inspection7/25/20057/25/20057/25/2005 NR
DetailsTom Arcoraci
exp
BLD-Aging Inspection5/23/20055/23/20055/23/2005 PASS
DetailsTom Arcoraci
ok for final now that fire is finaled
FIRE-Final Inspection2/8/20052/8/20052/8/2005PPASS
DetailsTroy Cobbley
fire life safety finaled 2/8/2005 12:26:24 PM
FIRE-Final Inspection2/3/20052/3/20052/3/2005PPART
DetailsTroy Cobbley
Scott; Phone #: ###-#### A temporary occupancy was given until the arrows are fixed in the exit sign in the spa or it has been turned. 2/3/2005 2:44:52 PM
FIRE-Final Inspection2/2/20052/2/20052/2/2005PFAIL
DetailsTroy Cobbley
Repair the emergency light at the main entrance. Repair the exit sign at the north end of the back corridor. Install fire extinguisher at the front entrance. Turn the exit sign in the spa area to point the right way or delete arrow. 2/2/2005 3:38:19 PM
FIRE-Final Inspection2/2/20052/2/20052/2/2005PFAIL
DetailsTroy Cobbley
Repair the emergency light at the main entrance. Repair the exit sign at the north end of the back corridor. Install fire extinguisher at the front entrance. Turn the exit sign in the spa area to point the right way or delete arrow. 2/2/2005 3:38:19 PM
FIRE-Final Inspection2/1/20052/1/20052/1/2005PFAIL
DetailsRick Jackson
Fire sprinkler anti-freeze okay per test reports from Grinnel; need fire extinguishers; key lock at main exit; add exit signs per plans and relocate one; need to test exit signs and emergency lights for battery back-up 2/1/2005 3:05:39 PM
BLD-Final1/31/20051/31/20051/31/2005PPART
DetailsLane Manuel
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice
Temp. C of O OK pending fire insp. temp. occ. approval. 1/31/2005 4:03:45 PM
BLD-Framing/Rough-in11/29/200411/29/200411/29/2004PPART
DetailsLane Manuel
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice
framing @ Interior "dome" ok per eng. design. 11/29/2004 1:41:38 PM
BLD-Framing/Rough-in11/17/200411/18/200411/18/2004PFAIL
DetailsLane Manuel
Scott; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner
need to provide additional firestopping mat'l @ rear of space.
need rough fire sprinkler approval ? 11/18/2004 1:35:22 PM
BLD-Framing/Rough-in11/15/200411/16/200411/16/2004AFAIL
DetailsJim Sly
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice C/N posted. 11/16/2004 5:02:45 PM
BLD-Final10/26/200410/27/200410/27/2004ACANC
DetailsJim Storey
brian --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
BLD-Final10/26/200410/27/200410/27/2004ACANC
DetailsJim Storey
brian --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIRE-Final Inspection10/27/200410/27/200410/27/2004PFAIL
DetailsTroy Cobbley
Tamper zone was set up as a trouble zone not a supervisory zone. Monitoring station did not receive all of the trouble signals. Need junction box at valve for the wire splices. 10/27/2004 4:02:38 PM
BLD - Request for Extension10/21/200410/22/200410/22/2004 PASS
DetailsTom Arcoraci
Still working on this project Kim Stark ###-####
BLD-Aging Inspection6/3/20046/3/20046/3/2004 NR
DetailsTroy James