Permit Information
Permit NumberBLD04-00155
StatusFinaled
Name BOISE CONSUMER CO-OP
Site Address 888 W FORT ST
Project NameBOISE CONSUMER CO-OP
Customer Number 
ePlanReviewNo
Description
(BOISE CONSUMER CO-OP) Install a Class I hood system and grease duct in the meat department per approved plans. The duct is to be wrapped with fire master duct wrap system per manufactures listing requirements. This building is fully fire spinklered.(PC#051-04) (RMH)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/28/20044/29/20044/29/2004PPASS
DetailsDave Hannah
richard; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIRE-Final Inspection4/28/20044/28/20044/28/2004PPASS
DetailsRick Jackson
FIRE-Final Inspection4/20/20044/20/20044/20/2004AFAIL
DetailsRick Jackson
Fire sprinklers overspaced from new hood to meat prep area - from hood to next sprinler is over 10ft; there appeared to be a head that was removed to make room for the new hood and should have been relocated outside the hood to prevent overspacing 4/20/2004 8:40:33 AM