Permanent Occupancy | | 8/17/2005 | 8/17/2005 | | DONE |
|
|
|
|
FIRE-Final Inspection | 6/17/2005 | 6/17/2005 | 6/17/2005 | P | PASS |
Forrest France
|
|
|
Fire life safety finaled.
|
BLD-Final | 5/17/2005 | 5/18/2005 | 5/18/2005 | A | PART |
Jim Storey
|
|
|
tim -pending fire fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylietemp ok pending ada on pocket door /restaroom signage/ele perm
|
FIRE-Final Inspection | 5/17/2005 | 5/18/2005 | 5/18/2005 | A | PART |
Forrest France
|
|
|
Temporary occupancy given with Sam Rogers permission. Final pending installation of approved door hardware on pocket door at file room. Pocket door has been disabled for use until approved hardware is installed.
|
FIRE-Final Inspection | 5/13/2005 | 5/13/2005 | 5/13/2005 | P | FAIL |
Forrest France
|
|
|
Smoke detectors did not shut down HVAC units upon activation. Post street address. Provide exit disharge light and test. Install fire extiguisher. Provide approved door hardware on pocket door at file room.
|
BLD-Energy code compliance | 4/18/2005 | 4/18/2005 | 4/18/2005 | P | PASS |
Jim Storey
|
|
|
tim ###-####
|
BLD-Framing/Rough-in | 4/15/2005 | 4/15/2005 | 4/15/2005 | P | NR |
Jim Storey
|
|
|
ceing grid inspection please///tim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 3/2/2005 | 3/3/2005 | 3/3/2005 | A | PASS |
Troy James
|
|
|
tim ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Aging Inspection | 12/20/2004 | 12/20/2004 | 12/20/2004 | | PASS |
Jim Storey
|
|
|
wip 12/20/2004 8:22:07 AM
|