BLD-Final | 1/21/2011 | 1/24/2011 | 1/24/2011 | A | PASS |
Mike Jordan
|
|
|
holly Phone #: ###-####. All issues resolved. Ok for perm occ.
|
FIRE-Final Inspection | 1/21/2011 | 1/21/2011 | 1/21/2011 | P | PASS |
Troy Cobbley
|
|
|
All items from the previous correction notice have been corrected. Holly and I discussed the allowed storage arrangement.
|
BLD-Aging Inspection | 11/26/2010 | 11/26/2010 | 11/30/2010 | P | DONE |
Troy Cobbley
|
|
|
Information has been forwarded to Jason Blais and Scott Arellano as per policy for aging permits.
|
BLD-Aging Inspection | 11/26/2010 | 11/26/2010 | 11/26/2010 | | PEND |
Tom Arcoraci
|
|
|
|
FIRE-Conference | 5/4/2010 | 5/13/2010 | 5/13/2010 | A | DONE |
Troy Cobbley
|
|
|
I stopped at the job site and spoke to Holly about the job status.
|
FIRE-Conference | 5/5/2010 | 5/6/2010 | 5/6/2010 | A | DONE |
Troy Cobbley
|
|
|
I went over items completed and remaining items with Holly, Clint, Tim and the warehouse manager. All items have been corrected except on exit sign/emergency light at the south warehouse exit did not function, missing Knox Box, and possibly a racking/high piled storage permit. If a racking/storage permit is to be a voided the owner needs to keep all storage under 12', racks no higher than 8' and empty plastic water bottles less than 5'. Water filled bottles can be stored up to 12'. The racks will have to be modified to permanantly discourage placement of horizontal members above 8'. Tim Frost was consulted.
|
FIRE-Conference | 5/4/2010 | 5/5/2010 | 5/5/2010 | A | DONE |
Troy Cobbley
|
|
|
I spoke to Clint about getting this project finaled. He needs a conference for tomorrow morning to discuss the issues.
|
BLD-Conference | 2/5/2008 | 2/5/2008 | 2/6/2008 | A | FAIL |
Mike Jordan
|
|
|
Talked to secratary at echo water, left business card, manager to call me. No return phone call as of 5:00pm today.
|
BLD-Aging Inspection | 4/26/2007 | 4/26/2007 | 4/26/2007 | | NR |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 10/25/2006 | 10/25/2006 | 10/30/2006 | | NR |
Mike Jordan
|
|
|
Needs life/safety.
|
BLD-Aging Inspection | 8/24/2006 | 8/24/2006 | 8/24/2006 | | NR |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 6/20/2006 | 6/20/2006 | 6/20/2006 | | NR |
Troy Cobbley
|
|
|
|
BLD-Final | 4/12/2006 | 4/13/2006 | 4/13/2006 | A | FAIL |
Troy Cobbley
|
|
|
Clint; Phone #: ###-#### Repair the exit signs/emergency lights in the warehouse area, the exit signs in the office need repaired or removed, Remove the thumbturn from the main exit and provide indicator and sticker, remoe the dead bolts from the warehouse exterior doors, provide racking permit for racking over 8' and the storage over 12' see review notes #1 and #19, provide fire extinguishers per fire review comment #7, provide code compliant fire sprinkler monitoring system per review comment #15, provide knox box per review comment #6. Owner needs to review comments #16 through #26 for high piled storage requirements.
|
BLD-Aging Inspection | 4/11/2006 | 4/11/2006 | 4/12/2006 | | NR |
Troy Cobbley
|
|
|
I spoke to clint and he would find the drawings and call in the inspection for tommorrow
|
FIRE-Final Inspection | 6/30/2004 | 7/1/2004 | 6/30/2004 | A | CANC |
Troy Cobbley
|
|
|
CLINT; Phone #: ###-#### Internet Inspection Request from: Annette Moore Inspection cancelled from web by: Aimee Hughes
|