Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberBLD04-01051
StatusFinaled
Name CAFCO INC
Site Address 9958 W FAIRVIEW AVE
Project NameEurope Delicious Bakery
Customer Number 
ePlanReviewNo
Description
Europe Delicious Bakery - To construct a 7063 sq. ft. Type VA, two story shell building with three separate tenant spaces. First floor to have an 2076 sq. ft. future tenant space and a 3876 sq. ft. tenant space for the future bakery. The second floor future tenant space has been designed for a Group R-3 occupancy only with one exit and 40 # floor load. A conditional use permit shall be required for the residence on the second floor. Other work includes all site improvements, paving and landscaping per approved plans and attachments. No occupancy is allowed under this shell permit. All tenant spaces will require separate plans and permits to be provided prior to any construction beyond the shell. As being a fire-resisitive building all basic fire rated construction for the shell as shown on the approved plans must be completed. Tenant Improvement permit for the bakery is under BLD04-01882 and has been included with the approved plans. letter of completion only
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final6/23/20056/23/20056/23/2005PPART
DetailsJim Sly
bill; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
OK for Temp Occ. C/N..... Need Mech and Public works to sign for Perm Occ. Obtain Perm Occ status within 90 days of this notice
FIRE-Final Inspection6/23/20056/23/20056/23/2005APASS
DetailsForrest France
Fire life safety finaled.
FIRE-Final Inspection6/22/20056/22/20056/22/2005PFAIL
DetailsForrest France
HVAC RTU at northeast corner of building failed to shut down upon smoke detection, all remaining life safety issues are satisfactory.
FIRE-Final Inspection6/21/20056/21/20056/21/2005AFAIL
DetailsForrest France
Duct smoke detectors failed to shut HVAC units off upon activation, exit discharge lighting at three locations still not working, door hardware at two doors is not approved.
BLD-Final6/20/20056/20/20056/20/2005PFAIL
DetailsForrest France
Exit discharge lighting at three locations did not operate under emergency power, max occ. signs not installed, not all door hardware has been installed , still need to test duct smoke detectors and annunciators, hood suppresion system not ready to test.
BLD-Final6/16/20056/16/20056/16/2005PNR
DetailsJim Sly
bill; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Met with Troy C and owner to go over code issues. (Fire life/safety and structural issues)
FIRE-Final Inspection6/16/20056/16/20056/16/2005PFAIL
DetailsTroy Cobbley
Provide panic hardware on both north doors and the one west exit door from the banquet room. Provide exit discharge lighting on the banquet room doors and the coffee shop doors. Provide maximum occupant load signs for the banquet room "184" and the coffee shop "56". Provide ADA approved hardware on all doors. Install and test the duct smoke detectors and the remote annunciators. Provide hood suppression system for the type 1 hood with permit.
FIRE-Final Inspection6/14/20056/15/20056/15/2005AFAIL
DetailsTroy Cobbley
bill; Phone #: ###-#### Remove thumbturn locks from east exit doors, Provide "Door to remain unlocked when building is occupied" at both of the east exit doors, test duct smoke detectors and provide with approved remote annunciators, provide address numbers viewable from Fairview. Fixed seating is not allowed per shell permit review comments.
BLD-Conference5/27/20055/31/20055/31/2005ACANC
DetailsJim Sly
bill ###-#### says per dixie's request
BLD-Conference4/28/20054/29/20054/29/2005ADONE
DetailsJim Sly
per your request Internet Inspection Request from: Letitia Mesa George Slane has had a discussion with the new Contractor (Bill) on this job about his responsibility to follow Requests per Bldg, Plumb, and Mech inspectors per their Correction Notices. George said that the Contractor understands all corrections that are posted. Selected Corrections are as follows. Structural: Do not go beyond the scope of work approved by the City of Boise. Do not cover Plumbing installed W/O permit (ie. for 2nd story R-3) or area of Kitchen where new hood to be located. I have allowed Contr to cover selected areas per appr plan. No additional work to be completed on future tenant spaces, including R-3 space (2nd floor), W/O Bldg permit . Mech Corrections: Do not rock Kitchen. Plumbing was asked to inspect and approve Plumbing installed for R-3 and said they would when a permit is issued. for that area. 4/29/2005 12:24:06 PM 4/29/2005 12:36:30 PM
BLD-Conference4/28/20054/29/20054/29/2005ACANC
DetailsJim Sly
per your request Internet Inspection Request from: Letitia Mesa
BLD-Conference4/14/20054/15/20054/15/2005APART
DetailsJim Sly
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Ok to rock lid... exept Kitch and portion below 2nd story. 4/15/2005 12:02:22 PM
BLD-Framing/Rough-in4/11/20054/12/20054/12/2005ANR
DetailsJim Sly
bill ###-#### Complete Corr. 4/12/2005 11:05:34 AM
BLD-Framing/Rough-in4/4/20054/4/20054/4/2005PFAIL
DetailsJim Sly
bill; Phone #: ###-#### Internet Inspection Request from: Barbara Moore C/N posted. 4/4/2005 3:14:31 PM
BLD-Conference3/24/20053/25/20053/25/2005APART
DetailsJim Sly
###-#### bill Talked with Mike Otto.....Need 1hr roof/ceiling and floor/ceiling assembly through out.... talked with Bill (contractor) about this. 3/25/2005 11:31:17 AM
BLD-Conference3/23/20053/24/20053/24/2005ANR
DetailsJim Sly
BILL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
BLD-Conference2/22/20052/22/20052/22/2005PPART
DetailsJim Sly
Bill; Phone #: ###-#### Internet Inspection Request from: Jan Rice Met with Bill.....(new Contractor) Corr notice.....Notify City of Boise for changes of Gen Contr, Eng of record or Arch of record. Need all Eng and Engineers Calcs. Do not build beyond approved plan. 2/22/2005 3:02:59 PM
BLD-Conference2/7/20052/8/20052/8/2005ADONE
DetailsLane Manuel
BILL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
spoke w/ contr. regarding roof sheathing issues 2/8/2005 11:50:22 AM
BLD-Conference1/7/20051/10/20051/10/2005APART
DetailsJim Sly
Met with Terry of Benchmark Constr. to discuss requirements for completion of this project. They are bidding for the completion. 1/10/2005 12:08:39 PM
BLD-Conference1/7/20051/7/20051/7/2005PCANC
DetailsJim Sly
Terry; Phone #: ###-#### Internet Inspection Request from: Jan Rice canncell reschedule monday - Terry
BLD-Conference12/8/200412/8/200412/8/2004PPART
DetailsJim Sly
Bill; Phone #: ###-#### Internet Inspection Request from: Jan Rice Met with Bill Caferetti........He may be the new Contractor for this job. If so, Advised to change on Case information on project.....Contact City of Boise. Was notified from Mike Otto that B J Developement is no longer the Contractor for this job. 12/8/2004 2:42:56 PM 12/8/2004 2:45:48 PM
BLD-Conference11/12/200411/15/200411/15/2004ANR
DetailsJim Sly
joan ###-#### Joan called and cancelled. 11/15/2004 9:33:13 AM
BLD-Conference11/10/200411/12/200411/12/2004ACANC
DetailsTom Arcoraci
joan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles///canceled per Joan///11/12/01 8:05am BAS
BLD-Conference11/10/200411/12/200411/12/2004ACANC
DetailsTom Arcoraci
joan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
BLD-Conference11/4/200411/5/200411/5/2004APART
DetailsJim Sly
Joan call 1/2 hr ahead; Phone #: ###-#### Internet Inspection Request from: Jan Rice Met with Joan.... C/N Any changes on Approved Shell/core plan must be resubmitted to Boise City Plan review for approval. Do not build beyond what is on approved plan. 11/5/2004 11:32:48 AM
BLD-Conference11/1/200411/1/200411/1/2004PPART
DetailsJim Sly
Joan please call before you go; Phone #: ###-#### Internet Inspection Request from: Jan Rice 11/1/2004 2:39:52 PM
BLD-Other6/9/20046/9/20046/9/2004ADONE
DetailsJim Sly
Jennifer called and asked me to issue a STOP WORK at this address. This was completed 6/7/04 AM. Footings and foundation walls poured W/O inspection. Backfill completed and excavators and plumbers were working on underground Plumbing. There is no Temp Electrical installed. Contractor (lady) was on site when I issued Stop work order for Building W/O Bldg permit. Jim Sly (316).