(J R SIMPLOT COMPANY - 3RD FLOOR) This building is fire sprinklered because it is a high-rise. To remodel the 3rd floor (17,073 square feet) of an existing high-rise building for a whole floor tenant (15,900 net square feet). For exit separation reasons, a 2-hr fire barrier intended to function as a horizontal exit will be constructed to divide the floor into two egress areas. Work is to include interior nonbearing walls, 2-hr fire barrier walls with fire doors, interior doors and windows, and glass block walls all per the approved drawings and the plan review report on file. The restrooms are also being upgraded to be accessible to the disabled. The location of fire sprinkler heads shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection11/24/200411/29/200411/29/2004APASS
DetailsRick Jackson
Fire/life safety final okay 11/29/2004 11:20:24 AM
Permanent Occupancy 11/29/200411/29/2004 DONE
Details
BLD-Final11/15/200411/16/200411/16/2004APART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 11/15/2004 at 10:30:26 AM. Contact: ###-####. ok for temp occ ok for perm occ after fire alarm go perm 11/16/2004 10:37:21 AM
FIRE-Final Inspection11/15/200411/16/200411/16/2004APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 11/15/2004 at 10:31:14 AM. Contact: ###-####. Temp occupancy approved per Dave Miller for fire alarm - need detectors at doors with hold opens 11/16/2004 12:05:39 PM
BLD-Final11/12/200411/12/200411/12/2004PFAIL
DetailsJim Storey
Scheduled by a contractor via Hello! on 11/12/2004 at 8:34:36 AM. Contact: ###-####. cable trays not protected per listing. doors not latching/ separate permit needed for sucurty firerated stairs and rated door function. 11/12/2004 2:46:43 PM
FIRE-Final Inspection11/12/200411/12/200411/12/2004PFAIL
DetailsRick Jackson
Rated doors not latching; it appears card reader access control locks are being installed by tenant contractors - a separate permit will be required to interface with alarm system with motion sensor and push to exit button release; hang fire extinguishers 11/12/2004 2:50:26 PM
BLD-Framing/Rough-in9/23/20049/24/20049/24/2004PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 9/23/2004 at 5:38:37 PM. Contact: ###-####. ok to cover north half 9/24/2004 2:14:31 PM
BLD-Framing/Rough-in8/27/20048/27/20048/27/2004PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 8/27/2004 at 9:54:36 AM. Contact: ###-####. short wall bracing ok 8/27/2004 4:13:29 PM
BLD-Energy code compliance8/24/20048/26/20048/26/2004APASS
DetailsDave Hannah
Scheduled by a contractor via Hello! on 8/24/2004 at 10:18:37 AM. Contact: ###-####. ok to cover walls 8/26/2004 9:52:15 AM
BLD-Wall cover8/19/20048/20/20048/20/2004APART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 8/19/2004 at 2:57:22 PM. Contact: ###-####. ok to cover one side but need to remove screws from top track that have run into ceiling grid also need braceing on 4 and 6 high walls and detail on soffit item 17 on plans 8/20/2004 10:36:29 AM