Permit Information
Permit NumberBLD04-02239
StatusFinaled
Name LE CAFE DE PARIS
Site Address 204 N CAPITOL BLVD
Project NameFONG BLDG-BASEMENT
Customer Number 
ePlanReviewNo
Description
(LE CAFE DE PARIS)(FONG BLDG-BASEMENT) To remodel the 5,967 sq ft basement area for a bakery with pastry kitchen and banquet room, per approved plans on file. Work to include, construction of partitions to create kitchen area, restrooms, storage, wine room and restrooms, Installation of a suspended ceiling system in the kitchen area, construction of two fully accessible restrooms, installation of kitchen equipment, sinks, oven type two hood systems. This basement was previously construted under separate permit, the shafts, Hvac system, Elevator, exit enclosure and street exits were all previously existing. This building is fully fire sprinklerd for one-hour supstitution, this building was determined for nonseparated uses for A2 occupany per section 302.3.2. Any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (PC#630-04) rmh
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 2/13/20062/13/2006 DONE
Details
BLD-Final4/4/20054/4/20054/4/2005PPART
DetailsDave Hannah
mathew; Phone #: ###-#### Internet Inspection Request from: Barbara Moore nok for temp occ ok for perm occ after elec go perm 4/4/2005 2:33:33 PM
FIRE-Final Inspection3/30/20053/31/20053/31/2005ACANC
DetailsForrest France
matthew pending bld fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
BLD-Final3/30/20053/31/20053/31/2005AFAIL
DetailsDave Hannah
matthew pending fire fn; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie needs ada restrooms finished and hand rails on stairs 3/31/2005 1:55:57 PM
FIRE-Final Inspection3/31/20053/31/20053/31/2005PPASS
DetailsForrest France
Fire final pass. Per certificates of occupancy provided by matthew total A occupancy is less than 300.
FIRE-Final Inspection3/29/20053/30/20053/30/2005AFAIL
DetailsTroy Cobbley
###-#### The relocated smoke detector in the basement did not operate and according to Alarmco the fire alarm panel has not contacted the monitoring company since Monday the 28th of March. The building manintenance guy has been notified 3/30/2005 9:53:14 AM
Code Occupancy Approval3/24/20053/23/20053/23/2005APASS
DetailsScott M.Brown
SIGNED OFF FINAL, WHY WE WERE ON SIGN OFF SHEET IS THE QUESTION. 3/24/2005 10:25:25 AM
FIRE-Final Inspection3/22/20053/22/20053/22/2005PFAIL
DetailsTroy Cobbley
mattew ; Phone #: ###-#### provide exit signs and emergency lights as shown on sheet e-2. Relocate smode detector to ceiling and test. Provide ceiling tile at sprinkler heads. Provide matching temp pendents in kitchen or provide reason. Provide approved door hardware as per approved drawings. This includes poket door, also remove thumb turn from office door. Provide verification of note 18. Repair exit light at top of exit at north stairs. 3/23/2005 10:14:53 AM
BLD-Framing/Rough-in12/9/200412/10/200412/10/2004PPASS
DetailsDave Hannah
brian; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie steel stud walls ok to cover 12/10/2004 2:21:51 PM