Permit Information
Permit NumberBLD04-02272
StatusFinaled
Name DAVE EVANS CONSTRUCTION
Site Address 1003 S ALLANTE PL
Project NameDIRECT MORTGAGE
Customer Number 
ePlanReviewNo
Description
Direct Mortgage (Tenant Improvement) - To finish a 4615 square foot office tenant space for Direct Mortgage. This tenant space is being finished at the east portion of a new 6,000 square foot shell building being constructed under building permit BLD04-02231. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection8/9/20058/10/20058/10/2005APASS
DetailsTroy Cobbley
life safety finaled
FIRE-Final Inspection8/8/20058/9/20058/9/2005AFAIL
DetailsTroy Cobbley
ben ; Phone #: ###-#### The hvac units still will not go into heat mode for testing. Sample tubes have been fixed.
FIRE-Final Inspection8/3/20058/4/20058/4/2005AFAIL
DetailsTroy Cobbley
Duct detectors have been relocated. Of the three detectors only the one located on the south unit has the sample tube facing the correct direction and shut down properly. The other two's sample tube are incorrectly placed and the units would not go into heat mode.
FIRE-Final Inspection8/3/20058/3/20058/3/2005PCANC
DetailsTroy Cobbley
robbie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD-Final7/26/20057/29/20057/29/2005PPASS
DetailsTom Arcoraci
ben; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok for perm occ when fire signs perm occ
FIRE-Final Inspection7/27/20057/28/20057/28/2005APART
DetailsTroy Cobbley
A temporary occupancy was given wit sam rogers permission until the three duct smoke detectors have been placed correctly and tested
FIRE-Final Inspection7/26/20057/27/20057/27/2005AFAIL
DetailsTroy Cobbley
Mount fire extinguishers as discussed. Change door hardware at restroom corridor to allow passage from corridor and along route as directed by exit signs. Test duct smoke detectors.
BLD-Energy code compliance6/1/20056/2/20056/2/2005APASS
DetailsMike Jordan
robbie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore