FIRE-Final Inspection | 8/9/2005 | 8/10/2005 | 8/10/2005 | A | PASS |
Troy Cobbley
|
|
|
life safety finaled
|
FIRE-Final Inspection | 8/8/2005 | 8/9/2005 | 8/9/2005 | A | FAIL |
Troy Cobbley
|
|
|
ben ; Phone #: ###-#### The hvac units still will not go into heat mode for testing. Sample tubes have been fixed.
|
FIRE-Final Inspection | 8/3/2005 | 8/4/2005 | 8/4/2005 | A | FAIL |
Troy Cobbley
|
|
|
Duct detectors have been relocated. Of the three detectors only the one located on the south unit has the sample tube facing the correct direction and shut down properly. The other two's sample tube are incorrectly placed and the units would not go into heat mode.
|
FIRE-Final Inspection | 8/3/2005 | 8/3/2005 | 8/3/2005 | P | CANC |
Troy Cobbley
|
|
|
robbie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Final | 7/26/2005 | 7/29/2005 | 7/29/2005 | P | PASS |
Tom Arcoraci
|
|
|
ben; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok for perm occ when fire signs perm occ
|
FIRE-Final Inspection | 7/27/2005 | 7/28/2005 | 7/28/2005 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given wit sam rogers permission until the three duct smoke detectors have been placed correctly and tested
|
FIRE-Final Inspection | 7/26/2005 | 7/27/2005 | 7/27/2005 | A | FAIL |
Troy Cobbley
|
|
|
Mount fire extinguishers as discussed. Change door hardware at restroom corridor to allow passage from corridor and along route as directed by exit signs. Test duct smoke detectors.
|
BLD-Energy code compliance | 6/1/2005 | 6/2/2005 | 6/2/2005 | A | PASS |
Mike Jordan
|
|
|
robbie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|