Permit Information
Permit NumberBLD04-02362
StatusFinaled
Name RA SCHULTZ AND COMPANY
Site Address 3363 N COLE RD
Project NameCOLE VILLAGE
Customer Number 
ePlanReviewNo
Description
(ON THE SPOT CLEANERS - COLE VILLAGE) This building is fire sprinklered for building area increase. To remodel an existing 4,296 square foot tenant space for a dry cleaning business. This project is a change of Occupancy Classification. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, interior doors, an interior window, suspended ceiling, and interior finishes all per the approved drawings and the plan review report on file. Also, the existing 867 square foot mezzanine will be demolished under this permit. The fire sprinkler system serving this tenant space shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/24/20052/25/20052/25/2005APASS
DetailsJim Sly
matt; Phone #: ###-#### Internet Inspection Request from: Barbara Moore OK for Perm Occ. 2/25/2005 8:12:23 AM
Permanent Occupancy 2/25/20052/25/2005 DONE
Details
BLD-Final2/23/20052/24/20052/24/2005ANR
DetailsJim Sly
matt; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD-Final2/18/20052/23/20052/23/2005PPART
DetailsJim Sly
Matt; Phone #: ###-#### or ###-#### jack Internet Inspection Request from: Jan Rice OK for Temp. 2/23/2005 3:55:39 PM
FIRE-Final Inspection2/22/20052/23/20052/23/2005ACANC
DetailsTroy Cobbley
Duplicate inspection. Finaled 2/22/2005 by 430 2/22/2005 12:41:14 PM
FIRE-Final Inspection2/18/20052/22/20052/22/2005APASS
DetailsTroy Cobbley
Life safety finaled 2/22/2005 12:18:47 PM
FIRE-Final Inspection2/14/20052/15/20052/15/2005AFAIL
DetailsTroy Cobbley
The existing corridor has been blocked off. Approved plans show door to be installed. Resubmit plans showing modifications. The exhaust ventilation system does not operate automatically. See IFC 1205.3 and IMC 502.5.2 2/15/2005 9:10:08 AM
FIRE-Conference1/27/20051/27/20051/27/2005APART
DetailsRick Jackson
Met with GC while testing the alarms - need sprinkler head in riser room; room created for fire alarm panel requires heat; complete fire alarm permit 1/27/2005 10:37:33 AM
FIRE-Final Inspection1/26/20051/27/20051/27/2005AFAIL
DetailsRick Jackson
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need resubmittals to show duct detectors on zone 8; need to test duct detectors as units did not shut down 1/27/2005 10:35:52 AM
BLD-Framing/Rough-in12/21/200412/22/200412/22/2004APASS
DetailsJim Sly
matt; Phone #: ###-#### Internet Inspection Request from: Barbara Moore