Permit Information
Permit NumberBLD04-02934
StatusFinaled
Name LYSTRUP/JENSEN ARCHITECTS
Site Address 10740 W FAIRVIEW AVE
Project NameDESERET INDUSTRIES
Customer Number 
ePlanReviewNo
Description
(DESERET INDUSTRIES) To construct a new a 20" x 90" covered exterior storage area on the southwest corner of the building per approved plans and DRH04-00282. This structure is being separated from the original building by a fire wall to separate to types of construction (new exterior structure to be a type VB the original building is a Type III-B) Work to include, installation of 3hr rated fire doors in CMU exterior walls, new foundation, slab, columns, beams and metal roof deck, ALSO under this permit an existing interior wall is being upgraded to a 1hr Fire barrier partition to limit the fire area so that the building alarm system does not have to be upgraded throughout the building only the retail area expansion. This building is fully fire sprinklered any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (rmh) (PLAN MODIFICATOIN: 3/28/05) THE ONE HOUR FIRE BARRIER HAS BEEN ILLIMINATED IN LIEU OF A COMPLETE FIRE ALARM SYSTEM BEING INSTALLED THROUGHOUT BUILDING. THE FOUR HOUR FIRE WALL THAT SEPARATES THE NEW EXTERIOR ADDITION FROM THE MAIN BUILDING HAS BEEN MODIFIED TO A 3HR FIRE WALL AS REQUIRED FOR TYPE OF CONSTRUCTION (RMH)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/6/200512/8/200512/8/2005PPASS
DetailsJim Sly
don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
C/C issued
DOC - Permit Finaled12/8/200512/8/200512/8/2005PPASS
DetailsJim Sly
DOC - Permit Finaled12/8/200512/8/200512/8/2005PPASS
DetailsJim Sly
DOC - Permit Finaled12/8/200512/8/200512/8/2005PPASS
DetailsJim Sly
DOC - Permit Finaled12/8/200512/8/200512/8/2005PPASS
DetailsJim Sly
FIRE-Final Inspection11/8/200511/9/200511/9/2005AFAIL
DetailsTroy Cobbley
need to final fire alarm and fire sprinkler, need to test exit signs and emergency lights, need to provide "Fire Door-Do Not Block" signs on both sides of both fire doors, provide door and exit hardware from the new storage area to the exterior as discussed.
FIRE-Final Inspection11/3/200511/8/200511/8/2005AFAIL
DetailsTroy Cobbley
Need fire alarm and fire sprinkler finaled. No items looked except the roll down doors which operated correctly.
FIRE-Final Inspection10/10/200510/10/200510/10/2005PFAIL
DetailsTroy Cobbley
fire sprinkler plans are still in review and fire alarm failed. No life safety inspection performed.
FIRE-Final Inspection10/7/200510/10/200510/10/2005AFAIL
DetailsTroy Cobbley
fire sprinkler plans are still in review and fire alarm failed. No life safety inspection performed.
BLD-Foundation9/7/20059/8/20059/8/2005APASS
DetailsJim Sly
don ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Letter from Eng. 2500 psi design No special insp Req. Wall taller than what shows on appr plan.......Eng letter OK'd change...... Need to add additional horiz bar.....inspected and Ok'd as instructed by Eng. Found wall OK.
BLD-Foundation9/1/20059/2/20059/2/2005AFAIL
DetailsJim Sly
foundation wall insp///don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
Footing poured W/O special insp 3000psi
C/N Need (stamped) letter from Eng of record reducing design strength of conc to 2500psi or less, or special insp required. Not accepting (unstamped) letter from Architect waiving special insp because project was simple and as no significance.
Verts (#4) lapped less than 40 dia. (approx 12" or less).
BLD-Footing8/31/20058/31/20058/31/2005PPART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 8/31/2005 at 9:12:34 AM. Contact: ###-####. Footing for new canopy at sw end of bldg. Approved plans call for special inspections. Informed contractor that special insp. was required.
FIRE-Sprinkler Rough-in8/16/20058/17/20058/17/2005PCANC
DetailsTroy Cobbley
don ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIRE-Conference8/10/20058/11/20058/11/2005ADONE
DetailsTroy Cobbley
Per sam rogers a temp would be acceptable if the existing fire alarm system provided adequate sound levels in the remodeled area. All other life safety items would need to be provided prior to the temporary occupancy being given
BLD-Conference8/8/20058/9/20058/9/2005ACANC
DetailsJim Sly
don ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Canc by Contr.
BLD-Footing8/5/20058/8/20058/8/2005PNR
DetailsJim Sly
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD-Framing/Rough-in7/5/20057/7/20057/7/2005APART
DetailsJim Sly
fire wall inspection///don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
Moved 3"abs out of 1hr wall....the remaining one needs framing perpendicular to wall and Firestopping device. Need UL listing for firestop (device). Call for insp of 1hr wall after all firestopping.
BLD-Framing/Rough-in6/27/20056/28/20056/28/2005AFAIL
DetailsJim Sly
don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa C/N......
Contractor to supply UL listed assembly for top connection of 3hr wall and plastic pipe penitration.