Permit Information
Permit NumberBLD05-00261
StatusFinaled
Name MEMMELAAR CONSTRUCTION
Site Address 8011 W USTICK RD
Project NameIDAHO HIGH SCHOOL ACTIVITIES
Customer Number 
ePlanReviewNo
Description
(IDAHO HIGH SCHOOL ACTIVITIES ASSOCIATION)(STORAGE AREA) To construct and enclose a new 481 sq. ft. storage area underneath a portion of an existing covered patio area of an existing 6,960 sq. ft. building per approved plans, CUP04-00139, and MOD#1/DRH04-00304. A fire life/safety inspection is to also be conducted for the entire building in order to obtain a Certificate of Occupancy for this building. Work to include new perimeter reinforced concrete grade beam to frost depth, new wood framed exterior walls, new exterior double doors, some new exterior siding, some interior finish work, and some electrical work. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building is not fire sprinklered. JCB
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Code Occupancy Approval  11/16/2005  
Final - OK. Meets compliance with CUP04-00139 (X-Ref CU85-92-Mod #1) and DRH04-00304
BLD-Final11/14/200511/15/200511/15/2005APASS
DetailsJim Sly
bill; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
OK for Perm Occ as far as Structural...... ():
Permanent Occupancy 11/15/200511/15/2005 DONE
Details
FIRE-Final Inspection11/14/200511/14/200511/14/2005PPASS
DetailsTroy Cobbley
Life safety finaled
FIRE-Final Inspection10/31/200510/31/200510/31/2005PFAIL
DetailsTroy Cobbley
Provide verification of the cfm rating for the roof top units and lower and tag the fire extinguisher in the storage room.
BLD-Final8/11/20058/12/20058/12/2005PNR
DetailsJim Storey
memmelaar; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa fire failled no insp. performed .
FIRE-Final Inspection8/11/20058/12/20058/12/2005AFAIL
DetailsTroy Cobbley
Provide emergency lighting in main corridor and lobby. See sheet A2.01. Provide emergency lighting in each of the conference rooms. See sheet A2.01. Provide exit discharge lighting at the three exits. Must be listed for outdoor/cold weather. See review note #10. Provide additional text for the occupant load sign, "Dividers closed 66".
Redduce storage height per note #13 (24"). Re-install hydraulic closers and provide gaskets on all doors in rated assemblies. Provide fire extinguisher for the new storage room. See note #3. Provide zoning and cfm information on the hvac system.
BLD-Final8/11/20058/11/20058/11/2005PNR
DetailsMike Jordan
herman; Phone #: ###-#### Note: if possible before 3:00 pm Internet Inspection Request from: Cathy Chiles. life/safety insp required.
BLD-Framing/Rough-in7/27/20057/27/20057/27/2005PPASS
DetailsJim Sly
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Left note.....May call for Conf insp for all other issues per scope of work.
BLD-Footing6/28/20056/30/20056/30/2005APASS
DetailsJim Sly
memmelaar construction; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
Foot and wall... OK