Permit Information
Permit NumberBLD05-00487
StatusFinaled
Name BOISE VARSITY BAR & GRILLE
Site Address 3201 W AIRPORT WAY
Project NameAIRPORT
Customer Number 
ePlanReviewNo
Description
(BOISE VARSITY BAR & GRILLE - BOISE AIR TERMINAL - ORIGINAL CONCOURSE B) This building is fire sprinklered to substitute for 1-hr fire-resistive construction. To construct a 1,842 square foot restaurant tenant space in the Southeast corner of "Original Concourse B" at the Boise Air Terminal. The former restaurant tenant spaces at this location will be demolished. Work is to include overhead coiling security grilles, interior nonbearing walls, suspended acoustical ceilings, gypsum board soffits, millwork, a grease hood, a side-hinged swinging egress door, and finishes. All work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with 2002 NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection4/17/20064/17/20064/17/2006 PASS
DetailsJim Storey
Permanent Occupancy 4/17/20064/17/2006 DONE
Details
BLD-Aging Inspection2/14/20062/14/20062/16/2006PNR
DetailsForrest France
Final pending completion of the concourse fire alarm upgrade to be inspected next month per conversation with contractor.
BLD-Aging Inspection2/14/20062/14/20062/14/2006 DEFR
DetailsJim Storey
to fire
BLD-Aging Inspection12/14/200512/14/200512/14/2005 NR
DetailsJim Storey
pending fire.
BLD-Final10/13/200510/14/200510/14/2005APART
DetailsJim Storey
Scheduled by a contractor via Hello! on 10/13/2005 at 1:10:27 PM. Contact: ###-####.temp ok plendig health sign off.
FIRE-Final Inspection10/12/200510/13/200510/13/2005PPART
DetailsTroy Cobbley
A temporary occupancy was given with Sam Rogers permission. The temp was given on the fire alarm system in the tenant space which is to be changed out to a new system with the concouse alarm upgrade. Sound levels on when the alarm was activated did not meet the 15db above ambient as per code. Life safety can be finaled when the alarm permit is finaled. I could not make "temporary" under the fire alarm permit since it is in the "review" status.
FIRE-Final Inspection10/10/200510/11/200510/11/2005AFAIL
DetailsTroy Cobbley
Mount max occupant load sign, Provide approved door hardware for "Store 105", provide verification of the cd rating of the temporary strobes so proper coverage can be verified and then test in the presence of the inspector. If this is done a temporary occupancy can be given by Sam Rogers permission
BLD-Final10/10/200510/11/200510/11/2005ACANC
DetailsJim Storey
Scheduled by a contractor via Hello! on 10/10/2005 at 11:38:55 AM. Contact: ###-####.
BLD-Final10/7/200510/7/200510/10/2005PNR
DetailsJim Storey
Scheduled by a contractor via Hello! on 10/7/2005 at 8:31:44 AM. Contact: ###-####.
BLD-Final10/7/200510/10/200510/10/2005ANR
DetailsJim Storey
Scheduled by a contractor via Hello! on 10/7/2005 at 5:49:43 PM. Contact: ###-####.
FIRE-Alarm Testing10/7/200510/7/200510/7/2005PFAIL
DetailsForrest France
Provide fire ext. with current inspection tag, provide max occupant load sign, relocate K class extinguisher as discussed, need to final fire sprinkler permit prior to bld final.
BLD-Framing/Rough-in8/8/20058/9/20058/9/2005APART
DetailsJim Storey
framing ok / need finsh welds at weld plats and justify truss loading.
BLD-Framing/Rough-in8/8/20058/8/20058/8/2005PPASS
DetailsJim Storey
Scheduled by a contractor via Hello! on 8/8/2005 at 8:04:20 AM. Contact: ###-####.