BLD-Final | 8/5/2005 | 8/8/2005 | 8/8/2005 | A | PASS |
Jim Sly
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa OK for Perm Occ. ():
|
Permanent Occupancy | | 8/8/2005 | 8/8/2005 | | DONE |
|
|
|
|
BLD-Final | 6/23/2005 | 6/23/2005 | 6/23/2005 | P | NR |
Jim Sly
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Barbara Moore All corrections completed. Just need Electrical to sign off for Perm Occ.......then Structural Perm Occ. OK
|
FIRE-Final Inspection | 6/16/2005 | 6/16/2005 | 6/16/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire life safety finaled
|
FIRE-Final Inspection | 6/14/2005 | 6/15/2005 | 6/15/2005 | A | FAIL |
Troy Cobbley
|
|
|
The correct remote annunciators have been installed and they operate correctly but when the duct detectors goes into alarm they do not shut down the hvac units.
|
BLD-Final | 6/13/2005 | 6/13/2005 | 6/13/2005 | P | PART |
Jim Sly
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa OK for Temp.... Need Fire and Electr final C/N Fill in holes at furnace room (1hr) walls
|
FIRE-Final Inspection | 6/10/2005 | 6/10/2005 | 6/10/2005 | P | PART |
Troy Cobbley
|
|
|
Temporary occupancy was given with sam rogers permission until the correct annunciator have been installed for the duct smoke detectors and tested.
|
BLD-Final | 6/8/2005 | 6/9/2005 | 6/9/2005 | P | NR |
Dave Hannah
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Need Plumb and fire sign off.... Electr now signed Temp. Mech pass.
|
FIRE-Final Inspection | 6/8/2005 | 6/9/2005 | 6/9/2005 | A | FAIL |
Troy Cobbley
|
|
|
No approved plans on site for inspection, no fire extinguisher, door hardware not correct, possiblity of needing duct smoke detectors.
|
BLD-Energy code compliance | 5/12/2005 | 5/13/2005 | 5/13/2005 | A | PASS |
Jim Sly
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
BLD-Framing/Rough-in | 5/11/2005 | 5/11/2005 | 5/11/2005 | P | PASS |
Jim Sly
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|