BLD-Final | 7/7/2005 | 7/7/2005 | 7/7/2005 | | DONE |
|
|
|
all corrections made ok.
|
Permanent Occupancy | | 7/7/2005 | 7/7/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | | | 7/7/2005 | | DONE |
|
|
|
|
FIRE-Final Inspection | 5/20/2005 | 5/23/2005 | 5/23/2005 | P | PASS |
Troy Cobbley
|
|
|
Life safety finaled
|
FIRE-Final Inspection | 4/22/2005 | 4/22/2005 | 4/22/2005 | P | PART |
Troy Cobbley
|
|
|
mark; Phone #: ###-#### New door at kitchen will be supplied within three weeks. Door between the bar and the elevator lobby has been removed. Per Mark this door is also being replace. This door and its hardware will be inspected with the new kitchen doo
|
FIRE-Final Inspection | 4/19/2005 | 4/19/2005 | 4/19/2005 | P | FAIL |
Troy Cobbley
|
|
|
Pocket doors to be locked open during business hours. Provide signage stating this at the doors. New door into kitchen does not meet IFC 1008.1.1. Provide emergency lighting at top of the north stairs. Test all other emergency lights in elevator lobby. Provide emergency lighting for the dance area. Provide ADA approved door hardware on kitchen door and on exit door between the bar and elevator lobby. See IFC 1008.1.8.1 and remove the dead bolt. Double doors (inactive leaf) from the dance area to the elevator lobby must be locked open during business hours. Provide signage stating this at the doors. Relocate exit sign to be above the active leaf.
|
BLD-Final | 4/15/2005 | 4/15/2005 | 4/15/2005 | P | PART |
Dave Hannah
|
|
|
Ok for temp. occupancy. No outstanding structural issues, need final sign-offs from all agencies prior to issuing final CO.
|