Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberBLD05-00855
StatusFinaled
Name THE LOFT
Site Address 622 W IDAHO ST
Project NameADELMAN BLDG-2ND FLR
Customer Number 
ePlanReviewNo
Description
(THE LOFT)(ADELMAN BLDG-2ND FLR) To remodel a 6,205 sq.ft. space for new restaurant/bar per approved plans. Work to include, constructoin of a noncombustible partition to remodel kitchen area, install new sink, miscelaneous interior finishes. This building is fully fire sprinklered for one hour substitution, any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (rmh)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final7/7/20057/7/20057/7/2005 DONE
all corrections made ok.
Permanent Occupancy 7/7/20057/7/2005 DONE
Details
DOC - Permit Finaled  7/7/2005 DONE
FIRE-Final Inspection5/20/20055/23/20055/23/2005PPASS
DetailsTroy Cobbley
Life safety finaled
FIRE-Final Inspection4/22/20054/22/20054/22/2005PPART
DetailsTroy Cobbley
mark; Phone #: ###-#### New door at kitchen will be supplied within three weeks. Door between the bar and the elevator lobby has been removed. Per Mark this door is also being replace. This door and its hardware will be inspected with the new kitchen doo
FIRE-Final Inspection4/19/20054/19/20054/19/2005PFAIL
DetailsTroy Cobbley
Pocket doors to be locked open during business hours. Provide signage stating this at the doors. New door into kitchen does not meet IFC 1008.1.1. Provide emergency lighting at top of the north stairs. Test all other emergency lights in elevator lobby. Provide emergency lighting for the dance area. Provide ADA approved door hardware on kitchen door and on exit door between the bar and elevator lobby. See IFC 1008.1.8.1 and remove the dead bolt. Double doors (inactive leaf) from the dance area to the elevator lobby must be locked open during business hours. Provide signage stating this at the doors. Relocate exit sign to be above the active leaf.
BLD-Final4/15/20054/15/20054/15/2005PPART
DetailsDave Hannah
Ok for temp. occupancy. No outstanding structural issues, need final sign-offs from all agencies prior to issuing final CO.