BLD-Final | 2/1/2011 | 2/2/2011 | 2/2/2011 | A | PASS |
Mike Jordan
|
|
|
chris Phone #: ###-####. All issues have been resolved. ok for perm. occ.
|
BLD-Final | 1/25/2011 | 1/26/2011 | 1/26/2011 | A | FAIL |
Jim Sly
|
|
|
chris Phone #: ###-#### C/N ..... Need min. 1 1/2" clearance between handrail and exterior wall.......Exterior stairway. Manager (Chris) said his notice and Order deadline is Feb 9th...and will try to get handrail and final inspection done before that date. He emmediately made a call to Contractor. and is going ahead in good faith to meet deadline.
|
FIRE-Final Inspection | 1/21/2011 | 1/25/2011 | 1/25/2011 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
FIRE-Final Inspection | 1/18/2011 | 1/19/2011 | 1/21/2011 | A | FAIL |
Troy Cobbley
|
|
|
The storage height for the sprinkler design has been exceeded. Chris is going to make adjustments and institute a height monitoring system for the rack storage. A re-inspection has been set up for next tuesday.
|
BLD-Aging Inspection | 11/26/2010 | 11/26/2010 | 11/30/2010 | P | DONE |
Troy Cobbley
|
|
|
Information has been forwarded to Jason Blais and Scott Arellano as per policy for aging permits.
|
BLD-Aging Inspection | 11/26/2010 | 11/26/2010 | 11/26/2010 | | PEND |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 6/14/2010 | 6/14/2010 | 6/14/2010 | | PEND |
Mike Jordan
|
|
|
|
FIRE-Final Inspection | 8/7/2009 | 8/11/2009 | 8/12/2009 | P | FAIL |
Troy Cobbley
|
|
|
All items except for the racking permit have been corrected. Jay is following up on getting the permit going.
|
FIRE-Conference | 3/16/2009 | 3/16/2009 | 3/16/2009 | A | DONE |
Troy Cobbley
|
|
|
Robert, with Sentry Security, had questions about how to incorporate new zones into the existing four zone fire alarm panel. I deferred him to the fire alarm plan reviewer.
|
FIRE-Final Inspection | 3/2/2009 | 3/3/2009 | 3/4/2009 | A | FAIL |
Troy Cobbley
|
|
|
All items have been addressed except for verification of the cfm for the hvac units, verification that the two fire doors are still functional and provide a racking permit for the steel storage racks that exceed 8'-0" and for any solid pile storage that exceeds 12'-0".
|
BLD-Aging Inspection | 2/25/2008 | 2/26/2008 | 2/27/2008 | A | FAIL |
Troy Cobbley
|
|
|
I did a walk through with Jay. Some of the correction items have been taken care of. See the print off of the job history that is in Jay's posession for items corrected and items still needing corrected.
|
BLD-Aging Inspection | 7/28/2006 | 7/28/2006 | 7/31/2006 | | NR |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 5/25/2006 | 5/25/2006 | 5/25/2006 | | CANC |
Mike Jordan
|
|
|
|
FIRE-Final Inspection | 8/3/2005 | 8/4/2005 | 8/4/2005 | A | FAIL |
Troy Cobbley
|
|
|
Contact: ###-####. Provide knox box per review note #1. Provide additional emergency light in the second floor corridor. Mount fire extinguisher on the second floor no higher than 48" to top of handle. Lower all fire extinguisher in warehouse to 48". Provide exit sign on second floor balcony as marked on sheet A2.0. Provide cfm information for all hvac units and areas served for possible duct smoke detector addition. Provide racking permits for all storage racks over 8' in height. Contact Bill Alexander for information. Provide smoke detector at the fire alarm panel. See approved drawings sheet A1.0 for locations of defiencies which include damaged fire doors and emergency lights/exit signs that need added or repaired. Several doors are also blocked by storage.
|
BLD-Final | 8/3/2005 | 8/4/2005 | 8/4/2005 | A | NR |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 8/3/2005 at 2:03:34 PM. Contact: ###-####. Need Fire final
|
BLD-Framing/Rough-in | 6/30/2005 | 6/30/2005 | 6/30/2005 | P | PART |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 9:07:50 AM. Contact: ###-####. grid ok
|
BLD-Framing/Rough-in | 6/6/2005 | 6/7/2005 | 6/7/2005 | A | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 6/6/2005 at 1:19:24 PM. Contact: ###-####.
|