BLD-Final | 7/14/2005 | 7/15/2005 | 7/15/2005 | A | PASS |
Dave Hannah
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for perm occ
|
FIRE-Final Inspection | 7/14/2005 | 7/15/2005 | 7/15/2005 | A | PASS |
Forrest France
|
|
|
Fire life safety passed inspection.
|
BLD-Final | 7/14/2005 | 7/14/2005 | 7/15/2005 | P | CANC |
Dave Hannah
|
|
|
|
Permanent Occupancy | | 7/15/2005 | 7/15/2005 | | DONE |
|
|
|
|
BLD-Final | 7/13/2005 | 7/14/2005 | 7/14/2005 | A | NR |
Dave Hannah
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore needs fire sign off and ada signage on restroom
|
BLD-Final | 7/14/2005 | 7/14/2005 | 7/14/2005 | A | CANC |
Dave Hannah
|
|
|
|
FIRE-Final Inspection | 7/13/2005 | 7/14/2005 | 7/14/2005 | A | FAIL |
Forrest France
|
|
|
Provide approved remote annunciator for attic HVAC smoke detector, provide the correct sign above main entry/exit, provide current annual inspection tags on fire extinguishers, remove all storage items in the basement- no storage or use of the basement allowed under this permit.
|
FIRE-Final Inspection | 7/13/2005 | 7/13/2005 | 7/13/2005 | P | FAIL |
Forrest France
|
|
|
Repair emergency light/exit sign at back door, test HVAC duct smoke detection devices, provide proper verbage on sign above door at main entry/exit, provide annual inspection tags on fire extinguishers, repair two exit signs at main entry, repair main exit discharge light.
|
BLD-Final | 7/13/2005 | 7/13/2005 | 7/13/2005 | P | CANC |
Dave Hannah
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa///Cancel per Larry///7/13/05 1:00pm BAS
|
BLD-Conference | 6/28/2005 | 6/29/2005 | 6/29/2005 | A | PART |
Dave Hannah
|
|
|
LARRY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles went over what he needs ot doe to get occ
|
FIRE-Final Inspection | 6/29/2005 | 6/29/2005 | 6/29/2005 | P | FAIL |
Forrest France
|
|
|
Door hardware not installed yet, exit signs and emergency lights not installed yet, HVAC needs smoke detection, no fire ext. installed yet, manual flush bolts on back exit door are not allowed, no building address posted, additional review needed when ready for inspection.
|
BLD-Framing/Rough-in | 6/15/2005 | 6/15/2005 | 6/16/2005 | P | PASS |
Dave Hannah
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to cover walls
|